aplicaciones valvulas de control

Upload: lopezcrg

Post on 04-Apr-2018

240 views

Category:

Documents


0 download

TRANSCRIPT

  • 7/29/2019 Aplicaciones Valvulas de Control

    1/45

    ISA is the international society for measurement and controlISA is the international society for measurement and control

    Volume EMC 21.01

    Control Valve ApplicationsHerbert L. Miller

    Application Categories

    Valves in Parallel and Series

    Frequent Application Problems

    Taken from the Practical Guide Series book: Control Valves

  • 7/29/2019 Aplicaciones Valvulas de Control

    2/45

    Notice

    The information presented in this publication is for the general education of the reader. Because neither the

    authors nor the publisher have any control over the use of the information by the reader, both the authors and

    the publisher disclaim any and all liability of any kind arising out of such use. The reader is expected to

    exercise sound professional judgment in using any of the information presented in a particular application.

    Additionally, neither the authors nor the publisher have investigated or considered the effect of any patents on

    the ability of the reader to use any of the information in a particular application. The reader is responsible for

    reviewing any possible patents that may affect any particular use of the information presented.

    Any references to commercial products in the work are cited as examples only. Neither the authors nor the

    publisher endorse any referenced commercial product. Any trademarks or tradenames referenced belong to the

    respective owner of the mark or name. Neither the authors nor the publisher make any representation regarding

    the availability of any referenced commercial product at any time. The manufacturers instructions on use of

    any commercial product must be followed at all times, even if in conflict with the information in this

    publication.

    Copyright 2000 Instrument Society of America.

    All rights reserved.

    Printed in the United States of America.

    No part of this publication may be reproduced, stored in retrieval system, or transmitted, in any form or by any

    means, electronic, mechanical, photocopying, recording or otherwise, without the prior written permission of

    the publisher.

    ISA

    67 Alexander Drive

    P.O. Box 12277

    Research Triangle Park

    North Carolina 27709

  • 7/29/2019 Aplicaciones Valvulas de Control

    3/45

    Editors Introduction

    This mini-book is available both in downloadable form, as part of the ISA Encyclopedia of

    Measurement and Control, and bound in a print format.

    Mini-books are small, unified volumes, from 25 to 100 pages long, drawn from the ISA catalog of

    reference and technical books. ISA makes mini-books available to readers who need narrowly focused

    information on particular subjects rather than a broad-ranging text that provides an overview of the entire

    subject. Each provides the most recent version of the materialin some cases including revisions that havenot yet been incorporated in the larger parent volume. Each has been re-indexed and renumbered so it can

    be used independently of the parent volume. Other mini-books on related subjects are available.

    The material in this mini-book was drawn from the following ISA titles:

    Control Valves, a Practical Guide Series book edited by Guy Borden, Jr. and Paul G. Friedmann,

    Chapter 12. Order Number: 1-55617-565-5

    To order: Internet: www.isa.org

    Phone: 919/549-8411

    Fax: 919/549-8288

    Email: [email protected]

  • 7/29/2019 Aplicaciones Valvulas de Control

    4/45

  • 7/29/2019 Aplicaciones Valvulas de Control

    5/45

    v

    Table of Contents

    Chapter 12 CONTROL VALVE APPLICATIONS 1by Herbert L. Miller

    The Application Categories, 2

    Valves in Parallel, 14

    Valves in Series, 23

    Frequent Application Problems, 25

    References, 37

    INDEX 39

  • 7/29/2019 Aplicaciones Valvulas de Control

    6/45

  • 7/29/2019 Aplicaciones Valvulas de Control

    7/45

    1

    12

    Control Valve

    Applications

    The purpose of this chapter is to present the information that will help processengineers specify control valves properly. It will show that not all of the control

    valves attributes are uniquely required for the process design. There are many

    common requirements for the categories of applications, regardless of the industry

    or the process. By recognizing the common requirements and their importance,the designer can specify the most economical design that meets performance

    needs.

    Many books on control valves concentrate on the design aspects of the valve,

    and little information is included on the subject of applications. An exception to

    this is Reference 1, which provides the practical design input associated with a

    good valve application. This reference provides many examples of control valve

    applications and illustrates the importance of knowing the control characteristics

    dictated by the process. Another source of good application knowledge is the

    control valve manufacturers. Many have prepared specific application brochures

    and guidelines for experiences they have frequently encountered. These brochures

    have a wealth of background information because they integrate the experience of

    many customers involving the same applications and the experience gained across

    different industries encountering similar applications. Many practical guidelines

    regarding selection and installation practices are also provided in Reference 2.

    In the discussion in this chapter all applications of control valves are classified

    into four categories. In describing the applications, the attributes that will be

    emphasized are those important in each of the four categories, independent of the

    many different application names used from industry to industry. Valve types or

    materials will not be discussed unless they are key to a successful application.

    Selection among valve types is covered in Chapter 14 of the Practical Guide

    Series bookControl Valves; selection among materials was discussed in Chapter

    11 ofControl Valves. There are exceptions within every category because of the

    needs unique to a specific process within an industry. An example of this would bea pump recirculation valve that would normally fail open to protect the pump but,

    in some nuclear power plants, fails closed by design.

    It is assumed in the following discussion that the valves have been sized

    correctly. A correctly sized valve is a major factor in a successful application. The

    use of the ISA data sheet, Reference 3, ensures that all the pertinent information is

    available for the sizing decisions. It is recognized that many companies have their

    own valve data sheets, but many contain omissions that result in important

    information not being passed onto the valve designer. The ISA data sheet standard

    provides a good checklist of key information that may impact the users specific

  • 7/29/2019 Aplicaciones Valvulas de Control

    8/45

    Control Valve Applications

    2

    application. Chapter 6 ofControl Valves discusses sizing; Chapter 22 ofControl

    Valves describes a valve sizing computer program.

    In the discussion in this chapter emphasis is placed on the attributes that are

    unique to the application and not so much on problems that occur due to poor

    selection. Of course, being aware of these attributes can help assure that you make

    a proper valve design choice.

    The application categories are as follows:

    Process control/feed regulation Continuous letdown Intermittent letdown Recirculation

    In addition to these four categories, a separate discussion is provided for valves

    that are installed in parallel or series applications. These configurations occur in

    many processes so a specific section is devoted to them. Also discussed in this

    chapter are common valve application problems caused by improper specification

    or installation practices.

    The definitions of terms used in this chapter are discussed in Chapter 3 of

    Control Valves and are based on the ISA standard S75.05, titled Control Valve

    Terminology.

    The Application Categories

    Process Control/Feed Regulation

    In this category, a control loop or system has been pressurized and has a valve

    that is controlling the feed to a process in response to a control signal. The control

    signal could be based on a need for flow or used to maintain a pressure or

    temperature to the process or to maintain a fluid level. This setup would typically

    require continuous valve operation. Frequently, there are parallel control valves to

    aid in start-up or shutdown when wide rangeability is required.

    To provide proper valve control trim characterization is usually needed. Thisvalve trim is required for process startup and shutdown, which, of course, cannot

    be avoided even though it may not be frequent. When the system is operating at

    low loads both the flow rate and system pressure drop are low, but valve inlet

    pressure can be high due to pump runback. This results in high pressure drop

    across the control valve at low flow. At full flow (full load) conditions, the system

    pressure loss has increased to cause lower pressure drop across the control valve,

    as shown in Figure 12-1. These conditions point to the need for good valve

    rangeability, which usually results in reciprocating stem-type valves with equal

    percentage trim characteristic. With parallel start-up valves and/or low-pressure

    processes, this regulation may be possible using a rotary-type valve with a

    modified ball design.

    Figure 12-1 shows a schematic of the situation covered by this application.Also shown is a frequently encountered pressure-versus-load curve for the

    application. As seen at the low-load condition, the pressure drop across the valve

    is very high. This is the difference between the pressure developed by a pump or

    compressor upstream and the pressure drop through the system.

    The names assigned to the valves in this application are numerous. Some of

    them are as follows:

    Flow control Level control Pressure control

  • 7/29/2019 Aplicaciones Valvulas de Control

    9/45

    The Application Categories

    3

    Pressure reduction

    Regulator (flow)

    Throttle

    Figure 12-1. Process Control/Feed Regulation Application.

    Key attributes for this application category are as follows:

    1. Accuracy of control. The output of this valve affects almost all of the

    downstream functions in the process. If a steady feed rate cannot be

    maintained, then all of the pressures, temperatures, and flows will becontinuously changing, sometimes with an increased gain or error signal

    multiplication. Thus, the quality of the process output, whether it is

    electric power output, clean gas, paper, chemical product, or other, is

    impacted by the ability of this valve to maintain an accurate output. In

    some processes, the variation of an inaccurate valve output may not be

    noticed at the process output because of a damping due to long residence

    times. In these cases, however, the continuous variation may lead to long

    period oscillations and fatigue in process equipment near the valve. Small

    signal response is often important to optimize efficiency or process

  • 7/29/2019 Aplicaciones Valvulas de Control

    10/45

    Control Valve Applications

    4

    output.

    2. Rangeability. This is the second most important attribute for this valve

    because the process must be controlled during start-up and shutdown.

    Also, during operation, abnormal conditions may frequently exist that

    create the need to operate at reduced loads. In the electric power

    generation field, it would be necessary to reduce load depending upon

    whether the load dispatcher responded to diminished use of electric

    power. In the chemical process field it may be a breakdown or

    maintenance of a parallel train in the system that calls for the process to

    operate at reduced load.

    To handle the start-up and shutdown conditions, it has been traditional

    to use two valves in parallel to achieve the needed rangeability. There are,

    however, valve designs today that can handle this function in one valve

    body (see the discussion on parallel valves later in this chapter). To

    achieve good rangeability and linearity of the valve-flow-to-stem position

    (installed linearity), the valve trim must be characterized. Thus, at the

    low-load conditions, a valve capacity versus position curve

    (characterization) will look like that shown in Figure 12-2. This

    characterization not only provides better rangeability and control but alsoassures that the valve closure member does not operate near the seat and

    thus minimizes damage to the critical seating surfaces as a result of

    excessive fluid velocities. Depending upon the low-load pressure drop,

    other measures may be necessary to limit high fluid velocity erosion such

    as the use of multi-stage trim designs. These designs become a

    consideration when pressure ratios, p1/p2, across the valve exceed three;

    otherwise pressure drop across the valve could result in cavitation or

    excessive noise. Cavitation (see Chapter 7 ofControl Valves) and

    excessive noise (see Chapter 8 ofControl Valves) can occur at pressure

    drops as low as 30 psi (0.2 MPa) for some fluid conditions. The

    characterization and trim-erosion considerations are very important

    because they contribute significantly to the most vital function of thisvalve and that is accuracy of feed control. In this application, other

    attributes are usually secondary. These are as follows:

  • 7/29/2019 Aplicaciones Valvulas de Control

    11/45

    The Application Categories

    5

    Figure 12-2. Cv/Flow versus Travel.

    3. Failure mode. Fail safe is the preferred failure mode and is usually in

    place or last position. This means that all actuator types can be used;

    pneumatic, electric, or hydraulic. There are always exceptions. One is in

    the nuclear power industry where the normal feedwater regulators are

    failed closed to eliminate an uncontrolled leak path, while the auxiliary

    feedwater system takes control.

    4. Stroke speed. Stroke speed is generally not a consideration because most

    processes cannot change load quickly because of stored energy or productin the system. Thus, normal valve speeds are quick enough to respond to

    the demands imposed.

    5. Shutoff. This is usually not a consideration because these valves are

    seldom shut. So, an ANSI/FCI-70-2 leakage class III or even less is

    sufficient in most cases.

    The most obvious example of a valve in this application would be a boiler

    feedwater regulator valve where a constant-speed feed pump is used. The

    pressure condition for the valve inlet (pump output) and valve outlet (system

    pressure) are shown on Figure 12-1. A representative set of conditions for this

    application would be a flow rate of 55,000 lb/h (metric 25 t/h) at a pressuredifferential of 735 psi (5.07 MPa) at start-up. At a full-load flow rate of 990,000

    lb/h (450 t/h) the pressure differential is 30 psi (0.20 MPa). Thus the pressure

    drop across the valve changes by 25 times as flow is varied by 20 times over

    the load range. The resultant valve rangeability exceeds 100 in that the

    minimum Cv is 4, and the maximum is 370. However, to provide control at the

    maximum condition, a Cv of over 400 is required.

  • 7/29/2019 Aplicaciones Valvulas de Control

    12/45

    Control Valve Applications

    6

    A range of conditions for the gas transmission metering valves would be a low

    flow pressure differential of 900 psi (6.2 MPa) and a high flow pressure

    differential of 100 psi (0.7 MPa). Another valve selection criteria in this

    application that may be a consideration is valve-generated noise. With the high

    compressible fluid pressure differentials, some valve designs could produce noise

    levels in excess of 100 dBA.

    Continuous Letdown

    In this application category, the valve is located between two large reservoirs of

    different pressures where the downstream reservoir could be the atmosphere. In

    this case, the valve sees a constant pressure drop, so flow control is established bythe valve position. There is no need to provide anything other than a linear trim

    characterization for this purpose unless extended duty at low feed rates is also

    required by the process. An equal percent closure member will allow travel farther

    off the seat for extended operation at low flows.

    Reliability and ruggedness are the keys to this continuous-duty application, soselecting the proper valve design for the pressure drop condition is important.Table 12-1 provides a guideline for which type of valve to select for specific

    pressure ratios.

    Figure 12-3 shows a schematic of the situation covered by this application. The

    most usual control condition is that of either upstream or downstream pressure or

    level control. The feed rate is varied as necessary to maintain pressure or level. Anexample of upstream pressure control is the letdown from a process, such as a

    chemical reactor vessel, a gas reservoir, or a reservoir level control. Probably more

    numerous are the downstream pressure control requirements, such as for steam to

    an auxiliary turbine or process reactor and for gas flow into a distribution system

    such as for multiple burners. The control variable can also be flow instead of

    pressure. This would be the case for burner control valves, spray or mixing valves

    used for pressure or temperature control, and gas transmission pressure-reducing

    valves.

    A less obvious example of a valve in this application is that of a gas

    transmission metering valve. The highest flows occurs at the lowest

    differential pressure, and the lowest flow rates occur at the highest differential

    pressures. This is caused by variable load resulting from changing weather

    conditions. As noted by Reference 4,

    When it is cold outside, consumers require large volumes of gas,

    which results in great demand placed on the local distribution

    company, LDC. The LDCs in turn require a greater amount of gas from

    the pipeline system. This results in small differential pressure between

    the pipeline and the LDC, with corresponding high volumes of gas.

    This situation requires a valve with a high capacity.

    In contrast, when the weather turns warmer, consumer demand

    diminishes and the LDCs place very little demand on the pipeline. The

    pipeline system pressure remains high because of the reduced

    demand. Therefore, high differential pressures occur between the

    pipeline and LDC with very little flow occurring. This situation requires

    a valve that can handle low capacity.

  • 7/29/2019 Aplicaciones Valvulas de Control

    13/45

    The Application Categories

    7

    Figure 12-3. Continuous and Intermittent Letdown Application.

    In specifying conditions for these valve applications, the most common error is

    omitting the off-load operating conditions. Usually, only one set of operating

    conditions is provided, that of steady-state full load. The off-load conditions are

    important because of the complexity of most plants start-up procedures, whichrequire holding at partial loads for extended periods. Thus, the need for good

    rangeability is usually missed in these applications, resulting in poor valve

    selection with the corresponding result of poor control of the process start-up or

    part-load performance.

    Typical names assigned to these valves are:

    Attemperation

    Blowdown Flow control Letdown Level control Pressure control

    Pressure regulator Reducing Spray

    Key attributes for the continuous letdown applications are the following:

    1. Accuracy of control. As with the process control valve, this is the most

    important function for this valve. Maintaining a near constant pressure,flow, or temperature condition is essential to the process product quality

    and reliability of the equipment affected by the control. A continuously

    varying output would have many short- and long-term damaging

    influences.

    This application is fairly routine in terms of its demand on the control

    valve. Many different types of valve designs can handle the conditions

    imposed without detrimental effects. There, of course, can be exceptions

    where the attributes discussed here may assume more importance than

    indicated here.

    2. Rangeability. This is not generally an important issue because most valve

    designs provide sufficient rangeability to meet the process needs. Areasonable need is for a fifteen-to-one rangeability. Since the pressure

    drop across the valve is constant, the trim of the valve is linear, and for

    most valves the travel position is a reasonable approximation of the load.

    3. Failure mode. This depends upon the specific application, and all modes

    of failures on loss of power to the actuator are used. If a generalization is

    to be made, it would be to have this valve fail-in-place so that the system

    is not disturbed by an abrupt change in pressure or flow conditions. Some

    engineers may prefer to fail the valve closed so that the operator is alerted

    to the valve failure.

  • 7/29/2019 Aplicaciones Valvulas de Control

    14/45

    Control Valve Applications

    8

    4. Stroke speed. As with the process control/feed regulation application, this

    is usually not a consideration.

    5. Shutoff. This is not an important consideration because the valves are

    rarely closed unless the process is off line and isolated by other system

    valves.

    Intermittent Letdown

    As with continuous letdown applications, the valve reduces the pressure

    between two large reservoirs, and frequently the downstream reservoir is the

    atmosphere. Obviously, for fluids damaging to the environment and public health,

    a downstream reservoir would capture the flow for further processing, such as

    through a flare arrangement, where the fluid is burned before release.

    The pressure drop could be constant or variable depending upon the specific

    application. The variable case would occur on a blowdown situation, so the inlet

    pressure would decrease with time. The valve stroke would be increased if a near

    constant flow rate was desired to minimize blowdown time. Or, for the case of

    upstream pressure control, the stroke would be varying depending upon the

    process input and output of the upstream reservoir.Figure 12-3 is the same for continuous and intermittent letdown applications.

    As implied by the name, the only difference in the two processes is the time of

    operation or duty cycle on the valve. Even though the valve is used less frequently,

    the conditions for the valve represent a tougher service. In this case, the control

    valve must perform the dual functions of providing control and tight shutoff. The

    latter usually means a Class V or VI leakage (ANSI/FCI-70-2), but in many cases

    this is not sufficient. A block valve leakage requirement must be used to provide a

    sufficient criterion for the permissible leakage. The reason a tight shutoff is

    needed is that any leakage through this valve means a loss of process fluid that is

    needed upstream to make the process product or output.

    Valves in intermittent letdown service primarily perform a bypassing function.The valves are opened to bypass the entire process or parts of the process during a

    start-up/shutdown function or a safety-relieving function. In some cases, the valve

    can perform both functions of bypassing for control and safety relief. However,

    local codes must be checked to see if a dual role is permitted.

    Typical names assigned to various intermittent letdown valves are shown in the

    following list. Frequently, the name of the equipment being bypassed or blown

    down is used in combination with these labels:

    Antisurge Dump Reject Auxiliary Extraction

    Relief Blowdown Flare Start-up Bypass

    Injection Vent(ing) Depressurizing

    Letdown

    The attributes for the intermittent letdown application are as follows:

  • 7/29/2019 Aplicaciones Valvulas de Control

    15/45

    The Application Categories

    9

    1. Accuracy of control. For most valves in this application this is not an

    important function because most control valves provide sufficient

    resolution to meet the requirements. An exception frequently exists when

    the valves are in a start-up bypass function where a fine, accurate control

    is needed to maintain flow or upstream pressure conditions over extended

    periods. The pressure drop across these valves is constant for most of the

    operating conditions. As a result of this and the accuracy needs, a linearcharacterization of the trim is normally sufficient.

    2. Rangeability. Normal design capability is sufficient.

    3. Failure mode. Normally, this valve is in a fail-close configuration, its

    normal status, so that if power is lost to the valve the process is not

    disturbed unnecessarily. Occasionally, process system needs will require

    the valve to fail in its last position.

    When the valve is in a safety role, the valve configuration must be in the fail-safedirection, which is usually fail-open.

    4. Stroke speed. The dual functions of these applications dictate the speed ofoperation. When the valve is used in a safety function, the speed needs to

    be very fast, on the order of one-half to five seconds. The safety function

    could be to protect personnel, equipment, or the process output. This

    would only be necessary for the opening direction because, in this mode, it

    is usually relieving pressure from an over-pressurized upstream reservoir.

    When the valve is used in the process bypass mode, for start-up and

    shutdown function, speed is generally not a priority consideration. Speeds

    can be achieved without requiring special considerations because

    commercial positioners usually have sufficient capacity for pneumatic

    actuators. Electric drives, although they tend to be relatively slow, are fast

    enough. The use of hydraulic actuators for speed purposes would be over

    design except when the valve is used for safety relief.

    5. Shutoff. This is a key and critical function of valves in this application,

    regardless of whether the valve is performing a bypass or a safety role.

    Any loss of fluid through this valve reduces the process efficiency. Either

    pumps or compressors must work harder to overcome the leakage or the

    maximum loads achievable are reduced.

    The minimum shutoff requirement would be a Class V leakage for a control

    valve. However, often a Class VI or even a MSS-SP61* block valve closure is

    prudent for reliable long-term valve operation. For this reason, many control valve

    * The MSS-SP61 is a standard issued by the Manufacturers Standardization Society of the Valve and Fittings

    Industry, Inc. The SP61 standard is titled Pressure Testing of Steel Valves. It covers the requirements forthe shell and seat closure pressure testing of steel valves. The standard is not intended to be used for control

    valves. However, as noted in this chapter, there are many control valve applications in which the valve mustperform the role of modulating control and then become a block valve when shut. For many valves that areused in safety relief and plant start-up or shutdown applications, these dual roles are frequent requirements.

    If only a control valve leakage class is imposed then some leakage is permitted. The amount of leakage maynot be bothersome when the valve is new. However, since these valves are normally shut, fluid erosion ofthe closure members due to the leakage results in a complete failure of the valve to shut off. In the extreme

    case, the ability to control is also lost. Manufacturers can produce control valve designs capable of meetingthe MSS-SP61 standard.

    The standard calls for a leakage test pressure drop of 110% of the 100F (38C) ANSI class rating

    pressure. If this high pressure may damage the seat, a possibility in control valve designs, then 110% of themaximum differential operating pressure may be used. The permissible leakage under this standard shall beless than 10 cc/h of liquid per inch of diameter of the nominal valve size.

  • 7/29/2019 Aplicaciones Valvulas de Control

    16/45

    Control Valve Applications

    10

    designs use the fluid pressure to help the closure member maintain a tight seating

    force. Soft seats are frequently used, but these may not be reliable in the high

    pressure drop situations, over 1500 psi (10 MPa), that frequently occur in this

    application category.

    Recirculation

    This application could be thought of as a subset of intermittent letdown in that

    the duty cycle is intermittent and the function performed is generally a process

    bypass situation. The bypass need is usually driven by the start-up, shutdown, orsystem-upset conditions. However, because the applications listed under this

    category are usually the most severe within the process system, they need special

    consideration to assure their reliable and long-term operability.

    Thus, the recirculation application is reserved for the cases in which either a

    pump or compressor is bypassed, as shown in Figure 12-4. In this case, the fluid

    that has been pressurized or compressed is reduced in pressure and returned to the

    pump or compressor inlet reservoir. The valves experience a wide range of

    pressures and temperatures, however, within a specific application, rangeability

    and control are seldom critical. The valve is usually closed, and its performance is

    judged by how well it shuts off. If shutoff is not maintained, the fluid must be

    repressurized for use by the process at increased energy expense. There have been

    cases in which recirculation loss is so high that the total output of the system ismeasurably reduced.

    A typical example of this application is the steam turbine bypass valve. This

    valve is installed to bypass the steam around the turbine until pressure and

    temperature are at appropriate turbine start-up conditions. The valves are

    closed as the turbine is brought on line. These turbine bypass valves can also

    be used for pressure relief valves per some code regulations, particularly in

    Europe. For safety purposes, the American Society of Mechanical Engineers

    Boiler and Pressure Vessel Code does not permit the use of this bypass control

    valve as the pressure relief valve. For the turbine bypass function, the most

    important valve attributes are usually shutoff, control, and opening speed.

    Another example involves the turbine drive of a synthetic gas compressor in

    an ammonia plant. The primary purpose here is not turbine protection butassuring there is high-pressure steam available to a downstream reformer if

    the gas compressor is tripped. Steam is needed to avoid catalyst deterioration

    resulting from carbon deposition and to provide time to achieve an orderly

    shutdown of the reformer. Thus, the trip-open function is very important in this

    application, requiring that the valves open in one to four seconds. Also,

    because of the fairly high pressure drop of 1000 psi (6.9 MPa), noise control is

    also a consideration in valve selection.

  • 7/29/2019 Aplicaciones Valvulas de Control

    17/45

    The Application Categories

    11

    Because most fluidsare erosive, particularlyliquids, a small leak

    through the valve willresult in the rapiddeterioration of theseating surfaces.

    Figure 12-4. Recirculation/Recycle Application.

    This valve will see the highest pressure drop in the entire plant when youbypass the main pump or compressor. The cost of fluid leakage through this valve

    traditionally exceeds the purchase price of a new valve many times over. This loss

    is seen in reduced plant efficiency, unavailable load and the increased pumping

    power required to pressurize or compress the fluid stream. It is not an application

    where the engineer should compromise on valve selection. The engineer must

    select a valve that will meet the long-term seat integrity requirements to assure

    leak-free operation. Frequently, this would utilize a design in which the fluid

    pressure assists in assuring that there are good seating forces between the closure

    member and the seat ring.

    Valves in this application go by many names depending upon whether it is flow

    through a pump or a compressor that is being bypassed. The most common names

    are as follows:

    Antisurge

    Mini-flow Bypass

    Recirculation

    Dump

    Recycle

    Kickback

    Return

    Leak-off

    Spillback

    Letdown

    Surge control

    In addition to the comments about leakage and control attributes discussedunder the intermittent letdown application, there are two other significant

    considerations concerning the selection of these valves. For liquid recirculation

    applications, those considerations are cavitation and vibration, and for compressor

    applications, they are noise and vibration. In both cases, the detrimental affect is

    caused by the high pressure drop associated with these valves and the

    accompanying low back pressure. The back pressure is usually near atmospheric

    but could be a vacuum if the downstream reservoir is a condenser. These

    applications frequently demand severe service valves that are specifically

    designed to handle these conditions.

  • 7/29/2019 Aplicaciones Valvulas de Control

    18/45

    Control Valve Applications

    12

    In summary, then, the key attributes for valves in this application, assuming

    proper sizing, of course, are as follows:

    Tight shutoff. Usually pressure assisted via piloted designs or unbalancedplug designs with large actuators.

    Anti-cavitation/low noise trim

    Pipe vibration elimination

    Secondary considerations include the following:

    Flow characteristics. Usually linear for pumps and characterized forcompressors

    Failure mode. Normally open

    Stroke speed. 2 to 5 seconds for compressible; up to 25 seconds forliquids

    Frequently, the speed requirement for the compressor antisurge valve drives the

    designer to question the capability of pneumatic actuators. High speeds can be

    achieved with a pneumatic system as is demonstrated by the actual field test

    results from a compressor recycle valve. As shown by Figure 12-5, that valve

  • 7/29/2019 Aplicaciones Valvulas de Control

    19/45

    The Application Categories

    13

    opened to 95% of full stroke in only 1.7 seconds. The valve and actuator sizes and

    conditions were as follows:

    Figure 12-5. Valve Position versus Time Opening.

    As this actual valve design demonstrates, a pneumatic actuator can achieve

    very rapid position changes to provide good surge control of the compressor. The

    air supply tubing to the actuator and the air source must be large enough to

    provide the rapid air flow rate to the actuator. Otherwise, speed will be limited.

    The air supply pressure to achieve this quick opening is dependent upon the valve

    hydraulic and friction forces. Thus, the air supply pressure may decrease and still

    allow the stroke time to be achieved, provided the pressure results in enough force

    to move the valve closure member. Consult the valve manufacturer if you are

    concerned that the air supply may be restricted.

    Fluid Mixed Refrigerant

    Actuator size 113 in2 730 mm2

    Valve stroke 24 in 610 mm

    Plug weight 1320 lb 600 kg

    Inlet pressure 190 psi 1.31 MPa

    Outlet pressure 45 psi 0.31 MPa

    Flow rate 1,620,000 lb/hr 735 t/h

    Air supply pressure 100 psi 0.69 MPa

  • 7/29/2019 Aplicaciones Valvulas de Control

    20/45

    Control Valve Applications

    14

    Valves in Parallel

    There are three primary reasons for having control valves in parallel. These are

    illustrated in Figure 12-6. All of the situations illustrated in the figure are driven

    by the process but are heavily influenced by the capability of the control valve

    selected.

    Figure 12-6. Parallel Valve Application.

    The first reason for having control valves in parallel is to have a redundant

    valve available in the event that problems with the primary valve develop. In this

    case, it is very important that the process be kept on line and running. The usual

    reason is the economics of the output product or the high cost of a shutdown. A

    shutdown may require a lengthy start-up time, or in some cases an unsafe

    condition could result from the lack of feed control. Certainly, the first

    consideration by the engineer is to use a highly reliable valve in this situation, a

    valve that is designed for the service conditions. An example in which these

    conditions would exist is in coal gasification, where erosive fluids cause valves to

    wear out quickly. To avoid repeated shutdown, parallel valves are used so that

    repair can take place while the process remains up and running. Another exampleis the use of parallel or redundant valves in the nuclear industry, where decay heat

    from the reactor core must be removed after a reactor is tripped. Thus, regardless

    of the reliability of the valve, the consequences of even a remote possibility that

    the primary valve will fail are offset by the availability of the redundant parallel

    valve system.

    A second reason for having two valves in parallel is to assure balance in the

    process equipment. Balance may mean equalizing temperature or chemical

    concentration, as in mixing situations, or splitting the flow stream for process

    benefit. As shown in Figure 12-6, an example of thermal balancing would be a

  • 7/29/2019 Aplicaciones Valvulas de Control

    21/45

    Valves in Parallel

    15

    heat exchanger that must have flow through both tube banks to assure that the

    tubes do not overheat. In this situation, the most common problem is that small

    signal changes to the valve result in too much flow change, a valve resolution

    problem. Generally, the resolution problem is related to the valve selection. Too

    much capacity has been installed, and/or the trim characterization does not

    provide sufficient gain for good resolution. There are valves available today that

    can provide extra rangeability and excellent characterization so that good controlis achievable. Valves that have an ability to achieve this capability but with

    different degrees of success are illustrated by Figures 12-7 through 12-12. The

    figures illustrate various design concepts used to expand the flexibility of the

    valve to meet a wide range of flow conditions. In many cases, a single

    manufacturer will supply more than one concept. It might be argued that the

    rangeability and characterization needs could be achieved by the control system

    feeding the correct signal to the valve. The problem arises in the valves ability to

    respond to the small signal change with a correspondingly small flow change. The

    trim design and characterization are key attributes that influence the flow response

    to the change in control signal.

    Figure 12-7. VRTTrim Valve. (Courtesy of Masoneilan)

  • 7/29/2019 Aplicaciones Valvulas de Control

    22/45

    Control Valve Applications

    16

    Figure 12-8. V-Line Series Noise Attenuator Ball. (Courtesy of Fisher Controls International Inc.)

    INSERT PHOTO HERE

  • 7/29/2019 Aplicaciones Valvulas de Control

    23/45

    Valves in Parallel

    17

    Figure 12-9. Cascade Trim Valve. (Courtesy of Copes Vulcan, Inc.)

    INSERT PHOTO HERE

  • 7/29/2019 Aplicaciones Valvulas de Control

    24/45

    Control Valve Applications

    18

    Figure 12-10. Mark OneGlobe Valve. (Courtesy of Valtek International)

    Figure 12-11. Q-BallValve Schematic. (Courtesy of Neles-Jamesbury Inc.)

  • 7/29/2019 Aplicaciones Valvulas de Control

    25/45

    Valves in Parallel

    19

    Figure 12-12. DragTrim Valve. (Courtesy of Control Components Inc.)

    INSERT PHOTO HERE

  • 7/29/2019 Aplicaciones Valvulas de Control

    26/45

    Control Valve Applications

    20

    Another example of valves in parallel to maintain balance is illustrated by the

    use of a three-way valve design to replace two valves in parallel, as illustrated in

    Figure 12-13. Control of the temperature of the fluid leaving the heat exchanger

    can be accomplished by bypassing a portion of the heating steam. To be

    successful, experience has shown that the bypass flow must be less than 25% of

    the total flow. As the bypass flow increases, the available pressure drop across the

    heat exchanger decreases with the lower flow through the exchanger. Thisincreases the pressure drop across the exchanger steam control valve branch,

    which now has to finely control the steam flow at a higher valve pressure drop in

    order to provide accurate temperature control. The pressure drop across the bypass

    valve branch has also increased with the lower exchanger flow. If the bypass valve

    outlet pressure drops below the valve pressure ratio that causes choking, then the

    ability to control temperature is lost since the bypass flow cannot be varied in the

    choked condition.

    That the mixing function of the three-way valve is an equivalent to the parallel

    valves is also apparent from Figure 12-13. In this situation, the two fluids would

    enter ports B and C and exit port A in proportion to the position of the valve

    stroke and porting size used in the design.

    Figure 12-13. Three-way Valve Substitute for Parallel Valves.

  • 7/29/2019 Aplicaciones Valvulas de Control

    27/45

    Valves in Parallel

    21

    When everything has been done right to achieve good rangeability, it may still

    be necessary to add a small valve in parallel with a larger capacity valve. This

    represents the third example of valves in parallel as illustrated in Figure 12-6. The

    smaller valve can either provide a fine control during the start-up or low load,

    called sequencing, or it can provide a trimming function for small process changes

    while operating at a higher load condition. The definition of the control logic will

    be based upon which need is dictated for the valves. From a valve integrity andlong-term reliability standpoint, the control logic designer should work to make

    sure the valves do not operate for extended periods with the valve closure element

    very near the seating surface. Travel at a position that causes the pressure drop to

    occur in the flow path between the closure member and the seating surface will

    cause erosion of these surfaces. The result is degradation of control, instability,

    and excessive leakage early in the valves life cycle.

    When two valves in parallel are sequenced for rangeability, the valve design

    and control logic selection are critical to a reliable system. The valve trim should

    not be of an inherent linear characteristic. The reason for this is that there is a

    discontinuity in the gain of the two valves when switching from one to the other.

    This is best understood by an example for an application involving continuous

    letdown and constant pressure drop.

    The transition from one valve to the other is usually quite fast relative to the

    process, which results in a bumpless transfer. The engineer should give

    consideration to the transition point so these valves are not continually opening

    and closing during normal operation. An operation that continually opens and

    closes will experience a gradual degradation due to premature wear. This higher

    wear rate can be avoided by performing proper Cv selection of the parallel valves.

    Reference 5 includes additional information on parallel logic involving control

    valves.

    The total capacity of valves in parallel is obtained simply by adding the Cvvalues of each valve in parallel. That is,

    Cv,o = Cv,1 + Cv,2 + + Cv,i (12-1)

    Consider a small valve with a Cv of 10 that is being sequenced with a valve with

    a maximum Cv of 100. Both valves have linear trim and actuators capable of

    one percent resolution. At the transition from the small valve to the large valve,

    the gain, or minimum change in Cv for the small valve is 1% of 10 or a 0.1 Cv

    change. After transition, the large valve gain is now in effect, and its gain is 1%

    of 100 or a Cv change of 1.0. Thus, the gain has increased ten times, creating a

    strong potential for an unstable or an oscillatory control scheme.

    When sequencing, the parallel valves should have a near equal percentage trim

    characteristic and be of equal gain on each side of the transition. This is shown

    in Figure 12-14 for the preceding example of two valves with a Cv of 10 and 100.

    It is assumed that the large valve has a minimum controllable Cv of 1/30 of thefull Cv. For this case, as load is increased and the small valve reaches its

    maximum Cv of 10, the larger valve is opened to a position of Cv equal to 10,

    and the small valve is closed. The gains are equal at the transition, and thus

    the process control resolution is not affected. Similarly, upon reducing load,

    the large valve controls until the Cv is down to 3.3, after which it closes and the

    small valve is opened to this capacity. The amount of overlap between valves is

    dependent upon many factors, which includes stroke time, valve

    characterization, and process response time.

  • 7/29/2019 Aplicaciones Valvulas de Control

    28/45

    Control Valve Applications

    22

    where

    Cv,o = overall Cv

    Cv,i = Cv of the ith valve

    Reference 6 discusses a fourth reason, controlling cavitation, for installing

    valves in parallel. This arrangement takes advantage of the change in thecavitation index of a valve when it opens, that is, less cavitation occurs at small

    openings. This reference provides measured cavitation index values for different

    valve designs as a function of the valve opening. In this situation, small openings

    refer to operation within 10 to 20% of the valve full-open position. If extended

    operation below 10% is needed, then other problems of control develop in that the

    valve trim parts may erode, vibrate, and create excessive noise. Another problem

    is the increased cost of a second valve, unless redundancy is a requirement.

    Reference 6 also discusses how cavitation could be controlled by placing two

    valves in series, as discussed in the next section. Again, increased cost is a

    disadvantage as is the potential that the upstream valve will adversely affect the

    downstream valves performance.

    Figure 12-14. Sequencing Two Parallel Valves of = % Trim.

  • 7/29/2019 Aplicaciones Valvulas de Control

    29/45

    Valves in Series

    23

    Valves in Series

    It is always desirable to

    use one valve becauseof the controlinstabilities that arise inthese seriesconfigurations.

    The use of control valves in series is usually driven by a desire to limit the

    pressure drop across a single valve. This may have been necessary many years

    ago. However, there are now valve designs that can absorb very high pressure drop

    conditions in a single valve without the accompanying problems of cavitation,

    erosion, vibration and noise. Table 12-1 provides pressure drop guidelines for

    different valve designs that will aid in the decision regarding whether valves inseries is a possible configuration. The cost of the valves, associated controls,

    installation, and calibrations would then be a second consideration.

    Table 12-1. Valve Type Selection Guide.

    Control instabilities are beyond the purpose of this discussion, but they canoccur when the fluid residence time between valves is much faster than the valve

    response time. As a general guide, the time constant of the valve should be less

    than the residence time of the fluid between the valves. For example, if the

    residence time is one second, the valve time constant should be one second or less.

    The time constant is defined as the time required to complete 63.2% of the total

    rise or decay of a step change in the signal to the valve. This is illustrated in Figure

    12-15. The residence time is calculated by dividing the distance between the two

    valves by the average fluid velocity in the connecting piping. That is,

    Residence Time = L/U = AL/w (12-2)

    where

    L = distance between valvesU = average fluid velocity

    A = piping flow area

    w = mass flow rate

    = fluid density

    Valve Type Flow Direction p1/p2 Limit* p/p1 Limit

    Multi-stage, Multi-path ------ No limit 1.0

    Multi-stage, Single-path ------ 5.5 .82

    Single-seat Globe Open 3.3 .70

    Close 2.3 .57

    Double-seat Globe ------- 3.3 .70

    Angle-body Cage Open 3.0 .67

    Close 2.3 .57

    Pinch ------ 2.9 .66

    Butterfly, 60% Open ------ 1.5 .33

    Reduced Ball, 80% ------ 1.2 .17

    *p1/p2 = 1/(1 p/p1)

  • 7/29/2019 Aplicaciones Valvulas de Control

    30/45

    Control Valve Applications

    24

    Figure 12-15. Single-Order Response Time.

    Instability also results if the pressure drop across one of the valves, particularly

    the downstream valve, becomes small, less than 20% of the overall pressure drop

    assigned to the valves. To assure a stable operation from this standpoint, a good

    rule is to have two-thirds of the overall pressure drop across the first valve and

    impose 80% of the drop as a top limit.

    Figure 12-16 shows a case in which control valves would be put in series, that

    is, when multiple lines feed downstream parallel processes and the designer places

    an inlet pressure reduction valve upstream of the distribution manifold. Such a

    case would occur on a gas burner distribution system where the inlet pressure is

    dropped and then individual valves control the gas flow to each burner.

    Figure 12-16. Series Valve Applications.

  • 7/29/2019 Aplicaciones Valvulas de Control

    31/45

    Frequent Application Problems

    25

    A gas transmission metering and reducing station is also an example of valves

    in series. A primary control valve reduces the pressure, and a monitor valve

    safeguards against the over-pressurization of the downstream line in case of the

    failure of the primary control valve. The system is designed for the primary valve

    to fail open and the monitor valve to fail closed.

    The overall capacity of valves in series if needed can be determined from the

    following equation:

    (1/Cv,0)2 = (1/Cv,1)

    2 + (1/Cv,2)2 + (1/Cv,i)

    2 (12-3)

    In these definitions, the overall pressure drop is used in the expression for Cv,0,

    and the pressure drop across each of the components is used in the Cv,i definition.

    This equation must also be used when a valve and another resistance component,

    such as a diffuser or orifice, is installed in series. (The Cv of an orifice or a diffusercan be approximated by using thirty times the flow area, where the area is

    expressed in square inches.) Failure to do so can result in an installed C v less than

    that required by the process.

    Frequent Application ProblemsIt is worthwhile to look at some of the common problems experienced when

    using control valves. These problems tend to be independent of the applications

    but can be aggravated by the unique needs of each installation. The root cause of

    these common problems varies from a lack of understanding of valve design and

    the selection of the wrong valve type (usually because of efforts to reduce initial

    capital cost) to poor calibration and maintenance.

    Controlling Pressure Drop

    The first problem to be discussed arises from the purposes of a control valve,

    which are to do the following:

    1. Convert energy by reducing the fluid pressure,

    2. Handle deviations from ideal operation,

    3. Handle the influence of unavoidable process changes,

    4. Permit the smooth transition from one load condition to another.

    To be able to achieve these objectives, there must be some pressure loss at the

    valve, and this results in an increase in fluid kinetic energy within the valve.

    Guidelines that have developed through many years of successful applications

    indicate that at least 10% of the system pressure drop should be available across

    the control valve to provide some control. To achieve good control, a value of 30%

    is desired. These guides are continually challenged, as in the case of the first

    application category discussed in this chapter, process control/feed regulation. Inthis application the most efficient plant operation would be to control the full-load

    condition without any energy absorption, an impractical goal. Thus, special

    attention must be devoted to the sizing pressure drop conditions to assure that the

    valve can modulate the feed flow and meet the control objectives.

    Excessive Fluid Velocities

    Throughout this discussion of control valve applications, we have referred to

    the problems of erosion, vibration, noise, cavitation, and flow instabilities. All of

    these problems can be eliminated by considering the control of fluid velocities

  • 7/29/2019 Aplicaciones Valvulas de Control

    32/45

    Control Valve Applications

    26

    during the flow and the accompanying pressure drop through the valve. Excessive

    fluid velocities cause widely varying local pressures because of the conversion of

    static pressure head to kinetic energy. This results in extreme turbulence and

    boundary layer separations as the fluid is forced to make directional changes in

    the flow path through the valve. The high fluid velocities and locally varying

    pressure differences cause the following:

    Uneven forces on moving parts leading to vibrations that cause excessivewear, breaking parts, unscrewing bolts, and noise and flow rateoscillations.

    Shock waves that lead to screech and high noise-level work environments.Even pipe breakage can occur, as noted in Reference 7, when the noise isin excess of 110 dBA.

    Cavitation and the rapid erosive wear of metallic surfaces near thelocation of the bubble collapse.

    Flashing of the fluid and the accompanying high-velocity liquid dropsthat erode metal surfaces.

    Erosion of metallic parts when the fluid has entrained hard solids such assand, pipe scale, weld slag, and catalyst.

    It should be apparent that good long-term control cannot be achieved when all

    or even one of these problems are present. Guidelines on what velocities are

    acceptable have been developed over many years of experience in a wide range of

    applications. These are expressed as a limit to the fluid kinetic energy exiting from

    the valve trim, as discussed in Reference 8.

    For the kinetic energy evaluation, the location in the valve that is of greatest

    concern is just downstream of where the fluid is throttled or controlled. At this

    location, the flow area is the smallest, and the fluid velocity and kinetic energy are

    the highest. The parts of the valve responsible for controlling and seating are often

    located at this point and are therefore subjected to the highest energy fluid.Figure 12-17 shows the throttle area for various kinds of valve trim. For a top-

    guided globe valve, the trim outlet flow area is the annulus area between the plug

    and seat. In a cage-guided valve, the trim outlet flow area is the exposed area of

    the windows in the cage. For a multi-path cage, the trim outlet flow area is the

    total area of all the exposed flow paths. For multi-stage trims, the flow area from

    stage to stage must not increase too rapidly or else the throttling will take place

    across the first stages, and the later stages will be ineffective (see Figure 12-17e).

    Butterfly and ball valves usually meet the presented criteria for kinetic energy.

    The pressure drop across these types of valves is not large enough to accelerate the

    flow to a high velocity level. Thus, a much lower value of energy is realized.

    In a valve, the disk or plug moves to increase or decrease the area through

    which flow can pass. For a given set of conditions, a fixed area of the trim is opento flow. Under any significant pressure drop conditions, this area will be

    considerably less than the inlet or outlet area of the valve. As a result, the fluid

    passing this point will have much higher velocities and kinetic energy levels than

    in other valve locations. The only way to increase this flow area without

    increasing the flow rate is to increase the resistance of the throttling flow path.

    The flow conditions defines how far the valve is open, and the valves trim design

    (flow path resistance) defines how much flow area exists at the trim outlet. Once

    this area is defined, the continuity equation can be used to calculate the velocity of

    the fluid at the outlet of the trim.

  • 7/29/2019 Aplicaciones Valvulas de Control

    33/45

    Frequent Application Problems

    27

    Figure 12-17. Throttling Exit Area (Ao) Examples for Typical Valve Trim Design.

  • 7/29/2019 Aplicaciones Valvulas de Control

    34/45

    Control Valve Applications

    28

    (12-4)

    The fluid density and velocity are used to establish the fluids kinetic energy:

    (12-5)

    Values for the constants M1, and M2 are shown in Table 12-2.*

    For gas or steam, the fluid velocity at the trim outlet may be sonic. If it is, the

    density of the fluid at the trim outlet must be higher than the outlet density (o) inorder to pass the given mass flow rate, w. This higher density can be estimated

    using Equation 12-4 by substituting the fluids sonic velocity, c, for the outlet

    velocity, Vo, and solving for density. This density and sonic velocity are then used

    in Equation 12-5 to find the kinetic energy.By including the effect of density in the criteria a single kinetic energy

    guideline can be defined for all fluids. Thus, the velocity for high-density fluids,

    such as liquids, would be much lower than for gases. Table 12-3 shows criteria for

    a valve trims outlet kinetic energy. The valve trim should be selected to keep the

    kinetic energy below these levels.

    Table 12-2. Numerical Constants for Velocity and Kinetic Energy Equations.

    For most conditions, an acceptance criterion of 70 psi (480 kPa) for the trim

    outlet kinetic energy will lead to a trouble-free valve. In some applications, where

    the service is intermittent (the valve is closed more than 95% of the time) and the

    fluid is clean (no cavitation, flashing, or entrained solids), the acceptance criteria

    can be increased but should never be higher than 150 psi (1030 kPa).

    * From the general form of the energy equation, potential energy is expressed in terms of a column height ofthe fluid. Similarly, kinetic energy is expressed in this discussion as a head. The form that is commonlyreferred to is the velocity head. The units of pressure are traditionally used for the velocity head expression,which can also be converted to a height of the fluid to be consistent with the potential energy term.

    For objects with a mass the kinetic energy is expressed as:

    KE= (mass)(V2/2)

    Similarly, the velocity head is an expression of the kinetic energy of the fluid, although in the form that

    is relative to a unit volume of the flowing medium. Thus,

    KE= (mass/volume)(V2/2) = V2/2

    The gravitational constant is usually shown in the denominator of the velocity head expression. This is

    required in order to convert from mass units to force units. The gravitational constant has been included inthe constant M2.

    Constant Units Used in Equations

    M w o Ao Vo KE

    M1 25 lb/h lb/ft3 in2 ft/s -

    1.0 kg/s kg/m3 m2 m/s -

    M2 4636.8 - lb/ft3 - ft/s psi

    1000 - kg/m3 - m/s kPa

    Vow

    M1oAo-------------------=

    KE1

    2---oVo

    2

    M2------------=

  • 7/29/2019 Aplicaciones Valvulas de Control

    35/45

    Frequent Application Problems

    29

    Table 12-3. Trim Outlet Kinetic Energy Criteria.

    In flashing service, liquid droplets are carried by their vapor at much higher

    velocities than would be the case for a single-phase liquid flow. To eliminate the

    risk of erosion in this situation, the acceptance criteria for flashing or potentially

    cavitating service should be lowered to 40 psi (275 kPa). The same criteria exists

    for liquids carrying entrained solids.

    Special applications may require even more stringent kinetic energy criteria.

    For example, pressure letdown valves used in pump test loops must be vibration-free so that a proper evaluation of the pump can be made. These valves are

    designed with trims that reduce the kinetic energy to less than 11 psi (75 kPa). Gas

    or steam valves with very low noise requirements may also result in extra-low trim

    outlet kinetic energy requirements.

    These kinetic energy criteria are additional sizing considerations that assure the

    reliable long-term operation of the control valve. A decision to ignore these rules

    may result in lower procurement cost but cause high operation and maintenance

    costs. In some cases, the ability of the valve to perform its control function may be

    jeopardized. References 9 and 10 present examples in which feedwater regulators

    could not perform the intended control function. Control was achieved when a

    trim was used that halved the fluid exit velocity of the originally installed cage

    trim and local smoothing of the flow path was incorporated.

    Remember to check thecalculated velocity tobe sure that it does notexceed the sonicvelocity of the fluid. Ifthe velocity is greater

    than sonic it must beset equal to sonicvelocity.

    The calculation of trim velocities and kinetic energy will require a knowledge

    of the cross-sectional area for the flow channel of interest as well as the number of

    ports. Approximate calculations can be made with some information about the

    valve design, but it is best to work with the manufacturer to obtain more accurate

    results. Another approach would be to use Equations 12-5 and 12-4 to calculate

    the Vo andAo, respectively, by fixing the kinetic energy at the Table 12-3 values.

    The area calculated is the area needed, at the valve travel, that passes the flow

    input to Equation 12-4. Then Equation 12-5 is used to calculate the fluid density

    so it can be used in Equation 12-4 with the velocity at sonic. This calculated area

    can then be compared with the flow area for the valve being proposed by the valve

    supplier. The actual area should always be greater than the calculated value in

    order to meet the kinetic energy selection criteria. A larger area would also be

    needed if cavitation or noise were major considerations in the application.

    Calibrating It Right

    A third problem involves achieving full-seat loading to maintain tight shutoff

    when the valve is closed. A prevalent practice is to calibrate the valve, or the

    bench set when a positioner is not used, so that the closure member (e.g., plug,

    diaphragm, disk) is just positioned at the seat instead of also assuring that the

    closure member is fully loaded against its seat.

    Service ConditionsKinetic Energy

    CriteriaEquivalent Water

    Velocity

    psi kPa ft/s m/s

    Continuous Service, Single-

    phase Fluids

    70 480 100 30

    Cavitating and Multi-phaseFluid Outlet

    40 275 75 23

    Vibration-sensitive System 11 75 40 12

  • 7/29/2019 Aplicaciones Valvulas de Control

    36/45

    Control Valve Applications

    30

    Unfortunately, it is not obvious to the inexperienced engineer that there must be agood seat load between the two mating seating surfaces. If there is not a sufficientload, then fluid leakage will rapidly erode the surfaces, the erosion time depending

    upon the valve pressure drop and fluid. If proper seat loads are not maintained, then it isimpossible to maintain design leakage rates.

    The situation is analogous to the manual control of the home water faucet. If

    the faucet is turned to just stop the water flow, it will not be long before it will startto drip. As a result of this experience, we subconsciously apply an extra torque to

    load the faucet plug against its seat to assure there will be no distracting or

    wasteful leakage.

    Full loading of a push-down-to-close sliding stem valve is only assured when

    the conditions within the actuator are as shown in Table 12-4. Single-acting

    actuators are most frequently a diaphragm design. With this design, the spring is

    either reducing the seating load or providing the entire seating force. The double-

    acting actuator is typically a piston design. With the piston design, the supplypressure is not limited as with the diaphragm design, and full-supply pressure is

    available to achieve higher seating forces. The higher pressures in the piston

    design have the additional benefit of increased stiffness and better control

    resolution.

    Table 12-4. Actuator Seating Load Source.

    As Baumann pointed out in his article on power signals (Reference 11), many

    designers think of the 4-to-20-mA signal as an information signal instead of a

    power signal. This signal, in the case of a control valve, is not only dictating the

    required position of the closure member, it also drives the operating power to

    position and seat the valve. When the valve is calibrated to be just closed at

    exactly 4 mA, the extra power built into the valve design to assure seating load is

    not applied. This seating load would only be applied when the control signal drops

    below 4 mA, a signal that is usually not built into the control system. Thus, the

    goal is to calibrate so that the valve positions and then seats with full loading

    when it is closed.

    CALIBRATION WITH POSITIONER

    For small signal changes on double-acting actuators, positioners are typically

    designed to maintain two-thirds to three-quarters of the supply pressure on the

    side of the piston in the direction of stem movement. In single-acting actuators,

    this bias pressure is replaced by a spring. In either case, the only way to ensure

    that maximum actuator load is provided to the valve seat when the valve is closed

    is through careful calibration.

    Actuator Type Conditions for Full Seat Load

    Single-acting, Spring to Open Supply Pressure on Top of Diaphragmor Piston Pushing toward the Seat

    Spring Pushing away from Seat

    Single-acting, Spring to Close Spring Pushing toward Seat

    0 psig under Diaphragm or Piston

    Double-acting Supply Pressure on Top of Piston

    Pushing toward the Seat0 psig under Piston

  • 7/29/2019 Aplicaciones Valvulas de Control

    37/45

    Frequent Application Problems

    31

    To ensure that the actuator fully loads the valve closure member against its seat,

    the calibrator has to purposely create a sufficient error between the valve position

    feedback to the positioner and the positioner input signal in order to cause the

    positioner to try to correct its position in the closing direction.

    To accomplish this, the positioner is typically calibrated to have the valve

    closure member reach the seat within the signal ranges shown in Table 12-5. The

    difference between these values and the true endpoint values of 3.0 psi, 15.0 psi(0.02 MPa, 0.10 MPa), 4.0 mA, or 20.0 mA is sufficient to create the error

    required within the positioner to cause it to provide maximum load in the seating

    direction.

    Table 12-5. Calibration for Seat Load.

    CALIBRATION WITHOUT POSITIONERS

    The problem of sufficient seat loading is particularly acute in throttling control

    valves that dont use a positioner. In these cases, the signal pressure to the actuator

    is also the operating pressure for the actuator. Even with the older standard signal

    ranges of 3 to 27 or 6 to 30 psi (0.02 to 0.19 or 0.04 to 0.21 MPa), resulting seat

    loads are considerably less than those available using a positioner, where up to

    full-supply pressure can be utilized to provide actuator thrust.

    Valve throttling applications without positioner control utilize a spring to

    oppose the operating pressure. They are generally of the spring and diaphragmstyle because of the low pressures involved and have large diaphragm areas

    relative to piston actuators.

    The user has very little flexibility in altering the calibration built into the

    factory selection of the actuator and spring. The spring force can be adjusted to

    increase the seating force, but if changed too much the valve may not fully open.

    Also, adjusting the valve when the valve is not pressurized may result in incorrect

    loads. This is because each valve design has its unique hydraulic and frictional

    forces upon which the actuator was selected and of which the user may not be

    aware.

    The calibration of the actuator takes into consideration two factors. The first is

    the actual signal pressure range. For example, if the designer counted on a 3-to-15

    psi (0.02 to 0.10 MPa) signal to the actuator being able to actually range from 0 to18 psi (0 to 0.12 MPa), the additional 3 psi (0.02 MPa) at the closed end of the

    stroke was assumed to provide seat load. If the valve is then calibrated in service

    to have a minimum of 3 psi (0.02 MPa) and a maximum of 15 psi (0.10 MPa)

    applied to the diaphragm, seat load will be reduced by 3 psi (0.02 MPa) times the

    diaphragm area, which is commonly several hundred pounds (kilograms).

    Reference 12 addresses this situation in the form of a standard that calls for an

    extended signal range.

    The second consideration in calibrating the actuator are the forces that the

    actuator will have to work with and against. These forces are hydraulic unbalance,

    Positioner SignalRange

    Valve Action onIncreasing Signal

    Positioner Signal when ClosureMember Just Contacts Seat

    3.0 to 15.0 psi(0.02 to 0.1 MPa)

    Opens >3.1 but 0.021 but 14.4 but 0.100 but 4.2 but 19.2 but

  • 7/29/2019 Aplicaciones Valvulas de Control

    38/45

    Control Valve Applications

    32

    friction, and seat load requirements. For example, if an actuator is intended by the

    user to be operated with a true 3-to-15 psi (0.02 to 0.10 MPa) signal, with no

    under- or over-ranging, the designer will have to build these loads, including seat

    load, into the actuator spring force or diaphragm force. This is commonly

    accomplished by selecting hardware that satisfies a bench set pressure range

    that may be quite different from the operating signal range of 3 to 15 psi (0.02 to

    0.10 MPa). This bench set pressure range is intended to allow the actuator tocompensate for the forces just noted when the valve is in service so that it will

    operate properly (e.g., provide the design seat load) within a 3-to-15 psi (0.02 to

    0.10 MPa) signal. To compensate for the requirement that there be an infinite

    number of springs to fit individual situations, spring adjusting screws are

    normally incorporated into the actuator design to achieve accurate spring forces.

    Thus, because of the relatively small available forces, when the technician sizes

    and selects actuators for throttling applications without a positioner it is critical

    that the technician calibrating the valve in the field know the operating pressure

    assumptions that were used to select the actuator and to calibrate the actuator

    accordingly. It should also be apparent that if the valve is moved to another

    application or fluid pressure conditions change in the existing installation, the

    technician will probably require new springs and a new calibration, or bench

    set, to assure the highest seating load.

    MORE CALIBRATION COMMENTS

    The calibration methods described in the preceding section provide excellent

    performance in almost every control system. In a control loop, the signal to the

    valve is created from a measurement in the process. The measurement is

    compared against a desired value, and a correction signal is then fed back to the

    valve. The valve responds to this signal to correct by changing position. Thus, in

    this basic function of the control valve there is no need for the travel stroke to

    match the input signal. So the calibration described in the last section will assure

    the design seat load when the valve is closed.

    The calibration described in the last section will provide a sufficient indication

    of valve position using the input signal to the valve. The position indication

    seldom must be highly accurate because it only provides relative feedback on the

    operation of the valve. If highly accurate position indication is required, a separate

    position transmitter can be added to provide this information.

    In the event that the calibration methods described in the last section are not

    acceptable, there are electrical and pneumatic devices that can then be added to

    the control schematic to cause a fully loaded seat interface when the signal

    reaches the closed position. These devices could add to the initial cost of the

    control valve, especially for small valves. However, this cost is much less than the

    maintenance cost associated with a valve that seals poorly. An example would be

    for a 3-to-15 psi (0.02 to 0.10 MPa) pneumatic signal, increasing signal to close,to add a high-gain relay so that at 15 psi (0.10 MPa) the power to the actuator

    would be the maximum supply pressure. But even in this case it would be

    advisable to set the relay at some signal level below 15 psi (0.10 MPa) to allow a

    margin for calibration or signal error. The control schematic for this example is

    shown in Figure 12-18 in which the full seating force is applied at 13.8 psi (0.095

    MPa), 1.2 psi (0.008 MPa) below the full closed signal. Some manufacturers

    current-to-pneumatic (I/P) converters have a snap-shut signal wherein the 3-to-15

    psi (0.02 to 0.10 MPa) output signal drops to zero as the 4-to-20 mA command

    drops below 4.2 mA.

  • 7/29/2019 Aplicaciones Valvulas de Control

    39/45

    Frequent Application Problems

    33

    Figure 12-18. Control Schematic to Modulate between 10% and 100% Open.

    The schematic shown in Figure 12-18 is for a 3-to-15 psi (0.02-0.10 MPa)

    modulation signal with increasing signal to close the valve, using a double-acting

    piston-type actuator. The actuator is fitted with a spring for fail-open on loss of thesignal. A regulator between the supply and snap-acting relay is set at 20 psi (0.138

    MPa). The snap-acting relay is set at 13.8 psi (0.095 MPa), which represents the

    signal for the 10% open position. When the signal is modulating between 3 and

    13.8 psi (0.02 and 0.095 MPa), the high selector and snap-acting relays are in the

    positions shown. Thus, the positioner receives the modulating signal and moves

    the valve actuator in accordance with the demanded position. When the signal

    exceeds 13.8 psi (0.095 MPa), the snap-acting relay changes position from

    venting to straight-through. The 20 psi (0.138 MPa) signal from the regulator then

    changes the high selector relay position and feeds this pressure to the positioner.

    The 20 psi (0.138 MPa) signal into the positioner causes the valve to go fully

    closed with the pressure above the piston at the supply pressure and the pressure

    below the piston at atmospheric. Thus, the maximum actuator force is directed to

    sealing the valve closure member.

    Other schematics can be created to assure full seating load for decreasing signal

    to close and for single-acting actuators.

    Operating Close to the Seat

    An application problem that is frequently encountered involves the extended

    duration of operating the valve with its closure member close to the valve seat

    (approximately 5% or less). Such operation causes seat deterioration. Under this

    low-flow condition, the flow path is the small opening between the closure

  • 7/29/2019 Aplicaciones Valvulas de Control

    40/45

    Control Valve Applications

    34

    member and seating surfaces. The fluid velocities can be extreme, resulting in

    erosion, noise, vibration, and, for liquids, cavitation damage. In some cases,

    erosion is so severe that the damage to the valve at low lift increases flow area, and

    the valve cannot control a needed minimum flow. To eliminate this problem, the

    minimum controllable flow must be determined from the process data and valve

    designs selected that have the needed rangeability for the application.

    The control schematic shown in Figure 12-18 can also be used to avoidoperation with the closure member close to the seat. When the valve stroke

    reaches a preset position, the snap-acting relay changes positioner signal causingthe valve to fully close and apply the full seating force.

    Poor Assembly

    Another contributor to valve problems is poor assembly in the field. It is critical

    that the manufacturers assembly instructions be followed to assure that trim parts

    are aligned well and, as discussed earlier, calibrated properly. The mechanical

    assembly of a valve may seem quite straightforward; however, the assembler may

    not be aware of the special design features included to assure a good functional

    control valve and its dependence upon proper assembly procedures.

    The issue of the alignment of parts is particularly critical in many applications.If alignment is not maintained within tolerances then the seating line or contact

    area between the closure member and the seat ring may not be as anticipated.

    Significant leakage will occur with the long-term erosion of these sealing

    surfaces. The erosion of parts also reduces the valves ability to provide good

    control.

    Another adverse effect of poor alignment is that the stem may be scratched and

    galled because of the close tolerances within the spacers and guides used in the

    packing box. If the stem becomes scored then the packing will have a dramatically

    reduced life as packing material is removed from the packing box during

    modulation. In general, the higher the fluid pressures, the tighter the spacer

    tolerances. The tight tolerances are needed to minimize the extrusion of the

    packing material from the box.Poor alignment results in high friction for the moving parts. This is not always

    apparent at the time of assembly. Friction can become a major problem during theoperation of the valve as the fluid system reacts to the excessive movement of the

    valve disk or plug in response to the higher friction. This excessive movement will

    cause the valve to continually search for the position that corresponds to the

    system control point.

    Poor alignment generally results from improper torquing of the packing box

    and the valve bonnet bolting. The latter is the body/bonnet closure joint that seals

    the internal valve pressure from the ambient. Both of these bolted joints must be

    tightened by bringing the mating components together while maintaining them as

    close to their final and fitted relationship as possible. While parts will have tight-

    fitting location registers, improper torquing will push the mating parts to theextreme of the tolerances, thus reducing design margins. Correct tightening of the

    bolts is achieved by using a crisscross tightening pattern and working up to the

    final torque value in small steps. If too large a torquing step is used, the parts

    become skewed and remain so through the final torque sequence. The skewed

    posture loads the internal mating parts non-uniformly and causes a misalignment.

    Tightening the packing box is a critical operation in the assembly of most

    valves. Regardless of the packing design supplied by the valve manufacturer, the

    instructions should be rigidly followed to assure alignment and to avoid excessive

    packing friction. Tightening is most critical in the high-temperature graphite

  • 7/29/2019 Aplicaciones Valvulas de Control

    41/45

    Frequent Application Problems

    35

    packing designs. This procedure generally involves a sequence of torquing levels,

    with the valve stem moved three or more times at each torque level until the

    maximum sealability torque is achieved. The torque is then backed off to a

    maximum operability torque level for optimum control. The torque levels

    should then be verified periodically during the start-up and operation of the valve

    to assure the optimum control performance. The maximum sealability and

    operability levels will vary depending upon the pressure rating of the valves.

    To assure that the finaltorque level results in aproperly bolted joint allmating parts includingthe studs and nuts,must be well lubricated.It is not uncommon tolose between 20 and40% of the torque valueto friction betweenthese parts.

    Do not reuse old seals and gaskets when reassembling a control valve. The

    seals and associated springs will take a permanent set in the application, whether

    elastomeric or graphite. They may not have the strength to initiate a proper seal on

    reuse. Elastomeric materials may be near the end of their lives and fail because of

    brittleness or poor ductility. Small nicks in the seals may also contribute to leak

    initiation and the subsequent erosion of the seal in the application. The

    replacement seals should be of the original design because special compositions

    or winding processes may have been specified by the manufacturer to assure

    proper function and long life for the specific application. The small cost of using a

    new and correct set of these soft goods is minor in comparison to the cost of

    excessive leakage or poor control function. In some cases, the reuse of seals and

    gaskets can even result in a shutdown of the process.

    Depending upon the design, there are times when it is necessary to connect the

    actuation system to the valve in a way that assures that an actuator stop does not

    limit the seating load. In some cases, this could even hold the closure member off

    of the sealing surface. The assembler must make sure that the seating load is not

    limited. The manufacturer must provide instructions that will assure that this

    attachment process can be done correctly.

    Following the proper assembly procedure assures that the design features of the

    valve are not compromised or negated. Thus, the reliability and performance of

    the valve will fulfill expectations.

    Actuator Supports

    Occasionally it is necessary to provide added support for a valve actuator. Thismay be the case if the actuator is quite heavy, such as for many electrical and

    electro-hydraulic designs, or when the valve is installed in a position in which theactuator is off the vertical centerline. In these cases, it is very critical that the

    support be flexible enough to allow for the thermal growth of the piping system

    and that the installation does not impose large lateral forces. Such forces could

    cause higher friction on the valves moving parts.

    Trying to stop pipelinevibration by holding theactuator is analogousto trying to stop a trainwith your car.

    The ideal support system is simply a pulley with a dead-weight

    counterbalancing the weight of the actuator, as shown in Figure 12-19. Other

    support systems require enough design effort to be assured that the actuator is not

    constrained or deflections imposed that add undesirable side loads on the actuator.

    One criterion that should never be used when designing a support system is to

    attempt to limit vibration and in particular to limit a pipeline vibration problem.

    The former almost always results in the fatigue failure of a restrained component

    and the latter will result in short-term destruction of the valve-actuator assembly.

    The vibration issue must be resolved by using damping devices mounted directly

    on the pipe or by eliminating the root cause of the vibration.

  • 7/29/2019 Aplicaciones Valvulas de Control

    42/45

    Control Valve Applications

    36

    Figure 12-19. Supporting a Heavy Actuator.

    System Debris and Flushing

    During new construction or the major repair of existing equipment there is

    always debris generated by the processes of cutting, machining, grinding,

    welding, erection, and installation. This occurs in spite of efforts to make sure the

    fluid side of the system is clear of all trash. Thus, it is critical that the system beflushed and the internals of valves and other critical equipment be protected by

    removing debris or by providing upstream strainers during initial operation to

    minimize damage caused by the debris. The effort to assure that a system is

    cleaned by flushing it requires significant planning; however, the investment pays

    itself back many times by extending the life of the many components in the

    system. To assist in this planning process, the reader is referred to References 13

    through 16. A measure of the significance of this issue is provided in Reference

    15, which noted that nine tons of iron oxide were removed from the power plant

    piping. The Installation and Location section of Chapter 18 ofControl Valves

    includes other examples of debris problems.The influence of debris in a system can have a very detrimental impact on the

    control valves. In the references cited in this chapter it is recommended that thetrim be removed before the flushing operations and that some sacrificial trim be

    subs