dig silent

21
DIgSILENT GridCode: LVRT in Spain with DIgSILENT GridCode DIgSILENT Ibérica Madrid, 15 February 2012

Upload: ever-fuentes

Post on 14-Oct-2014

223 views

Category:

Documents


3 download

TRANSCRIPT

Page 1: Dig Silent

DIgSILENT GridCode:

LVRT in Spain with

DIgSILENT GridCode

DIgSILENT Ibérica Madrid, 15 February 2012

Page 2: Dig Silent

DIgSILENT Ibérica S.L. 2

Spanish Study Case

Grid Code in Spain, published by the TSO Red Eléctrica de España:

“PROCEDIMIENTO DE OPERACIÓN 12.3: REQUISITOS DE RESPUESTA FRENTE A HUECOS DE TENSIÓN DE LAS INSTALACIONES EÓLICAS”

In revision:

“PROCEDIMIENTO DE OPERACIÓN 12.2: INSTALACIONES CONECTADAS A LA RED DE TRANSPORTE: REQUISITOS MÍNIMOS DE DISEÑO, EQUIPAMIENTO, FUNCIONAMIENTO Y SEGURIDAD Y PUESTA EN SERVICIO”

The document can be found at the website:

http://www.ree.es/operacion/procedimientos_operacion.asp

New version Nr 10 of the Spanish Wind Energy Association document (PVVC_v10) is published in response to the revision of the Spanish Grid Code (P.O.12.3 and draft version of P.O.12.2):

“PROCEDIMIENTOS DE VERIFICACIÓN, VALIDACIÓN Y CERTIFICACIÓN DE LOS REQUISITOS DEL P.O.12.3 SOBRE LA RESPUESTA DE LAS INSTALACIONES EÓLICAS Y FOTOVOLTAICAS ANTE HUECOS DE TENSIÓN”

The document can be found at the website:

http://www.aeeolica.org/

Page 3: Dig Silent

DIgSILENT Ibérica S.L. 3

Example of Dynamic Simulation Testing Procedure

Example of Dynamic Simulation Testing Procedure

STEP 1: Building the Wind farm dynamic model in DIgSILENT PowerFactory 14.1.2

NOTE: this example is built using templates in the global library;

Doubly Fed Induction Generators rated 6MW DFIG_WTG_6MW

Wind Farm Rated Power: 60MVA

Wind Farm Rated Voltage: 220kV

Page 4: Dig Silent

DIgSILENT Ibérica S.L. 4

Example of Dynamic Simulation Testing Procedure

STEP 2: Simulation of LVRT events according to the Spanish Grid Code:

EMT simulation - 10kHz time step

Voltage dip location: at the Wind Farm PCC, 220kV side

Voltage dip depth: 20% (3PH), 60% (2PH)

Voltage dip length: 500ms

Page 5: Dig Silent

DIgSILENT Ibérica S.L. 5

Example of Dynamic Simulation Testing Procedure

STEP 3: Export required signals from Plots in PowerFactory:

Ua(t), Ub(t), Uc(t) kV

Ia(t), Ib(t), Ic(t) kA

Textfile, white space/tab separated format

Voltage dip 60% (2PH) Voltage dip 20% (3PH)

Page 6: Dig Silent

DIgSILENT Ibérica S.L. 6

Example of Dynamic Simulation Testing Procedure

STEP 4: Analysis with DIgSILENT GridCode, checking for compliance.

STEP 4.1: File Types & Channels to read the results file.

Page 7: Dig Silent

DIgSILENT Ibérica S.L. 7

Example of Dynamic Simulation Testing Procedure

STEP 4: Analysis with DIgSILENT GridCode, checking for compliance.

STEP 4.1: File Types & Channels to read the results file.

STEP 4.2: Input of base values 60MVA and 220kV

Page 8: Dig Silent

DIgSILENT Ibérica S.L. 8

Example of Dynamic Simulation Testing Procedure

STEP 4: Analysis with DIgSILENT GridCode, checking for Grid Code compliance.

STEP 4.1: File Types & Channels to read the results file.

STEP 4.2: Input of base values 60MVA and 220kV

STEP 4.3: With the GridCode Editor, add the new procedure in the Spanish Grid Code (PVVC_v10_general).

Page 9: Dig Silent

DIgSILENT Ibérica S.L. 9

Example of Dynamic Simulation Testing Procedure

STEP 4: Analysis with DIgSILENT GridCode, checking for Grid Code compliance.

STEP 4.1: File Types & Channels to read the results file.

STEP 4.2: Input of base values 60MVA and 220kV

STEP 4.3: With the GridCode Editor, add the new procedure in the Spanish Grid Code (PVVC_v10_general).

- Add the zones and edit them. Add the list of limits for the different series.

Page 10: Dig Silent

DIgSILENT Ibérica S.L. 10

Example of Dynamic Simulation Testing Procedure

STEP 4: Analysis with DIgSILENT GridCode, checking for Grid Code compliance.

STEP 4.1: File Types & Channels to read the results file.

STEP 4.2: Input of base values 60MVA and 220kV

STEP 4.3: With the GridCode Editor, add the new procedure in the Spanish Grid Code (PVVC_v10_general).

- Edit the voltage dip shape for balanced dips.

Page 11: Dig Silent

DIgSILENT Ibérica S.L. 11

Example of Dynamic Simulation Testing Procedure

STEP 4: Analysis with DIgSILENT GridCode, checking for Grid Code compliance.

STEP 4.1: File Types & Channels to read the results file.

STEP 4.2: Input of base values 60MVA and 220kV

STEP 4.3: With the GridCode Editor, add the new procedure in the Spanish Grid Code (PVVC_v10_general).

- Edit the voltage dip shape for unbalanced dips.

Page 12: Dig Silent

DIgSILENT Ibérica S.L. 12

Example of Dynamic Simulation Testing Procedure

STEP 4: Analysis with DIgSILENT GridCode, checking for Grid Code compliance.

STEP 4.1: File Types & Channels to read the results file.

STEP 4.2: Input of base values 60MVA and 220kV

STEP 4.3: With the GridCode Editor, add the new procedure in the Spanish Grid Code (PVVC_v10_general).

- Edit the voltage support requirements.

Page 13: Dig Silent

DIgSILENT Ibérica S.L. 13

Example of Dynamic Simulation Testing Procedure

STEP 4: Analysis with DIgSILENT GridCode, checking for Grid Code compliance.

STEP 4.1: File Types & Channels to read the results file.

STEP 4.2: Input of base values 60MVA and 220kV

STEP 4.3: With the GridCode Editor, add the new procedure in the Spanish Grid Code (PVVC_v10_general).

- Define the plots that you want display.

- Select “Checked” option to display it.

- Save the Grid Code.

Page 14: Dig Silent

DIgSILENT Ibérica S.L. 14

Example of Dynamic Simulation Testing Procedure

STEP 4: Analysis with DIgSILENT GridCode, checking for Grid Code compliance.

STEP 4.1: File Types & Channels to read the results file.

STEP 4.2: Input of base values 60MVA and 220kV

STEP 4.3: With the GridCode Editor, add the new procedure in the Spanish Grid Code (PVVC_v10_general).

STEP 4.4: Click Analyze

Page 15: Dig Silent

DIgSILENT Ibérica S.L. 15

Example of Dynamic Simulation Testing Procedure

RESULTS

In the second tab, a table summarizes the fulfillment of requirements in Zones A, B, C and D.

THE “OK?” OPTION ACTIVATED MEANS THAT THE REQUIREMENT IS FULFILLED

Page 16: Dig Silent

DIgSILENT Ibérica S.L. 16

Example of Dynamic Simulation Testing Procedure

RESULTS

The “REE Voltage Dip Shape” graph allows to check if the voltage dip is “inside” the voltage dip rms envelope the wind farm can not disconnect and must provide reactive current support.

Voltage dip 60% (2PH) Voltage dip 20% (3PH)

Page 17: Dig Silent

DIgSILENT Ibérica S.L. 17

Example of Dynamic Simulation Testing Procedure

RESULTS

The “Ir/Itot(Vrms) Zone B” graph allows to check if the wind farm is injecting or consuming reactive power and fulfilling the requirements established by REE on the reactive current during the dip.

Voltage dip 60% (2PH) Voltage dip 20% (3PH)

Page 18: Dig Silent

DIgSILENT Ibérica S.L. 18

Example of Dynamic Simulation Testing Procedure

RESULTS

The “Power” graph allows to check the restoration of active power of the wind farm after the voltage dip.

Voltage dip 60% (2PH) Voltage dip 20% (3PH)

Page 19: Dig Silent

DIgSILENT Ibérica S.L. 19

Example of Dynamic Simulation Testing Procedure

REPORTING

Results are reported in Word format.

Page 20: Dig Silent

DIgSILENT Ibérica S.L. 20

Example of Dynamic Simulation Testing Procedure

REPORTING

Results are reported in Word format.

Page 21: Dig Silent

21

DIgSILENT GridCode Contact

Ana Morales/Xavier Robe

DIgSILENT Ibérica S.L.

Ribera del Loira, 46

28042 Madrid – Spain

Phone: +34 911273723/24

Email:

[email protected]

[email protected]

Website:

www.digsilent.com