calculo potencia seubestaciones
TRANSCRIPT
S.E
Sub
Esta
cion
CARGAS A ALIMENTAR DEMANDA PROYECTADA (KW)
0.5 N° lamp 70 watts Viviendas
(81 W)
URB
ANIZ
ACIO
N
1 CT-1 48 16 43.20 1.30 0.43 44.93 124.71 162.12 170CT-2 72 23 64.80 1.86 0.65 67.31
2 CT-1 48 16 43.20 1.30 0.43 44.93 124.71 162.12 170CT-2 72 23 64.80 1.86 0.65 67.31
3 CT-1 48 16 43.20 1.30 0.43 44.93 124.71 162.12 170CT-2 72 23 64.80 1.86 0.65 67.31
4 CT-1 48 16 43.20 1.30 0.43 44.93 124.71 162.12 170CT-2 72 23 64.80 1.86 0.65 67.31
5 CT-1 48 16 43.20 1.30 0.43 44.93 124.71 162.12 170CT-2 72 23 64.80 1.86 0.65 67.31
6 CT-1 48 16 43.20 1.30 0.43 44.93 124.71 162.12 170CT-2 72 23 64.80 1.86 0.65 67.31
7 CT-1 48 16 43.20 1.30 0.43 44.93 124.71 162.12 170CT-2 72 23 64.80 1.86 0.65 67.31
8 CT-1 48 16 43.20 1.30 0.43 44.93 124.71 162.12 170CT-2 72 23 64.80 1.86 0.65 67.31
9 CT-1 52 17 46.80 1.38 0.47 48.65 130.86 170.12 170CT-2 74 23 66.60 1.86 0.67 69.13
10 CT-1 52 16 46.80 1.30 0.47 48.56 130.86 170.12 170CT-2 74 24 66.60 1.94 0.67 69.21
11 CT-1 44 14 39.60 1.13 0.40 41.13 108.19 140.65 170CT-2 60 21 54.00 1.70 0.54 56.24
12 CT-1 48 16 43.20 1.30 0.43 44.93 124.80 162.24 170CT-2 72 24 64.80 1.94 0.65 67.39
13 CT-1 48 16 43.20 1.30 0.43 44.93 124.71 162.12 170CT-2 72 23 64.80 1.86 0.65 67.31
14 CT-1 48 16 43.20 1.30 0.43 44.93 124.71 162.12 170CT-2 72 23 64.80 1.86 0.65 67.31
15 CT-1 48 16 43.20 1.30 0.43 44.93 124.71 162.12 170CT-2 72 23 64.80 1.86 0.65 67.31
16 CT-1 48 16 43.20 1.30 0.43 44.93 124.71 162.12 170CT-2 72 23 64.80 1.86 0.65 67.31
17 CT-1 48 16 43.20 1.30 0.43 44.93 124.71 162.12 170CT-2 72 23 64.80 1.86 0.65 67.31
18 CT-1 72 26 64.80 2.11 0.65 67.55 149.67 194.57 200CT-2 72 21 64.80 1.70 0.65 67.15
19 CT-1 72 27 64.80 2.19 0.65 67.63 149.76 194.69 200CT-2 72 21 64.80 1.70 0.65 67.15
Maxima Demanda
Proyectada (KW)
Capacidad del Transformador
(KVA)
Total para Selección de Transformador
(KVA)
Tpotencia Transformador
(KVA)
SERVICIO PARTICULAR
Alumbrado Publico (f.s. =1.0)
Alumbrado Publico (Kw)
Perdidas Estrimadas (Kw)
N° de Lotes Vivienda