k14 main cmte presentation 20100114

Upload: paulo-viana

Post on 06-Apr-2018

225 views

Category:

Documents


0 download

TRANSCRIPT

  • 8/3/2019 K14 Main Cmte Presentation 20100114

    1/39

    IEEE C37.234 Guide for Protective

    Relay Application to Power

    System Buses

    B.Kasztenny (Chairman), S.Conrad (Vice-Chairman),P.Beaumont, K.Behrendt, O.Bolado, J.Boyle, G.Brunello,

    J.Burger, F.Calero, S.Chano, G.Dalke, A.Darlington, H.DoCarmo,

    D.Fontana, Z.Gajic, J.Holbach, L.Kojovic, F.Lopez, D.Lukach,

    D.McGinn, J.Miller, P.Mysore, J.O'Brien, B.Pickett,

    S.Sambasivan, G.Sessler, V.Skendzic, J.Smith, D.Tholomier,

    M.Thompson, J.Uchiyama, D.Ware, D.Weers, R.Whittaker,

    R.Young, S.Zocholl

    Presentation to the Main Committee of PSRC, January 14, 2010, Orlando, FL

  • 8/3/2019 K14 Main Cmte Presentation 20100114

    2/39

    Table of Contents

    Definitions

    Bus configurations

    Introduction to bus protection

    Relay input sources

    Bus protection methods

    Application of bus protection schemes

    Annexes

  • 8/3/2019 K14 Main Cmte Presentation 20100114

    3/39

    Definitions

    23new terms defined

    Bus protection and primary equipment

    breaker substitution Temporary usage of a bus tie breaker in a

    multiple bus configuration to substitute for one of the networkelements circuit breakers, typically for the maintenance of the latter;

    also known as breaker transfer

    breaker substitution Temporary usage of a bus tie breaker in a

    multiple bus configuration to substitute for one of the networkelements circuit breakers, typically for the maintenance of the latter;

    also known as breaker transfer

    check zone Nonselective part of a multi-zone bus protection

    system measuring current flows around the entire station andsupervising selective tripping from individual bus zones of protection

    check zone Nonselective part of a multi-zone bus protection

    system measuring current flows around the entire station andsupervising selective tripping from individual bus zones of protection

    stub bus Area of a bus or line that becomes isolated from theoriginal zone of protection or an area that loses protection due to the

    loss of sensing to zone protection relays

    stub bus Area of a bus or line that becomes isolated from theoriginal zone of protection or an area that loses protection due to the

    loss of sensing to zone protection relays

  • 8/3/2019 K14 Main Cmte Presentation 20100114

    4/39

    Bus design considerations

    Continuity of service for the bus andessential network elements

    Equipment maintainability and network

    switching flexibility Economical and footprint constraints

    Sectionalizing requirements to avoid

    exceeding breaker fault duties

    Ease of future bus expansion

  • 8/3/2019 K14 Main Cmte Presentation 20100114

    5/39

    Bus arrangements

    Single bus

    Main and transfer bus

    Double-bus double-breaker

    Double-bus single-breaker

    Breaker-and-a-half

    Ring bus

  • 8/3/2019 K14 Main Cmte Presentation 20100114

    6/39

    Main and transfer bus

  • 8/3/2019 K14 Main Cmte Presentation 20100114

    7/39

    Main and transfer bus

  • 8/3/2019 K14 Main Cmte Presentation 20100114

    8/39

    Introduction to bus protection

    Zones of protection

    Bus protection methods

    Scheme selection guidelines

  • 8/3/2019 K14 Main Cmte Presentation 20100114

    9/39

    Zones of protection

  • 8/3/2019 K14 Main Cmte Presentation 20100114

    10/39

    Dynamic zones of protection

  • 8/3/2019 K14 Main Cmte Presentation 20100114

    11/39

    Dynamic zones of protection

  • 8/3/2019 K14 Main Cmte Presentation 20100114

    12/39

    Dynamic zones of protection

  • 8/3/2019 K14 Main Cmte Presentation 20100114

    13/39

    Zones of protection

    Over

  • 8/3/2019 K14 Main Cmte Presentation 20100114

    14/39

    Bus protection methods

    Differential Differentially-connected overcurrent

    Instantaneous

    Time-delayed

    Percentage-restrained differential

    Restrained

    Advanced microprocessor based

    High-impedance differential

    Resistor-stabilized overcurrent

    High-impedance

    Partial differential overcurrent

    Fault bus

  • 8/3/2019 K14 Main Cmte Presentation 20100114

    15/39

    Bus protection methods

    Zone-interlocked schemes

    Simple blocking

    Directional blocking

    Time-coordinated relays overlapping the bus

    Protection (sensors) built into the gas isolated

    switchgear*

    * Not covered in the Guide

  • 8/3/2019 K14 Main Cmte Presentation 20100114

    16/39

    Scheme selection criteria

    Bus arrangement and flexibility

    Fixed vs. switchable buses

    Availability and characteristics of CTs

    For reconfigurable buses, availability ofauxiliary contacts of disconnect switches

    Performance requirements

    Security, Selectivity, Speed, Sensitivity

    Cost and complexity

  • 8/3/2019 K14 Main Cmte Presentation 20100114

    17/39

  • 8/3/2019 K14 Main Cmte Presentation 20100114

    18/39

    Relay input sources

    Current transformers Types

    Accuracy classes

    Equivalent circuit & time to saturation

    No universal CT requirements

    Voltage Transformers

    Voltage trip supervision

    Directional blocking schemes

    Position of switches and breakers

  • 8/3/2019 K14 Main Cmte Presentation 20100114

    19/39

    Detailed scheme review

    Section 7 gives in-depth review of eachmethod following a consistent pattern

    Theory of operation

    Setting considerations

    CT requirements

    Application considerations

  • 8/3/2019 K14 Main Cmte Presentation 20100114

    20/39

    Example High-impedance scheme

    Voltage setting:

    Above the maximum voltage for an

    external fault assuming that one CT

    saturates completely

    High enough so that pickup current is

    above the short circuit current on thesecondary of any PT or station service

    transformer inside the bus zone

    Below the accuracy class voltage

    rating of the lowest accuracy class CT

    in the differential circuit

    Low enough so that pickup current is

    below the minimum fault current for

    the bus

  • 8/3/2019 K14 Main Cmte Presentation 20100114

    21/39

    Example High-impedance scheme

    CT requirements:

    CTs dedicated to bus protection

    (cannot be shared)

    Equal CT ratios*

    The accuracy class voltage rating ofthe CT with the lowest accuracy class

    above the selected voltage setting,

    with margin

    * Ratio matching covered but discouraged

  • 8/3/2019 K14 Main Cmte Presentation 20100114

    22/39

    Application of bus protection

    Partial differential Loads

    Capacitor banks

    Application with overcurrent and distance relays

    Combined bus and transformer zone

    Buses with directly connected grounding

    transformers

    Application of auxiliary transformers

    Generally discouraged

  • 8/3/2019 K14 Main Cmte Presentation 20100114

    23/39

    Application of bus protection

    Applications with paralleled CTs

    Generally discouraged

    Guidelines included

  • 8/3/2019 K14 Main Cmte Presentation 20100114

    24/39

    Application of bus protection

    Application of auxiliary tripping relays Lockout relays

    Non-lockout relays

    Ratings

    Automatic reclosing after bus faults

    Dynamic bus replica

    Check-zone

    Voltage trip supervision

  • 8/3/2019 K14 Main Cmte Presentation 20100114

    25/39

    Dynamic bus replica

  • 8/3/2019 K14 Main Cmte Presentation 20100114

    26/39

    Position of switches and breakers

    Auxiliary contacts Scheme output89a 89b Declared position Discrepancy alarm

    On Off Closed Normal

    Off On Opened Normal

    On On Closed Alarm

    Off Off Closed Alarm

    If not opened, then closed logic

  • 8/3/2019 K14 Main Cmte Presentation 20100114

    27/39

    In-service transfer

  • 8/3/2019 K14 Main Cmte Presentation 20100114

    28/39

    In-service transfer

  • 8/3/2019 K14 Main Cmte Presentation 20100114

    29/39

    In-service transfer

  • 8/3/2019 K14 Main Cmte Presentation 20100114

    30/39

    Check zoneCheck zone

  • 8/3/2019 K14 Main Cmte Presentation 20100114

    31/39

    Application of bus protection

    Application of CT trouble detection Detection methods

    Fallback strategies

    Reliable, selective tripping at thedifferential zone boundary

    Line-side CT

    Bus-side CT

    Bus coupler considerations

    The role of Breaker Failure protection

  • 8/3/2019 K14 Main Cmte Presentation 20100114

    32/39

    Line-side CT

    Bus

  • 8/3/2019 K14 Main Cmte Presentation 20100114

    33/39

    Bus coupler considerations

  • 8/3/2019 K14 Main Cmte Presentation 20100114

    34/39

    Bus coupler considerations

  • 8/3/2019 K14 Main Cmte Presentation 20100114

    35/39

    Application of bus protection

    CT column ground fault protection

    In-zone grounds

    Surge arresters

    Safety grounds and circulating current whiletesting

    In-zone grounding of out-of-service elements

    In-service transfer of network elementsand breaker substitution

  • 8/3/2019 K14 Main Cmte Presentation 20100114

    36/39

  • 8/3/2019 K14 Main Cmte Presentation 20100114

    37/39

    Application of bus protection

    Stub bus considerations

    Breaker Failure considerations

    Backup protection

    Local backup

    Duplicated relays

    BF, batteries, wiring

    Reverse-looking distance relays

    Overcurrent relays

    Remote backup

  • 8/3/2019 K14 Main Cmte Presentation 20100114

    38/39

    Annexes

    Setting example for a high-impedance

    scheme (AnnexA)

    Logic example for double-bus single-

    breaker configuration (Annex B) Bus and Breaker Failure protection

    Two zones, check zone and voltage supervision

    In-service transfers and breaker substitution

    Setting guidelines for differentially

    connected OC schemes (Annex C)

  • 8/3/2019 K14 Main Cmte Presentation 20100114

    39/39