ashrae presentation 10-08-13

14
10/9/2013 1 Nathan J. Birmingham, P.E. SMOKE CONTROL SYSTEMS Special Inspections and the Issues That Arise Smoke Control Designs Smoke Control Special Inspections Smoke Control Equipment and Controls PRESENTATION OVERVIEW

Upload: daveleycons

Post on 18-Jul-2016

226 views

Category:

Documents


1 download

DESCRIPTION

dgDg

TRANSCRIPT

Page 1: Ashrae Presentation 10-08-13

10/9/2013

1

Nathan J. Birmingham, P.E.

SMOKE CONTROL SYSTEMSSpecial Inspections

and the Issues That Arise

• Smoke Control Designs

• Smoke Control Special Inspections

• Smoke Control Equipment and Controls

PRESENTATION OVERVIEW

Page 2: Ashrae Presentation 10-08-13

10/9/2013

2

• Why do they exist?

– Life Safety

• Where are they provided?

– High-rise buildings

– Underground buildings

– Windowless Prisons/Jails

– Smoke Protected Assembly Seating

– Atria

SMOKE CONTROL SYSTEMS

TYPES OF SMOKE CONTROL

Image from ASHRAE Handbook of Smoke Control Engineering, 2012

• Pressurization Method

Page 3: Ashrae Presentation 10-08-13

10/9/2013

3

• Smokeproof enclosures

– Ventilated Vestibules at each stair entrance, or

– Stairwell Pressurization

• Elevator Pressurization

– In lieu of elevator lobbies

TYPES OF SMOKE CONTROL

• Exhaust Method

– Atria

– Malls

• Keep smoke away from occupants

• Exhaust High, Supply Low

TYPES OF SMOKE CONTROL

Images from A Guide To Smoke Control in the 2006 IBC

Page 4: Ashrae Presentation 10-08-13

10/9/2013

4

• Air Flow method

– Use of opposed airflow

– Often used in combination with exhaust method

TYPES OF SMOKE CONTROL

Images from NFPA 92B, Standard for Smoke Management Systems in Malls, Atria and Large Spaces, 2009 ed.

• Special inspections are a means that an AHJ uses to determine code compliance

• Required expertise in Fire Protection Engineering Mechanical Engineering and certification as an air balancer

• Many jurisdictions require an independent Special Inspector (MA does not)

• Statement of special inspection should be submitted as part of permit documents

SMOKE CONTROL SPECIAL INSPECTIONS

Page 5: Ashrae Presentation 10-08-13

10/9/2013

5

• Test plan

– Outline of testing

– Description of types of tests

– Prerequisite states of construction required

• Duct Leakage testing

• Damper Inspection

• Sequence Testing

• Performance Testing

SPECIAL INSPECTIONS

• Final inspection test report

– Summary of Results

– Compilation of inspection reports and any issues that were identified

– Data Sheets of Equipment

– Signatures of Inspectors and EOR

SPECIAL INSPECTIONS

Page 6: Ashrae Presentation 10-08-13

10/9/2013

6

• Installation and Component verification

– Is the right equipment getting installed?

• Equipment Functional Testing

– Is the equipment working properly?

• Sequence of Operations Testing

– Are the systems properly integrated?

• System Performance Testing

– Does the system perform as designed, as required?

SPECIAL INSPECTIONS

• Listings

– Smoke Control listings ≠ Fire Alarm listings

– UUKL UL 864

• BMS or Fire Alarm

EQUIPMENT AND CONTROLS

Images from UL 864, Control Units and Accessories for Fire Alarm Systems

Page 7: Ashrae Presentation 10-08-13

10/9/2013

7

1. Fire Fighters Override Panel

2. Automatic Signal

– Smoke Detector, Waterflow Switch

3. Manual or Automatic control from other source

CONTROL PRIORITIES

• VFD Keypad not locked out

• Automatic alarm fails to override “not in auto” VFD

• VFD installed with a Bypass

• Subsequent alarms cannot alter the sequence initiated by the primary alarm.

• Control functions split between systems

– Electrical and Mechanical specs not harmonized

CONTROLS – COMMON ISSUES

Page 8: Ashrae Presentation 10-08-13

10/9/2013

8

• Electrical specifications

– Fan shuts down on fire alarm

• Mechanical specifications

– Building Controls tells fan to start

SPLIT CONTROL FUNCTIONS

Images from Klote, Milke Turnbull, Kashef, Ferreira Handbook of Smoke Control Engineering, ASHRAE 2012,

• Always use single control system (Required by NFPA 92, 2012)

CONTROL FUNCTIONS

Images from Klote, Milke Turnbull, Kashef, Ferreira Handbook of Smoke Control Engineering, ASHRAE 2012,

Page 9: Ashrae Presentation 10-08-13

10/9/2013

9

• Status Indication for all equipment

– Red � Closed/Off

– Green � Open/On

– Yellow � Fault

– White � Normal

– Blue � Duct Detector (Boston)

• Confirmation of Status

FIRE FIGHTERS OVERRIDE PANEL

• Manual Controls Switches

– Should be provided for all fans, doors, and windows.

– Manual control for dampers can often be omitted.

FIRE FIGHTERS OVERRIDE PANEL

Image from Klote, Milke Turnbull, Kashef, Ferreira Handbook of Smoke Control Engineering, ASHRAE 2012,

Page 10: Ashrae Presentation 10-08-13

10/9/2013

10

• Leak tested to 1.5 times the max design pressure

• Leakage not to exceed 5 percent of design flow

DUCTS

• 1.5x minimum number of belts

• 1.15 service factor on motor

• Power disconnects not monitored

– At the VFD

– At the Fan

FANS – POTENTIAL ISSUES

Page 11: Ashrae Presentation 10-08-13

10/9/2013

11

• Positive status of flow

– Pressure switch

– Flow switch

– CT sensor

FANS – POTENTIAL ISSUES

Image from Klote, Milke Turnbull, Kashef, Ferreira Handbook of Smoke Control Engineering, ASHRAE 2012,

• VFDs not protected with 2-hour construction

• VFDs not separated from other mechanical equipment

• Control wiring to and from room containing VFD not protected with 2-hour construction

VARIABLE FREQUENCY DRIVES (VFD)

Page 12: Ashrae Presentation 10-08-13

10/9/2013

12

• End switches

• Damper actuator

– Stroke time limited to 75s or less

DAMPERS – POTENTIAL ISSUES

Image from Klote, Milke Turnbull, Kashef, Ferreira Handbook of Smoke Control Engineering, ASHRAE 2012,

• Doors and windows are confirmed open before they are.

• Atrium Systems using natural makeup air

– Provide UPS to powered door operators

DOORS AND WINDOWS – POTENTIAL ISSUES

Page 13: Ashrae Presentation 10-08-13

10/9/2013

13

• Standby power not Emergency power

• Secondary power source or ATS in same room as normal power transformers and switch gears

POWER SYSTEMS

WEEKLY SELF - TEST

Images from Klote, Milke Turnbull, Kashef, Ferreira Handbook of Smoke Control Engineering, ASHRAE 2012,

Page 14: Ashrae Presentation 10-08-13

10/9/2013

14

• Residential buildings containing both stair and elevator pressurization

• Exit discharge doors from pressurized stairs can be a challenge to closed under pressure

WHAT TO WATCH OUT FOR

Nathan J. Birmingham, P.E.

Code Red Consultants, LLC

[email protected]

www.crcfire.com

QUESTIONS?