unidades paquete zp de l marca carrier 1

Upload: francisco-can

Post on 07-Aug-2018

215 views

Category:

Documents


0 download

TRANSCRIPT

  • 8/20/2019 Unidades Paquete Zp de l Marca Carrier 1

    1/20

    Single Package Air-ConditioningUnits with:• easy installation design• corrosion-proof basepan• pre-painted steel cabinet

    • sloped drain pan for improvedindoor air quality

    • top cover service access• lightweight, compact constructio

    Features/BenefitCompact, horizontal supplyand return unit, combin-ing easy installation andmaintenance with efficientperformance.

    E a s y t o in s t a ll

    T he 5 0 ZP units are sm all, com pact, ae a sy to h a n d le . E v e ry 5 0 Z P u n it h a san iden tical3 2 x 5 1 -in. foo tp rin t tom ake job site plann ing sim p le. T he cocise design uses less sh eet m etal an dm akes the 5 0 Z P un its ligh ter than othun its.T h e un it can be easily p o sitio n edon the jo bsite w ith th e h an d h olds buinto the un it basep an . D rop -in car-trid ge style h ea ters are u tilized to m inm ize in stallatio n tim e. T h e 5 0 Z P un itw a s de sign ed w ith p o ten tial safety h aa rd s in m in d . T h e re a re n o sh a rp e d gor corners w h ich cou ld injure a w o rker

    To p c o v e r s e r v ic e a c c e s s

    T he 5 0 ZP units are designed to be seviced from the top . T h e split-top de-sign allo w s ea sy ac cess fo r in stallatio nand m aintenance procedures o n theun it. R ou tine m ainten an ce tasks suchcoilclean ing are sp ed up w ithth ro ug h -th e-to p acce ss. M ultip le sidep a n e ls d o n o t n e e d to b e re m o v ed a sw ith o th er un its.

    ProductData

    50ZPSingle-Package Electric

    Cooling Units

    2 to 5 Nominal Tons

    Copyright 1997 Carrier Corporation Form 50ZP-

  • 8/20/2019 Unidades Paquete Zp de l Marca Carrier 1

    2/20

    N o - r u s t b a s e p a n w i t hin t e g r a t e d d r a in p a nT he 5 0 ZP units feature a tough , high-tech, com p osite m aterial basep an w ithintegrated drain p an . T h e com p ositem aterial elim in ates th e p o ten tial p ro b-lem s o f rustan d p rem ature rep lacem entw h ich are com m on w ith standard m etalbasepans.

    E a c h 5 0 Z P b a se p a n is slo p e d toelim inate stand ing w ater p er A S H R A ES tandard 6 2 -8 9 .

    D u r a b le p r e - p a in t e d s t e e lc a b i n e tT h e w atertigh t con structio n an dco rro sio n -resistan t n ish o f th e 5 0 Z Pun it w ill kee p it lo o kin g like n ew fo ryea rs. C arrier’s p ain t trea tm en t p ro cessen sures qu ality p ro tectio n ag ain st th eelem en ts.A com p act, lo w -p ro le designutilizes a lo uve red co il en clo sure fo rp ro tectio n ag ain st van da lism an d h aild a m a g e.

    Indoor-air qualityA slop ed drain pa n m inim izes theam ou nt of stand ing w ater inside theun it, w h ich lim its alga e grow th . T h edrain pa n is m ade of a rust-p roo f m ate-rial an d w ill n o t de terio rate o r releasefo reign m atter in to th e co n ditio n ed air.

    Lightweight, com pactc o n s t r u c t i o nT he 5 0 ZP unit is the lightest, m ostcom -pact packaged unit that C arrier hasever design ed. Its ligh t w eigh t (2 2 2 lbsfo r th e 5 0 Z P 0 2 4 u n it) m a k e s th e u n iteasier to han dle. T he low heigh t (2 2 -in.fo r 5 0 Z P 0 2 4 -0 3 6 , 3 0 -in . fo r 5 0 Z P 0 4 2 ,0 4 8 , a n d 3 4 -in . fo r 5 0 Z P 0 6 0 u n its)k e e p s d u c tw o rk to a m in im u m a n dm ak es th e un it less visible.

    E ffi c ie n t , d e p e n d a b lep e r f o r m a n c eT h e 5 0 Z P u n its o ffe r 1 0 .0 S E E R (S e a -son alE nergy E f ciency R ate)coo lingp erform ance ef ciencies. T his high p er-fo rm an ce levelcan redu ce coo ling ex-p e n se s by a s m u c h a s 2 5 % co m p a re d toolder coo ling equip m ent (dep end ing onlo cal clim ate co n ditio n s). A h igh -ef ciency, m ulti-spe ed blow er m otorsystem en sures qu ality p erfo rm an ce w ithm ostduct system s. T he com puter-design ed blow er w heel is balanced forqu iet o p eratio n .

    R u g g e d , r e l ia b l ec o n s t r u c t i o nT h e 5 0 Z P un its u tilize a structuralb eamdesign to form the fou r sides o f thecabin et. O nly 1 2 differen t p ieces of she et

    m etal are used in th e un it con structio nto sim p lify th e un it fo r g rea ter reliab ility.T h e 5 0 Z P un its are built to last.

    D u r a b l e , d e p e n d a b lec o m p o n e n t sC o m p r e s s o r s   are design ed for highef ciency. E ach com p ressor is h erm eti-cally sealed ag ain st co n tam in atio n tohelp p rom ote lon ger life and dep end able

    o p eratio n . V ibratio n isolatio n p ro vide squ iet op eration . R ecip ro catin g com p res-sors h ave in ternal h igh -p ressure an do vercurren t p ro tectio n .

    D ir e c t -d r i ve m u l t is p e e d , P S C (p e r -m a n e n t s p l it c a p a c i t o r ) b l o w e rm o t o r   is stan dard on allm o dels.

    Dir ect- dr ive, PSC condenser - f anm o t o r s   are design ed to h elp redu ceenergy con sum ption and p rovide forcooling op eration dow n to 4 0 F.

    R e fr ig e r a n t s y s t e m   is d esign ed top ro vide de p en da bility. L iqu id refrige ran tstraine rs are used to p ro m ote clean ,un restricted o p eratio n . E ach un it leave sth e facto ry w ith a full refrige ran t ch arge.R efrigerant service con ne ctio ns m akech eckin g o p eratin g p ressures easier.

    Model number nomenclature

    Table of contents P a g eFeatures/B ene ts ...... ...... ....... ...... ...... ...... ...... ...... .. 1 ,2M o d e l N u m b e r N o m e n c la tu re . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2A R I C a p a c ity R a tin g s . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3P h y sic al D a ta . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3A ccessories ...... ....... ...... ...... ...... ...... ...... ...... ...... 4 ,5B a se U n it D im e n sio n s . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6 -8S election P rocedure ...... ...... ...... ...... ....... ...... ...... ...... . 9P e rfo rm a n c e D a ta . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 0 -1 4E lectricalD ata ...... ....... ...... ...... ...... ...... ...... ...... .... 1 5C o n tro ls . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 6T ypicalInstallation ..... ... ... ... ... .... ... ... ... ... ... ... ... ... ... .. 1 7T ypicalW iring D iagram ....... ...... ...... ...... ...... ...... ...... . 1 7 ,1 8G u id e S p e ci c atio n s . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 9 ,2 0

    2

  • 8/20/2019 Unidades Paquete Zp de l Marca Carrier 1

    3/20

    ARI* capacity ratings

    UNIT 50ZP  NET COOLING CAPACITY†

    (Btuh)  STANDARD CFM SEER**

      SOUND RATING††(dB)

    024   22,800 800 10.0 80

    030   30,000 1000 10.0 84

    036   34,200 1200 10.0 84

    042   40,000 1400 10.0 84

    048   46,000 1600 10.0 84

    060   57,000 2000 10.0 84LEGEND

    db —   Dry BulbdB —   decibels (10 decibels = 1 bel)SEER —   Seasonal Energy Efficiency Ratiowb —   Wet Bulb

    *Air Conditioning and Refrigeration Institute.†Rated in accordance with U.S. Government DOE (Department of Energy) test

    procedures and/or ARI Standard 210/240-89.**All units have factory-installed time-delay relay.

    ††Rated in accordance with ARI Standard 270-84.

    NOTES:1. Ratings are net values, reflecting the effects of circulating fan heat.2. Cooling Capacity Ratings are based on cooling standard:

    80 F db/67 F wb indoor air entering temperature95 F db air entering outdoor unit

    Physical dataUNIT 50ZP 024 030 036 042 048 060

    OPERATING WEIGHT (lb)   222 236 250 297 310 350

    COMPRESSOR TYPE   Reciprocating

    REFRIGERANT   R-22Charge (lb)   3.0 3.9 4.7 4.4 6.1 7.5

    REFRIGERANT METERING DEVICE   Acutrol™ System

    CONDENSER   Copper Tubes, Aluminum Plate FinsRows...Fins/in.   1...17 1...17 2...17 1...17 2...17 2...17Total Face Area (sq ft)   7.9 7.9 6.2 11.1 8.6 10.7

    CONDENSER FAN   Propeller

    CFM   1600 2000 2000 2600 2600 2800Nominal Rpm   825 1100 1100 1100 1100 1100Motor Hp   1 ⁄ 8   1 ⁄ 4   1 ⁄ 4   1 ⁄ 4   1 ⁄ 4   1 ⁄ 4Diameter (in.)   20 20 20 20 20 20

    EVAPORATOR COIL   Copper Tubes, Aluminum Plate FinsRows...Fins/in.   2...15 3...15 3...15 3...15 3...15 4...15Total Face Area (sq ft)   3.1 2.8 3.1 3.9 4.3 4.9

    EVAPORATOR FAN MOTOR   Direct DriveBlower Motor Size (in.)   10 x 8 10 x 8 10 x 8 10 x 9 10 x 9 10 x 10Nominal Cfm   800 1000 1200 1400 1600 2000Rpm Range   550-1000 550-1000 800-1050 800-1050 1000-1100 950-1100Number of Speeds   3 3 3 3 2 3*Factory Speed Setting   Low Med Low Med Low LowMotor Hp   1 ⁄ 4   1 ⁄ 4   1 ⁄ 2   1 ⁄ 2   3 ⁄ 4   1

    CONNECTING DUCT SIZES   Round SquareSupply Air (in.)   14 13.9 x 13.9Return Air (in.)   14 13.9 x 27.8

    FIELD-SUPPLIED RETURN AIR FILTER†Throwaway (in.)   24 x 24 24 x 24 24 x 24 24 x 24 24 x 30 24 x 30

    *460-v motors are 2-speed only.†Required filter sizes shown are based on the ARI (Air Conditioning and Refrigeration Institute) rated

    airflow at a velocity of 300 ft/min for throwaway type or 450 ft/min for high capacity type. Recom-mended filters are 1-in. thick.

  • 8/20/2019 Unidades Paquete Zp de l Marca Carrier 1

    4/20

    Accessories

    ACCESSORY

    Outdoor Thermostat

    Crankcase Heater (230-1-60)

    Thermostat and Subbase

    Electronic Programmable Thermostat

    Controls Upgrade Kit

    Time Guard II Kit

    Low-Ambient Kit

    Electric Heat with Single-Point Kit (5.0 to 20.0 kW)

    E l ect r o n i c p r o g r ammab l e t h er mo s t at   p ro vide s 2 -stag ehe atin g an d 2 -stage coo lin g con trol w ith rem o te com m un i-ca tio n ab ility.

    T he r m o s t a t a n d s u b b a s e   p ro vide he atin g an d coo lingun it con trol. T he subb ase p ro vides system an d fan sw itch-in g at th e th erm o stat lo catio n .

    Lo w -am b i en t k it (Mo t o r m as t e r   II device)   a llo w s th eu se o f m e c h a n ic a l c o o lin g d o w n to o u td o o r a m b ie n t te m -p e ra tu re s a s lo w a s 0 ° F .

    Solid-state Time Guard II device   p rotects com p resso rby p reven tin g sho rt cyclin g.

    C r a n k c a s e h e a t e r   w arm s cran kcase o il to redu ce refrig-eran t m igratio n an d en sure p ro p er com p ressor lubrication .(R ecom m end ed on 2 0 8 /2 3 0 -v sing le-p hase un its in sizes0 2 4 -0 4 2 o n ly .)

    E lect r i c h ea t er s   p rovide heat in the un it w h en required.E a c h p a c k a g e h a s a h e a te r m o d u le th a t slid e s in to k e y e d

    m o un tin g slo ts in th e fan in let. H eater sizes ran ge fro m 5 .0to 2 0 .0 kW . T he electric heater design allow s the use of asin gle-p o in t p o w er sup p ly fo r th e en tire un it, resultin g inlo w er in stalled co sts.

    C o n t r o l s u p g r ad e k i t i n cl u d es   high - an d low -p ressuresw itche s w h ich p ro vide ad ditio n al safety features an d p ro -tect th e un it fro m run n in g at un suitab le p ressures.

    O u t d o o r t h e r m o s t a t   brin gs secon d stage o f 2 -stag e elec-tric h eater o n lin e w h en th e o utdo o r-air tem p erature fallsbelow th e set p oint.

    ELECTRIC HEATERS

    ODS CATALOGORDERING NO. NOMINALCAPACITY (kW)USED WITH SIZES

    024 030 036 042 048 060

    ELECTRIC HEATERS (208/230 — SINGLE PHASE — 60 Hz)

    CPHEATER026A00   5.0 X X X X

    CPHEATER039A00   10.0 X X X X

    CPHEATER025A00   15.0 X X X X

    CPHEATER027A00   20.0 X X X X

    ELECTRIC HEATERS (208/230 V — 3 PHASE — 60 Hz)

    CPHEATER029A00   5.0 X X X X

    CPHEATER030A00   10.0 X X X X

    CPHEATER031A00   15.0 X X X X

    CPHEATER033A00   20.0 X X X X

    ELECTRIC HEATERS (460 V — 3 PHASE — 60 Hz)

    CPHEATER034A00   5.0 X

    CPHEATER035A00   10.0 XCPHEATER036A00   15.0 X

    CPHEATER037A00   20.0 X

    LEGEND

    OD S —   Order Distribution System

    NOTE: Electric heaters are rated at 240 v and 480 v. Refer to Multiplication Factors table on page 5 for other voltages.

    4

  • 8/20/2019 Unidades Paquete Zp de l Marca Carrier 1

    5/20

    THERMOSTATS AND SUBBASES

    ODS CATALOGORDERING NO.

      DESCRIPTION

    TSTATCCN2S01-A   Automatic Changeover — 3 Heat/2 Cool (Programmable Residential Thermostat)

    TSTATCCP2S01-A   Automatic Changeover — 3 Heat/2 Cool (Non-Programmable Residential Thermostat)

    33CSPTN-01   Automatic Changeover — 2 Heat/2 Cool (Programmable Commercial Thermostat)

    --HH01AD-45   Manual Changeover — 2 Heat/1 Cool (Non-Programmable Thermostat)

    LEGEND

    ODS —   Order Distribution System

    MULTIPLICATION FACTO RS

    HEATER kWRATING

    VOLTAGEDISTRIBUTION

    V/3/60

    MULTIPLICATIONFACTOR

    240

    200 .69208 .75230 .92240 1.00

    480440 .84460 .92480 1.00

    Example: 15.0 kW (at 240 v) heater on 208 v= 15.0 (.75 mult factor)= 11.25 capacity at 208 v

  • 8/20/2019 Unidades Paquete Zp de l Marca Carrier 1

    6/20

    Base unit dimensions — 50ZP024-036

    UNIT  ELECTRICAL

    CHARACTERISTICS

    UNIT WT CENTER OF GRAVITY mm (in.)

    Lb Kg X Y Z

    50ZP024   208/230-1-60 222 101 355.6 (14.00) 508.0 (20.00) 241.3 (9.50)50ZP030   208/230-1-60 236 107 355.6 (14.00) 508.0 (20.00) 241.3 (9.50)50ZP036   208/230-1-60, 208/230-3-60 250 114 355.6 (14.00) 508.0 (20.00) 241.3 (9.50)

    REQUIRED CLEARANCES TO COMBUSTIBLE MAT’L

    Millimeters (in.)

    Top of Unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 0D uc t S id e o f U nit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 0S id e Opp os ite Du cts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 0B o tto m o f U n i t . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 0

    NEC REQUIRED CLEARANCES

    Millimeters (in.)

    Between Units, Power Entry Side . . . . . . . . . . . . . . . . . 1066.8 (42.00)Unit and Ungrounded Surfaces, Power Entry Side . . . . . . . 914.0 (36.00)Unit and Block or Concrete Walls and Other Grounded

    Surfaces, Power Entry Side . . . . . . . . . . . . . . . . . . . . 1066.8 (42.00)REQUIRED CLEARANCES FOR SERVICING

    Millimeters (in.)

    Condenser Coil Access Side . . . . . . . . . . . . . . . . . . . . . 762.0 (30.00)Power Entry Side . . . . . . . . . . . . . . . . . . . . . . . . . . . . 762.0 (30.00)

    (Except for NEC Requirements)Unit Top . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 914.0 (36.00)Side Opposite Ducts . . . . . . . . . . . . . . . . . . . . . . . . . . 762.0 (30.00)

    LEGEND

    CG —   Center of GravityN EC —   National Electrical Code

    NOTES:1. Clearances must be maintained to prevent recirculation of air from outdoor-

    fan discharge, with the exception of the condenser coil (914 mm [36 in.]). Aremovable fence or barricade requires no clearance.

    2. Dimensions are in millimeters. Dimensions in ( ) are in inches.

    6

  • 8/20/2019 Unidades Paquete Zp de l Marca Carrier 1

    7/20

    Base unit dimensions — 50ZP042,048

    UNIT  ELECTRICAL

    CHARACTERISTICS

    UNIT WT CENTER OF GRAVITY mm (in.)

    Lb Kg X Y Z

    50ZP042   208/230-1-60, 208/230-3-60 297 135 355.6 (14.00) 508.0 (20.00) 304.8. (12.00)50ZP048   208/230-1-60, 208/230-3-60 310 141 355.6 (14.00) 508.0 (20.00) 304.8 (12.00)

    REQUIRED CLEARANCES TO COMBUSTIBLE MAT’L

    Millimeters (in.)

    Top of Unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 0D uc t S id e o f Un it . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 0Side Opposite Ducts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 0B o tto m o f U n i t . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 0

    NEC REQUIRED CLEARANCES

    Millimeters (in.)

    Between Units, Power Entry Side . . . . . . . . . . . . . . . . . 1066.8 (42.00)Unit and Ungrounded Surfaces, Power Entry Side . . . . . . . 914.0 (36.00)Unit and Block or Concrete Walls and Other Grounded

    Surfaces, Power Entry Side . . . . . . . . . . . . . . . . . . . . 1066.8 (42.00)REQUIRED CLEARANCES FOR SERVICING

    Millimeters (in.)

    Condenser Coil Access Side . . . . . . . . . . . . . . . . . . . . . 762.0 (30.00)Power Entry Side . . . . . . . . . . . . . . . . . . . . . . . . . . . . 762.0 (30.00)

    (Except for NEC Requirements)U nit To p . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 91 4.0 (36 .0 0)Side Opposite Ducts . . . . . . . . . . . . . . . . . . . . . . . . . . 762.0 (30.00)

    LEGEND

    CG —   Center of GravityN EC —   National Electrical Code

    NOTES:1. Clearances must be maintained to prevent recirculation of air from outdoor-

    fan discharge, with the exception of the condenser coil (914 mm [36 in.]). Aremovable fence or barricade requires no clearance.

    2. Dimensions are in millimeters. Dimensions in ( ) are in inches.

  • 8/20/2019 Unidades Paquete Zp de l Marca Carrier 1

    8/20

    Base unit dimensions — 50ZP060

    UNIT  ELECTRICAL

    CHARACTERISTICS

    UNIT WT CENTER OF GRAVITY mm (in.)

    Lb Kg X Y Z

    50ZP060   230-1-60, 208/230-3-60, 460-3-60 350 159 355.6 (14.00) 508.0 (20.00) 355.6 (14.00)

    REQUIRED CLEARANCES TO COMBUSTIBLE MAT’L

    Millimeters (in.)

    Top of Un it . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 0Du ct Si de of Un it . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 0Side Opposite Ducts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 0B o tto m o f U n i t . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 0

    NEC REQUIRED CLEARANCES

    Millimeters (in.)

    Between Units, Power Entry Side . . . . . . . . . . . . . . . . . 1066.8 (42.00)

    Unit and Ungrounded Surfaces, Power Entry Side . . . . . . . 914.0 (36.00)Unit and Block or Concrete Walls and Other Grounded

    Surfaces, Power Entry Side . . . . . . . . . . . . . . . . . . . . 1066.8 (42.00)

    REQUIRED CLEARANCES FOR SERVICING

    Millimeters (in.)

    Condenser Coil Access Side . . . . . . . . . . . . . . . . . . . . . 762.0 (30.00)Power Entry Side . . . . . . . . . . . . . . . . . . . . . . . . . . . . 762.0 (30.00)

    (Except for NEC Requirements)Un it To p . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 91 4.0 (36 .00 )Side Opposite Ducts . . . . . . . . . . . . . . . . . . . . . . . . . . 762.0 (30.00)

    LEGEND

    CG —   Center of GravityNEC —   National Electrical Code

    NOTES:1. Clearances must be maintained to prevent recirculation of air from outdoor-

    fan discharge, with the exception of the condenser coil (914 mm [36 in.]). Aremovable fence or barricade requires no clearance.

    2. Dimensions are in millimeters. Dimensions in ( ) are in inches.

    8

  • 8/20/2019 Unidades Paquete Zp de l Marca Carrier 1

    9/20

    Selection procedure

    I D et er mi n e co o l i n g an d h eat i n g r eq u i r emen t s atdesign conditions.

    G iven :

    R e q u ire d C o o lin g C a p a c ity (T C ) . . . . . . 3 4 ,0 0 0 B tu hS e n sib le H e a t C a p a c ity (S H C ) . . . . . .. 2 5 ,0 0 0 B tu hR e q u ire d H e a tin g C a p a c ity . . . . . .. . . . 1 5 ,0 0 0 B tu hO utdo or E ntering -A ir Tem perature ........... 9 5 FIn do o r E n terin g-A ir

    T e m p e ra tu re . .. .. .. .. .. .. . 8 0 F e d b; 6 7 F e w bInd oo r-A ir Q uan tity ................... 1 2 0 0 cfmE xternal S tatic P ressure .............. 0 .2 0 in. w gE lectrical C h aracteristics (V -P h -H z). .. .. .. 2 3 0 -1 -6 0

    II S el ect u n i t b as ed o n r eq u i r ed co o l in g cap a cit y .

    E nter C oo ling C ap acities table at con den ser en terin gte m p e ra tu re o f 9 5 F , in d o o r a ir e n te rin g a t 1 2 0 0 c fma n d 6 7 F e w b . T h e 5 0 Z P 0 3 6 u n it p ro v id e s a to ta lc o o l-in g c a p a c ity o f 3 4 ,2 0 0 B tu h a n d a se n sib le h e a t c a -p a c ity o f 2 5 ,3 0 0 B tu h .

    Fo r ind oo r-air tem p erature other than 8 0 F edb, cal-culate sen sible h ea t ca p acity co rrectio n , a s req uired ,using the fo rm ula fo un d in N ote 4 follow in g the C oo l-

    in g C ap acities tab les.N O T E : U n it rating s are n et cap acities.

    III S el ect el ect r ic h ea t .

    T he requ ired he ating cap acity is 1 5 ,0 0 0 B tuh (given).D eterm in e th e electric h eat cap acity in kW .

    1 5 ,0 0 0 B tu h= 4 .4 k W o f h e a t re q u ire d

    3 4 1 4 B tu h / kW

    E nter the E lectric H eaters table on p age 4 for 2 0 82 4 0 , sin g le -p h a se , 5 0 Z P 0 3 6 u n it. T h e 5 -k W h e a te r2 4 0 v m ost closely satis es the heating required. Tcalculate kW at 2 3 0 v,m ultip ly the heater kW by m utip licatio n facto r 0 .9 2 fo un d in th e M ultip licatioF a c to rs ta b le o n p a g e 5 .

    5 kW x 0 .9 2 = 4 .6 kW4 .6 kW x 3 4 1 4 B tu h/ kW = 1 5 ,7 0 4 B tu h

    I V D e t e r m i n e f a n s p e e d a n d p o w e r r e q u i r e m e n tat d es i g n co n d i t io n s .

    B efo re en terin g th e air de livery tab les, ca lculate thto talstatic p ressure req uired .F ro m th e given ,F ilter P resure D ro p tab le, th e A ccessory E lectric H eat P ressuD ro p tab le, an d th e W et C o ilP ressure D ro p tab le, fin

    E xtern al static p ressu re 0 .2 0 in . wF ilter 0 .1 0 in . wE lectric H eat 0 .1 3 in . wW et C o il 0 .0 9 in . w

    T otal static p ressu re 0 .5 2 in . w

    E n ter th e table fo r D ry C o ilA ir D elivery — H o rizon t

    D ischarge. A t 0 .5 in. w g externa l static p ressure anhigh sp eed, th e m o to r de livers 1 2 9 7 cfm . In terp o laing for 0 .5 2 in. w g delivers 1 2 7 6 cfm , w h ich satisth e jo b requ irem en ts.

  • 8/20/2019 Unidades Paquete Zp de l Marca Carrier 1

    10/20

    Performance data

    COOLING CAPACITIES

    50ZP024

    TEMP (F)AIR ENT

    COND

    EVAP AIR — CFM/BF

    700/0.12 800/0.14 900/0.15

    Evap Air — Ewb (F)

    72 67 62 72 67 62 72 67 62

    85TC   23.9 23.0 21.4 23.2 22.5 21.3 22.3 21.6 21.0SHC   10.9 14.5 17.9 10.5 14.4 18.3 10.1 13.9 18.2

    kW   2.17 2.15 2.12 2.18 2.17 2.15 2.18 2.18 2.17

    95TC   24.6 22.6 20.5 24.5 22.8 20.8 23.5 22.6 20.9SHC   11.4 14.8 17.8 11.5 15.4 18.7 11.1 15.6 19.2kW   2.36 2.31 2.25 2.39 2.35 2.29 2.39 2.37 2.33

    105TC   24.1 21.6 19.3 24.3 21.9 19.7 24.1 22.1 19.9SHC   11.5 14.7 17.4 11.8 15.4 18.4 11.9 16.0 19.2kW   2.52 2.44 2.36 2.56 2.48 2.41 2.59 2.53 2.46

    115TC   22.9 20.3 18.0 23.2 20.6 18.3 23.3 20.7 18.7SHC   11.2 14.3 16.9 11.7 15.1 17.9 12.0 15.8 18.7kW   2.66 2.56 2.47 2.70 2.61 2.52 2.74 2.65 2.58

    50ZP030

    TEMP (F)AIR ENT

    COND

    EVAP AIR — CFM/BF

    875/0.07 1000/0.08 1125/0.09

    Evap Air — Ewb (F)72 67 62 72 67 62 72 67 62

    85TC   31.6 30.0 28.5 32.1 30.6 29.1 32.6 31.1 29.6SHC   21.6 23.7 25.8 22.9 25.2 27.6 24.2 26.6 29.1kW   3.14 3.09 3.04 3.21 3.17 3.12 3.28 3.23 3.19

    95TC   32.1 29.5 26.8 32.6 30.0 27.5 33.1 30.6 28.1SHC   19.9 22.4 25.0 21.0 23.7 26.4 22.1 24.9 27.7kW   3.24 3.22 3.20 3.31 3.30 3.28 3.38 3.37 3.36

    105TC   32.6 28.9 25.1 33.1 29.5 25.8 33.5 30.0 26.6SHC   18.2 21.1 24.1 19.1 22.2 25.3 20.0 23.2 26.4kW   3.34 3.34 3.35 3.41 3.43 3.45 3.47 3.50 3.53

    115TC   29.3 27.8 26.3 29.8 28.2 26.7 30.1 28.5 27.0SHC   15.2 17.4 19.6 16.0 18.5 21.0 16.7 19.5 22.3kW   3.77 3.71 3.64 3.85 3.78 3.71 3.91 3.85 3.78

    LEGEND

    BF —   Bypass FactorEwb —   Entering Wet BulbkW —   Total Unit Power InputSHC —   Sensible Heat Capacity, 1000 BtuhTC —   Total Cooling Capacity, 1000 Btuh (net)

    NOTES:1. Ratings are net; they account for the effects of the indoor-fan motor

    power and heat.2. Direct interpolation is permissible. Do not extrapolate.3. The following formulas may be used:

    sensible capacity (Btuh)t = t –  ldb edb

    1.10 x cfm

    t = Wet-bulb temperature corresponding to enthalpy of airlwbleaving indoor coil (h )lwb

    total capacity (Btuh)h = h –  lwb ewb

    4.5 x cfm

    Where: h = Enthalpy of air entering indoor coilewb

    4. The SHC is based on 80 F edb temperature of air entering indoorcoil.Below 80 F edb, subtract (corr factor x cfm) from SHC.Above 80 F edb, add (corr factor x cfm) to SHC.Correction Factor = 1.10 x (1 – BF) x (edb – 80).

    1 0

  • 8/20/2019 Unidades Paquete Zp de l Marca Carrier 1

    11/20

    COOLING CAPACITIES (cont)

    50ZP036

    TEMP (F)AIR ENT

    COND

    EVAP AIR — CFM/BF

    1050/0.08 1200/0.10 1350/0.11

    Evap Air — Ewb (F)

    72 67 62 72 67 62 72 67 62

    85TC   38.8 35.7 32.3 39.6 36.2 33.0 39.7 36.8 33.5SHC   18.9 24.5 29.6 19.7 26.0 31.5 20.3 27.6 33.2

    kW   3.65 3.53 3.42 3.74 3.61 3.51 3.80 3.70 3.59

    95TC   36.9 33.7 30.5 37.5 34.2 31.1 37.8 34.6 31.8SHC   18.2 23.8 28.7 19.1 25.3 30.5 19.9 26.7 31.8kW   3.83 3.71 3.59 3.92 3.79 3.67 3.99 3.87 3.76

    105TC   34.9 31.7 28.6 35.5 32.1 29.3 35.6 32.5 30.2SHC   17.6 23.0 27.7 18.6 24.5 29.3 19.1 25.9 30.2kW   4.02 3.88 3.75 4.11 3.96 3.84 4.17 4.03 3.94

    115TC   32.8 29.7 26.8 33.0 30.1 27.7 33.4 30.4 28.5SHC   17.0 22.4 26.7 17.7 23.8 27.7 18.5 25.2 28.5kW   4.20 4.05 3.91 4.27 4.14 4.03 4.36 4.21 4.13

    50ZP042

    TEMP (F)AIR ENT

    COND

    EVAP AIR — CFM/BF

    1225/0.11 1400/0.12 1575/0.14

    Evap Air — Ewb (F)72 67 62 72 67 62 72 67 62

    85TC   46.2 39.0 36.3 47.0 38.1 36.5 47.5 37.0 35.9SHC   22.1 25.6 31.8 23.0 25.4 32.9 23.9 24.8 33.0kW   4.19 3.89 3.81 4.28 3.92 3.88 4.37 3.95 3.93

    95TC   43.7 38.4 34.7 44.3 40.0 35.2 44.7 38.3 35.5SHC   21.2 26.1 31.5 22.1 27.2 33.2 23.0 27.8 34.5kW   4.39 4.17 4.03 4.49 4.24 4.13 4.58 4.30 4.21

    105TC   41.1 36.5 32.8 41.7 36.9 33.2 41.9 37.2 33.8SHC   20.3 25.7 30.8 21.2 27.2 32.6 22.0 28.5 33.7kW   4.60 4.40 4.25 4.70 4.49 4.34 4.78 4.57 4.44

    115TC   38.4 34.2 30.5 38.8 34.6 31.3 39.1 35.0 32.1SHC   19.4 25.1 29.8 20.3 26.6 31.3 21.1 28.1 32.1kW   4.81 4.62 4.45 4.89 4.71 4.56 4.98 4.80 4.68

    LEGEND

    BF —   Bypass FactorEwb —   Entering Wet BulbkW —   Total Unit Power InputSHC —   Sensible Heat Capacity, 1000 BtuhTC —   Total Cooling Capacity, 1000 Btuh (net)

    NOTES:1. Ratings are net; they account for the effects of the indoor-fan motor

    power and heat.2. Direct interpolation is permissible. Do not extrapolate.3. The following formulas may be used:

    sensible capacity (Btuh)t = t –  ldb edb

    1.10 x cfm

    t = Wet-bulb temperature corresponding to enthalpy of lwbleaving indoor coil (h )lwb

    total capacity (Btuh)h = h –  lwb ewb

    4.5 x cfm

    Where: h = Enthalpy of air entering indoor coilewb

    4. The SHC is based on 80 F edb temperature of air entering indocoil.Below 80 F edb, subtract (corr factor x cfm) from SHC.Above 80 F edb, add (corr factor x cfm) to SHC.Correction Factor = 1.10 x (1 – BF) x (edb – 80).

  • 8/20/2019 Unidades Paquete Zp de l Marca Carrier 1

    12/20

    Performance data (cont)

    COOLING CAPACITIES (cont)

    50ZP048

    TEMP (F)AIR ENT

    COND

    EVAP AIR — CFM/BF

    1400/0.06 1600/0.07 1800/0.08

    Evap Air — Ewb (F)

    72 67 62 72 67 62 72 67 62

    85TC   45.0 43.8 41.7 43.2 42.2 41.5 41.5 40.7 40.1SHC   20.7 29.4 37.8 19.8 28.4 38.9 19.8 27.6 37.4

    kW   4.42 4.41 4.34 4.42 4.42 4.42 4.44 4.44 4.44

    95TC   46.7 43.6 39.6 45.9 45.5 40.1 43.6 42.7 40.5SHC   22.8 30.8 37.4 22.1 32.1 39.5 21.4 32.1 40.4kW   4.88 4.77 4.60 4.89 4.86 4.72 4.90 4.90 4.83

    105TC   45.5 41.1 37.1 45.8 41.5 38.0 45.1 41.7 38.9SHC   23.1 30.1 36.4 23.9 32.0 38.0 24.1 33.7 38.8kW   5.23 5.03 4.85 5.33 5.14 4.98 5.38 5.25 5.12

    115TC   42.6 38.1 34.6 42.9 38.5 35.7 43.2 38.7 36.7SHC   22.3 29.2 34.6 23.4 31.2 35.7 24.4 33.0 36.6kW   5.48 5.26 5.09 5.59 5.38 5.25 5.70 5.49 5.39

    50ZP060

    TEMP (F)AIR ENT

    COND

    EVAP AIR — CFM/BF

    1750/0.06 2000/0.07 2250/0.08

    Evap Air — Ewb (F)72 67 62 72 67 62 72 67 62

    85TC   65.5 62.2 54.5 63.4 63.0 52.8 61.2 63.7 50.8SHC   30.8 41.7 48.2 30.0 44.1 47.4 29.2 46.5 46.1kW   6.22 6.16 5.80 6.23 6.30 5.82 6.23 6.43 5.84

    95TC   65.0 58.6 52.4 65.3 59.0 53.0 64.3 60.3 53.1SHC   31.4 40.5 47.8 32.4 43.2 50.7 32.5 45.7 52.3kW   6.78 6.55 6.21 6.90 6.72 6.35 6.95 6.86 6.47

    105TC   61.7 55.3 49.5 62.5 55.7 50.4 62.9 56.0 51.4SHC   30.4 39.0 46.9 32.0 41.2 49.8 33.2 43.2 51.3kW   7.22 6.87 6.60 7.38 7.01 6.76 7.51 7.14 6.93

    115TC   57.9 51.7 46.3 58.5 52.5 47.7 58.9 52.8 49.0SHC   29.2 37.8 45.6 30.5 40.4 47.6 31.8 42.9 49.0kW   7.60 7.27 6.97 7.75 7.43 7.17 7.88 7.57 7.37

    LEGEND

    BF —   Bypass FactorEwb —   Entering Wet BulbkW —   Total Unit Power InputSHC —   Sensible Heat Capacity, 1000 BtuhTC —   Total Cooling Capacity, 1000 Btuh (net)

    NOTES:1. Ratings are net; they account for the effects of the indoor-fan motor

    power and heat.2. Direct interpolation is permissible. Do not extrapolate.3. The following formulas may be used:

    sensible capacity (Btuh)t = t –  ldb edb

    1.10 x cfm

    t = Wet-bulb temperature corresponding to enthalpy of airlwbleaving indoor coil (h )lwb

    total capacity (Btuh)h = h –  lwb ewb

    4.5 x cfm

    Where: h = Enthalpy of air entering indoor coilewb

    4. The SHC is based on 80 F edb temperature of air entering indoorcoil.Below 80 F edb, subtract (corr factor x cfm) from SHC.Above 80 F edb, add (corr factor x cfm) to SHC.Correction Factor = 1.10 x (1 – BF) x (edb – 80).

    1 2

  • 8/20/2019 Unidades Paquete Zp de l Marca Carrier 1

    13/20

    WET COIL PRESSURE DROP

    UNIT SIZE50ZP

    AIRFLOW(cfm)

    PRESSURE DROP(in. wg)

    024

    600 0.02

    700 0.05

    800 0.06

    900 0.07

    030

    900 0.06

    1000 0.061200 0.08

    036

    1000 0.07

    1200 0.09

    1400 0.11

    1600 0.12

    042

    1000 0.04

    1200 0.06

    1400 0.08

    1600 0.09

    048

    1400 0.07

    1600 0.08

    1800 0.09

    060

    1700 0.07

    1800 0.082100 0.09

    2300 0.10

    FILTER PRESS URE DROP (in. wg)

    UNITSIZE50ZP

    FILTERSIZE(in.)

    CFM

    500 600 700 800 900 1000 1100 1200 1300 1400 1500 1600 1700 1800 1900 2000 2100 2200 230

    024-042   24 × 24 0.06 0.07 0.08 0.08 0.09 0.09 0.09 0.10 0.11 0.12 0.14 0.15 — — — — — — —

    048,060   24 × 30 — — — — — — — — 0.08 0.09 0.10 0.11 0.12 0.13 0.14 0.15 0.16 0.17 0.1

    ACCESS ORY ELECTRIC HEAT P RESSURE DRO P (in. wg)

    CFM

    Heater kW 600 800 1000 1200 1400 1600 1800 2000 2200

    5-20   0.06 0.08 0.10 0.13 0.15 0.18 0.20 0.23 0.25

  • 8/20/2019 Unidades Paquete Zp de l Marca Carrier 1

    14/20

    Performance data (cont)

    DRY COIL AIR DELIVERY* — HORIZONTAL DISCHARGE (Dedu ct 1 0 % for 2 0 8 Volt O pe ra tion)

    UNIT50ZP

    MOTORSPEED

    AIRDELIVERY

    208 AND 460 VOLT HORIZONTAL DISCHARGE

    External Static Pressure (in. wg)

    0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9

    024

    Low  Watts   288 285 282 279 274 268 261 — —

    CFM   875 820 802 734 668 582 478 — —

    Med  Watts   390 383 378 369 360 350 340 — —

    CFM   1131 1090 1038 978 917 830 721 — —

    High   Watts   528 520 510 495 480 460 450 — —CFM   1391 1338 1285 1200 1115 1018 920 — —

    030

    Low  Watts   288 285 282 279 274 268 261 — —

    CFM   875 820 802 734 668 582 478 — —

    Med  Watts   390 383 378 369 360 350 340 — —

    CFM   1131 1090 1038 978 917 830 721 — —

    High  Watts   528 520 510 495 480 460 450 — —

    CFM   1891 1338 1285 1200 1115 1018 920 — —

    036

    Low  Watts   470 450 445 410 388 359 326 311 —

    CFM   1302 1264 1204 1120 1008 950 863 751 —

    Med  Watts   450 435 420 400 380 345 338 321 —

    CFM   1231 1218 1205 1163 1081 940 873 783 —

    High  Watts   660 635 610 575 540 505 485 460 —

    CFM   1700 1660 1581 1450 1297 1190 1095 989 —

    042

    Low  Watts   478 458 440 411 378 350 327 317 —

    CFM   1303 1270 1224 1179 1126 1022 911 816 —

    Med   Watts   481 468 450 438 404 370 338 320 —CFM   1310 1280 1241 1181 1110 1022 943 811 —

    High  Watts   — 798 678 647 618 578 540 500 460

    CFM   — 1736 1688 1618 1510 1421 1309 1187 1060

    048Low

      Watts   — — 801 760 730 688 650 600 570CFM   — — 1898 1841 1757 1682 1564 1429 1365

    High  Watts   — — 870 842 818 782 696 632 628

    CFM   — — 2000 1903 1799 1718 1625 1446 1333

    060†

    Low  Watts   890 850 810 790 735 680 580 480 422

    CFM   1834 1820 1791 1762 1703 1640 1415 1159 950

    Med  Watts   1040 1018 1001 958 896 840 800 650 580

    CFM   2230 2202 2160 2122 2052 1926 1752 1468 1121

    High  Watts   1073 1038 1000 950 890 835 790 691 575

    CFM   2230 2102 2025 1960 1901 1855 1791 1588 1202

    *Air delivery values are based on operating voltage of 230 v or 460 v,

    dry coil, without filter or electric heater. Deduct wet coil, filter, and elec-tric heater pressure drops to obtain external static pressure availablefor ducting.

    †460-v motors have 2 speeds (size 060 only).

    NOTES:

    1. Do not operate the unit at a cooling airflow that is less than 350 cfmfor each 12,000 Btuh of rated cooling capacity. Evaporator-coil frost-ing may occur at airflows below this point.

    2. Dashes indicate portions of the table that are beyond the blower mo-tor capacity or are not recommended.

    1 4

  • 8/20/2019 Unidades Paquete Zp de l Marca Carrier 1

    15/20

    Electrical data

    UNIT50ZP

    NOMINALVOLTAGE(V-Ph-Hz)

    VOLTAGERANGE

      COMPRESSOR OFM IFM ELECTRIC HEAT POWER SUPPLY  DISCONNECT

    SIZE

    Min Max RLA LRA FLA FLA Nominal kW* FLA MCA MOCP FLA LRA

    024   208/230-1-60 187 254 10.9 61.0 0.9 2.4 —/— —/— 16.9/ 16.9 20/ 20 16/ 16

    683.8/ 5.0 18.1/20.8 25.6/ 29.0 30/ 30 24/ 277.5/10.0 36.1/41.7 48.1/ 55.1 50/ 60 44/ 51

    030   208/230-1-60 187 254 15.2 69.4 1.5 2.4

     —/— —/— 22.9/ 22.9 30/ 30 22/ 22

    793.8/ 5.0 18.1/20.8 25.6/ 29.0 30/ 30 24/ 277.5/10.0 36.1/41.7 48.1/ 55.1 50/ 60 44/ 51

    11.3/15.0 54.2/62.5 70.7/ 81.1 80/ 90† 65/ 75

    036

    208/230-1-60 187 254 15.9 86.0 1.5 2.8

     —/— —/— 24.2/ 24.2 30/ 30 23/ 23

    963.8/ 5.0 18.1/20.8 26.1/ 29.5 30/ 30 24/ 277.5/10.0 36.1/41.7 48.6/ 55.6 50/ 60 45/ 5111.3/15.0 54.2/62.5 71.2/ 81.6 80/ 90† 66/ 7515. 0/ 20. 0 72.2/83.3 93. 6/ 107. 7 100/110† 86/ 99

    208/230-3-60 187 254 8.9 64.5 1.5 2.8

     —/— —/— 15.4/ 15.4 20/ 20 15/ 15

    743.8/ 5.0 10.4/12.0 16.5/ 18.5 20/ 20 15/ 177.5/10.0 20.8/24.1 29.6/ 33.6 30/ 35 27/ 31

    11.3/15.0 31.3/36.1 42.6/ 48.6 45/ 50 39/ 4515.0/20.0 41.7/48.1 55.6/ 63.6 60/ 70† 51/ 59

    042

    208/230-1-60 187 254 18.5 97.6 1.5 2.8

     —/— —/— 27.4/ 27.4 35/ 35 26/ 26

    1073.8/ 5.0 18.1/20.8 27.4/ 29.5 35/ 35 26/ 277.5/10.0 36.1/41.7 48.6/ 55.6 50/ 60 45/ 51

    11.3/15.0 54.2/62.5 71.2/ 81.6 80/ 90† 66/ 7515. 0/ 20. 0 72.2/83.3 93. 8/ 107. 7 100/110† 86/ 99

    208/230-3-60 187 254 10.9 73.0 1.5 2.8

     —/— —/— 17.9/ 17.9 25/ 25 17/ 17

    833.8/ 5.0 10.4/12.0 17.9/ 18.5 25/ 25 17/ 177.5/10.0 20.8/24.1 29.6/ 33.6 30/ 35 27/ 31

    11.3/15.0 31.3/36.1 42.6/ 48.6 45/ 50 39/ 4515.0/20.0 41.7/48.1 55.6/ 63.6 60/ 70† 51/ 59

    048

    208/230-1-60 187 254 21.3 107.0 1.5 4.2

     —/— —/— 32.3/ 32.3 40/ 40 31/ 31

    12111.3/15.0 54.2/62.5 72.9/ 83.4 80/ 90† 67/ 7715 .0/20.0 7 2.2/83 .3 95 .5/109 .4 1 00 /11 0† 8 8/10 1

    208/230-3-60 187 254 12.3 73.0 1.5 4.2

     —/— —/— 21.1/ 21.1 25/ 25 21/ 21

    873.8/ 5.0 10.4/12.0 21.1/ 21.1 25/ 25 21/ 217.5/10.0 20.8/24.1 31.3/ 35.3 35/ 40 29/ 32

    11.3/15.0 31.3/36.1 44.3/ 50.4 45/ 60 41/ 4615.0/20.0 41.7/48.1 57.4/ 65.4 60/ 70† 53/ 60

    060

    230-1-60 207 254 26.9 128.0 1.4 6.2  — — 41.2 50 40

    14120.0 83.3 111.9 125† 103

    208/230-3-60 187 254 17.7 128.0 1.4 6.2

     —/— —/— 29.7/ 29.7 35/ 35 29/ 29

    1463.8/ 5.0 10.4/12.0 29.7/ 29.7 35/ 35 29/ 297.5/10.0 20.8/24.1 33.8/ 37.8 35/ 40 31/ 35

    11.3/15.0 31.3/36.1 46.8/ 52.9 50/ 60 43/ 4915.0/20.0 41.7/48.1 59.9/ 67.9 60/ 70† 55/ 62

    460-3-60 414 508 9.0 63.0 0.7 3.2

     — — 15.2 20 15

    715.0 6.0 15.2 20 15

    10.0 12.0 19.0 20 1815.0 18.0 26.6 30 2420.0 24.1 34.1 35 31

    LEGEND

    FLA —   Full Load AmpsHACR —   Heating, Air Conditioning and RefrigerationIFM —   Indoor (Evaporator) Fan MotorLRA —   Locked Rotor AmpsMCA —   Minimum Circuit AmpsMOCP —   Maximum Overcurrent ProtectionNEC —   National Electrical CodeOFM —   Outdoor (Condenser) Fan MotorRLA —   Rated Load Amps

    *Heater capacity (kW) is based on heater voltage of 208 v, 240 v, or480 v. If power distribution voltage to unit varies from rated heater voltage, heaterkW will vary accordingly.

    †Fuse or HACR circuit breaker.

    NOTES:1. In compliance with NEC requirements for multimotor and combination load and

    equipment (refer to NEC Articles 430 and 440), the overcurrent protective de-vice for the unit shall be fuse or HACR breaker.

    2.   Unbalanced 3-Phase Supply VoltageNever operate a motor where a phase imbalance in supply voltage is greater than 2%.   Use the following formula to determine the percentage of voltageimbalance.

    % Voltage Imbalance

    max voltage deviation from average voltage= 100 x

    average voltage

    Example: Supply voltage is 460-3-60

    AB = 452 vBC = 464 vAC = 455 v

    452 + 464 + 455Average voltage =

    3= 457

    Determine maximum deviation from average voltage:(AB) 457 − 452 = 5 v(BC) 464 − 457 = 7 v(AC) 457 − 455 = 2 v

    Maximum deviation is 7 v.

    Determine percentage of voltage imbalance:7

    % Voltage imbalance = 100 x457

    = 1.53%

    This amount of phase imbalance is satisfactory as it is below the maximu

    allowable 2%.

    IMPORTANT: If the supply voltage phase imbalance is more than 2% con-tact your local electric utility company immediately.

  • 8/20/2019 Unidades Paquete Zp de l Marca Carrier 1

    16/20

    Controls

    S e q u e n c e o f o p e r a t io n

    Cooling

    N O T E : W ith th e F A N sw itc h in th e O N p o sitio n , 2 4 v issup p lied to th e in do o r-fan relay (IF R ) th ro ug h th e G term i-n alo n th e th erm o stat. T h is voltage en ergizes th e co ilo f th econ tacto r, clo sin g th e n o rm ally-o p en seto f con tracts w h ichp rovide con tin uo us p ow er to the in do or-fan m o to r (IF M ).M o v in g th e F A N sw itc h b a c k to th e A U T O . p o sitio n , p ro -

    viding th ere is n ot a call fo r coo lin g, deen ergizes the IF R ,o p e n s th e IF R c o n ta c ts, a n d d e e n e rg ize s th e IF M . T h e F A Nsw itch in A U T O . p osition cycles up on a callfo r coo ling .

    O n a callfor coo ling , 2 4 v is sup p lied to the com p ressorcon tactor (C )an d IFR sim ultaneo usly throu gh the Y and Gterm in als o f th e th erm o stat, respe ctively. O n un its w ith aco m p resso r tim e de lay relay, th ere is a bu ilt-in , 5 -m in ute

    (± 4 5 secon ds)d elay betw een com p ressor starts. E n ergiz-ing the con tacto r closes th e no rm ally-o p en set o f con tactssup p lying p ow er to bo th the com p ressor and ou tdo or-fanm otor (O FM ). E ne rgizin g the IFR closes th e no rm ally-o p ense t o f c o n ta c ts p ro v id in g p o w e r to th e IF M . O n th e lo s s o fth e c a ll fo r c o o lin g , 2 4 v is re m o v e d fro m b o th th e c o n -tactor and IFR and op ening bo th the con tacts sup p lyingp o w e r to co m p re sso r/ O F M a n d IF M .

    H eat i n g —   If acc esso ry electric h ea ters a re in stalled , o n acall for heat, circuit R -W is m ade through the therm ostatcon tacts. C ircuit R -G is m ade w h ich energizes the IFR . Ifthe he aters are staged ,th en the the rm ostat closes a secon dset of con tacts (W 2 ) w hen secon d stage is required. W henth erm o statis satis ed, co n tacts o p en ,d een ergizin g th e h eaterrelay and the IFR .

    1 6

  • 8/20/2019 Unidades Paquete Zp de l Marca Carrier 1

    17/20

    Typical installation

    Typical wiring diagram

    Power WiringControl Wiring

    Outdoor Airflow

    Indoor Airflow

    *Separate disconnect per NEC(National Electrical Code) requiredfor electric heater when single-point connection is not used.

    ELECTRIC HEATER WIRING

  • 8/20/2019 Unidades Paquete Zp de l Marca Carrier 1

    18/20

    Typical wiring diagram (cont)

    LEGEND

    AWG —   American Wire GageC —   Contactor, CompressorCAP —   CapacitorCOMP —   Compressor MotorEQUIP —   EquipmentFL —   Fuse LinkFU —   FuseGND —   GroundHR —   Heater Relay

    (Strip Heat)IFM —   Indoor Fan MotorIFR —   Indoor-Fan RelayIP —   Internal ProtectorOFM —   Outdoor-Fan MotorQT —   Quadruple TerminalTDR —   Time Delay RelayTRAN —   Transformer

    Field Splice

    Marked Wire

    Terminal (Marked)

    Terminal (Unmarked)

    Terminal Block

    Splice

    Splice (Marked)

    Factory Wiring

    Field Control Wiring

    Field Power WiringAccessory or Optional Wiring

    To indicate common potentialonly, not to represent wiring

    1 8

  • 8/20/2019 Unidades Paquete Zp de l Marca Carrier 1

    19/20

    Guide specifications

    Packaged Rooftop Cooling Unit with Elec-tric Heat — Constant Volume Application

    HVAC Guide Sp ecifications

    S ize R a n g e : 2 t o 5 To n s , N o mi n al C o o lin g

    C a rrie r M o d e l N u m b e r: 5 0 Z P

    P a r t 1 — G e n e r a l

    1 .0 1 S Y S T E M D E S C R IP T IO N

    O u td o o r ro o fto p / slab m o u n ted ,e lectrically co n tro lledco o lin g un it utilizin g a recip ro catin g co m p resso r fo rco o lin g du ty an d o p tio n ale lectric h eaters fo r h eatin gdu ty. U n it sh all disch arge sup p ly air h o rizon tally assho w n on con tract draw ings.

    1 .0 2 Q U A L IT Y A S S U R A N C E

    A . U nitshallbe rated in accordan ce w ith A R IS tandards2 1 0 / 2 4 0 -8 9 a n d 2 7 0 -8 4 . D e sig n e d in a cco rd a n cew ith U L S tand ard.

    B . U nit shall be U L listed as a total p ackage for safetyreq uirem en ts.

    C . R o o f c u rb sh a ll b e d e sig n e d to co n fo rm to N R C A

    S tan da rds.D . In sulation an d adh esive shallm eetN F PA 9 0 A requ ire-

    m e n ts fo r fl a m e sp re a d a n d sm o k e g e n e ra tio n .

    1 .0 3 D E L IV E R Y , S T O R A G E A N D H A N D L IN G

    U n it shall be sto red an d h an dled p er m an ufacturer’srecom m en dation s.

    P a r t 2 — P r o d u c t s

    2 .0 1 E Q U IP M E N T

    A . G eneral:

    F acto ry assem bled sin gle p iece coo lin g un it. C o n -tain ed w ith in th e un it en clo sure shall be all facto ryw irin g, p ip in g ,co n tro ls,refrige ran tch arge (R -2 2 ),a n d

    spe cial fea tures requ ired p rio r to eld start-up .B . U n it C a b in e t:

    1 . U n it cabinet shall be con structed of ph osph ated,bo n de rized, zin c-co ated p re-p ain ted stee l.

    2 . B asep an m ade of a sing le-p iece, n on -corrosive,co m p o site m aterial.

    3 . Ind oo r blow er com p artm ent interior cabinet sur-faces shallbe in sulated w ith a m in im um   1⁄2-in .th ick ,

    exible berglass in sulatio n , coa ted o n th e air sidew ith alu m in u m fo il.

    4 . C a b in e t p a n e ls sh a ll b e e a sily re m o v a b le fo rservicin g .

    5 . U nit shallh ave a slop ed no n-corrosive drain p anth a t c o n fo rm s to A S H R A E S ta n d ard 6 2 -8 9 .

    6 . U n it in s u la tio n c o n fo r m s to A S H R A E S ta n d a rd6 2 P .

    C . F a n s :

    1 . In d o o r B lo w e r (E v a p o ra to r F a n ):

    a . F a n sh a ll b e 2 - o r 3 -sp e e d d ire ct d riv e sh o w n o n th e e q u ip m e n t d ra w in g s .

    b. Fan w h eelshallbe m ade from steel,be do ubin let typ e, h ave fo rw ard curved blad es w ithco rro sio n resistan t n ish, an d be dy n am icaba lan ced.

    2 . O utdo or (con den ser) fan shall be of the direcdriven p ro p eller typ e w ith alum in um blad es rieted to co rro sio n resistan t stee lsp id ers. It sha llbdy n am ically ba lan ced , an d discha rge air verticaupw ards.

    D . C o m p re sso r:

    F ully h erm etic; recip ro catin g typ e w ith in tern al anex tern al vib ratio n iso latio n .

    E . C o ils:

    1 . E vapo rator and con den ser coils shallh ave alumnu m p late ns m echan ically bo nd ed to seam lecop p er tub es w ith all jo in ts brazed.

    2 . T ube she eto p en ing s sh allbe b elled to p revent tubw ear.

    3 . O utdo o r coilshallbe p rotected by m etallo uverep an els.

    F. R efrigerant C o m p on ents:

    1 . R efrigerant com p on ents shallb e of the A cutrolfeed system typ e.

    2 . S ervice gage con nection s on suction , dischargan d liq u id lin es.

    3 . A bility to ro ute ga ge h o ses th ro ug h un itside p an

    G . C o ntrols:

    U n it sha llbe co m p lete w ith self-co n tain ed lo w -vo ltag

    co n trol circuit.H . O p eratin g C h aracteristics:

    1 . U n it shall be capable of starting and run ning 1 1 5 F a m b ie n t o u td o o r te m p e ra tu re p e r m a xm u m lo a d c rite ria o f A R I S ta n d a rd 2 1 0 -8 9 .

    2 . C o m p ressor w ith stand ard con trols shall be cp a b le o f o p e ra tio n d o w n to 4 0 F a m b ie n t o u td o otem p erature.

    I. E lectrical R eq u irem en ts:

    A llun itp o w er w irin g sha llen ter un itca bin et at a sin glo ca tio n .

    J. M otors:

    1 . C o m p re sso r m o to rs sh a ll b e o f th e re frig e racoo led type w ith line break therm al and curreo verlo ad p ro tectio n .

  • 8/20/2019 Unidades Paquete Zp de l Marca Carrier 1

    20/20

    Guide specifications (cont)

    2 . A ll fan m o tors sha ll ha ve p erm an en tly lubricatedbearing s, and inh eren t autom atic reset the rm alo verlo ad p ro tectio n .

    3 . O utdo or (con den ser) fan m otor shall b e totallyen clo sed.

    K . S p ecialF eatures:

    1 . L o w A m b ie n t P a ck ag e:

    P ackag e sh all con sist o f a solid-state con tro l an dco n den ser co iltem p erature sensor fo r con tro llin go utdo o r-fan m o to r o p eratio n ,w h ich shallallo w un itto o p e ra te d o w n to 0 ° F o u td o o r a m b ie n t te m -p erature.

    2 . H eatin g S ectio n:

    a. E q uip p ed w ith eld-in stalled electric resis-tan ce h ea ter(s) o f th e ch aracteristics sho w nin the equip m ent schedule.

    b . H e a te r e le m e n ts sh a ll b e o p e n w ire ty p e , a d -equa tely sup p orted an d in sulated w ith ce-ram ic bu shin gs.

    c. E lectric h eater p ackages m ustp rovide sing le-

    p oint p o w er con n ection cap ability.

    3 . C o m p re sso r S h o rt C y c le D e v ic e :

    S o lid-state con tro l sh all p ro tect com p resso r byp reve n tin g sho rt cyclin g.

    4 . C on trols U p grade K it:

    C o ntain s h igh an d low p ressure sw itches. K itsshallp ro tect un itfro m o p eratin g at un accep tablep ressures.

    5 . O u td o o r T h e rm o s ta t:

    A llo w s fo r stag in g o f e lectric h eaters based o no utdo o r-air tem p erature.

    6 . C rankcase H eater:

    W arm s cran kcase o ilto redu ce refrige ran tm igra-tio n an d en sure p rop er com p ressor lubricatio n.

    7 . T h e rm o sta t a n d S u b b a se :

    P rovides staged coo lin g an d he atin g, autom atic(or m an ual) chan geo ver, fan con trol.

    8 . E lectron ic P rog ram m able T h erm o stat:

    T h erm o statp ro vide s 2 -stage h eatin g a n d 2 -stag ecoo ling con trol w ith rem ote com m un icationab ility.

    Carrier Corporation • Syracuse, New York 13221 1-97