PREPARADO POR: ING. RODRIGO G. CÁRCAMO M. CICH 3062 JUTICALPA, OLANCHO. MAYO DE 2005 PROPIETARIO: PATRONATOS DE LAS COLONIAS “SANTA MARÍA, 25 DE FEBRERO, SITRAMEDHYS Y SANTA EDUVIGES” PROYECTO DE: ALCANTARILLADO SANITARIO

Upload: tranhanh

Post on 02-Feb-2018

233 views

Category:

Documents


1 download

TRANSCRIPT

Page 1: ALCANTARILLADO SANITARIO - · PDF filealcantarillado sanitario memoria tÉcnica colonias “ santa marÍa, 25 de febrero, sitramedhys y santa eduviges ” Índice 1. generalidades

PREPARADO POR: ING. RODRIGO G. CÁRCAMO M.

CICH 3062

JUTICALPA, OLANCHO. MAYO DE 2005

PROPIETARIO: PATRONATOS DE LAS COLONIAS “SANTA MARÍA, 25 DE FEBRERO,

SITRAMEDHYS Y SANTA EDUVIGES”

PROYECTO DE:

ALCANTARILLADO SANITARIO

Page 2: ALCANTARILLADO SANITARIO - · PDF filealcantarillado sanitario memoria tÉcnica colonias “ santa marÍa, 25 de febrero, sitramedhys y santa eduviges ” Índice 1. generalidades

COLONIAS: SANTA MARÍA, 25 DE FEBRERO, SITRAMEDHYS Y SANTA EDUVIGES

Preparado por: Ing. Rodrigo G. Cárcamo M. CICH 3062

CONSULTORIA Y DISEÑO CÁRCAMO MURILLO CODICAM

SISTEMA DE ALCANTARILLADO SANITARIO

Page 3: ALCANTARILLADO SANITARIO - · PDF filealcantarillado sanitario memoria tÉcnica colonias “ santa marÍa, 25 de febrero, sitramedhys y santa eduviges ” Índice 1. generalidades

COLONIAS: SANTA MARÍA, 25 DE FEBRERO, SITRAMEDHYS Y SANTA EDUVIGES

Preparado por: Ing. Rodrigo G. Cárcamo M. CICH 3062

CONSULTORIA Y DISEÑO CÁRCAMO MURILLO CODICAM

ALCANTARILLADO SANITARIO

MEMORIA TÉCNICA

COLONIAS “ SANTA MARÍA, 25 DE FEBRERO, SITRAMEDHYS Y SANTA EDUVIGES ”

ÍNDICE

1. Generalidades

1.1 Objetivos del Proyecto 1.2 Área de Influencia del Proyecto 1.3 Topografía

2. Memoria Descriptiva 2.1. Naturaleza del Flujo 2.2. Dotación a usar 2.3. Gasto de infiltración 2.4. Período de diseño 2.5. Análisis hidráulico 2.6. Diámetro mínimo 2.7. Volúmenes de aguas 2.8. Pendientes permisibles 2.9. Velocidades permisibles

3. Instalación de Tuberías

3.1. Ancho de Zanja 3.2. Instalación de Tubería 3.3. Relleno de Zanja

4. Obras Complementarias 4.1. Pozos de Inspección 4.2. Estructuras complementarias 4.3. Descarga 4.4. Pruebas de los sistemas 4.5. Deposición final de excretas

5. Memoria de Cálculo y Planos

5.1. Memoria de cálculo 5.2. Planos

Page 4: ALCANTARILLADO SANITARIO - · PDF filealcantarillado sanitario memoria tÉcnica colonias “ santa marÍa, 25 de febrero, sitramedhys y santa eduviges ” Índice 1. generalidades

COLONIAS: SANTA MARÍA, 25 DE FEBRERO, SITRAMEDHYS Y SANTA EDUVIGES

Preparado por: Ing. Rodrigo G. Cárcamo M. CICH 3062

CONSULTORIA Y DISEÑO CÁRCAMO MURILLO CODICAM

1. GENERALIDADES

1.1. Objetivos del Proyecto: Este proyecto de alcantarillado sanitario es para cubrir la

demanda de saneamiento básico de este sector de la ciudad, ya que carece de dicho

sistema, el presente proyecto se desarrollará en forma técnica y estructurada conforme

a las políticas y estándares del Plan Maestro de Alcantarillado Sanitario de la ciudad de

Juticalpa y de Urbanización y Desarrollo de la Municipalidad de Juticalpa, Departamento

de Olancho.

1.2. Área de Influencia del Proyecto: Este Proyecto de alcantarillado sanitario se desarrollará

en las Colonias: Santa María, 25 de Febrero, Sitramedhys y Santa Eduviges. Estas

colonias en conjunto tiene un área aproximada de 20 hectáreas (28.5 manzanas),

beneficiando a una población estimada de 3,000 habitantes. Este proyecto encuentran

ubicado en el sector sur oeste de la ciudad de Juticalpa, Departamento de Olancho.

1.3. Topografía: El levantamiento topográfico se realizó con sistema de topografía

convencional, obteniendo los datos necesarios en planimetría y altimetría, para permitir

un resultado confiable al momento de realizar los estudios de Alcantarillado Sanitario de

las colonias antes mencionadas.

El terreno presenta una topografía variable, pero mayormente plano, en toda el área del

proyecto, pero con pendientes satisfactorias para las evacuaciones del sistema a

analizar.

2. MEMORIA DESCRIPTIVA.

2.1. Naturaleza del Flujo: El drenaje sanitario es un porcentaje del abastecimiento de agua

que la comunidad desecha, el cual proviene de las cocinas, baños, lavabos, sanitarios,

lavaderos, etc. Algunos residuos se mantienen en suspensión otros en solución y otros

Page 5: ALCANTARILLADO SANITARIO - · PDF filealcantarillado sanitario memoria tÉcnica colonias “ santa marÍa, 25 de febrero, sitramedhys y santa eduviges ” Índice 1. generalidades

COLONIAS: SANTA MARÍA, 25 DE FEBRERO, SITRAMEDHYS Y SANTA EDUVIGES

Preparado por: Ing. Rodrigo G. Cárcamo M. CICH 3062

CONSULTORIA Y DISEÑO CÁRCAMO MURILLO CODICAM

tan finamente divididos que adquieren características de partículas coloidales.

El flujo de aguas de desecho incluye aguas residenciales domésticas, de escurrimiento

pluvial e infiltración de aguas subterráneas.

2.2. Dotación a usar: La dotación que se usará para aguas negras será el 75% del consumo

promedio Diario (Cmd) siendo éste de 40.0 galones por persona por día (151.4 LDPP) y

tomándose un total de seis personas por lote, los resultados son los siguientes: 32

galones por persona por día (121.12 LDPP).

2.3. Gasto de Infiltración: La absorción y la infiltración se tomará como cuatro (4) veces él

gasto promedio en el caso de tuberías de concreto en redes secundarias. Para tuberías

de PVC. se tomará como dos (2) veces el gasto promedio. Para colectores principales de

concreto se tomará un valor de 2,200 litros por pulgada de diámetro y kilómetro de

longitud por día.

2.4. Período de Diseño: Se diseñara un sistema que tome en consideración la vida útil de

cada elemento como a continuación se detalla:

ELEMENTO DEL SISTEMA VIDA ÚTIL

Alcantarillas colectores principales 20 años mínimo

Planta de tratamiento: 10 años mínimo

Edificios 20 años mínimo

Obras de tratamiento 10 años mínimo

Equipo 10 años mínimo

2.5. Análisis Hidráulico: El cálculo hidráulico de las alcantarillas se hará sobre la base de la

fórmula de Manning para el flujo de canales abiertos, usando el coeficiente de rugosidad

“n” igual a 0.011 para tubería de PVC. y 0.015 para tuberías de concreto.

2.6. Diámetro Mínimo: Se podrán usar diámetros de 152 mm en los tramos cabeceras de la

Page 6: ALCANTARILLADO SANITARIO - · PDF filealcantarillado sanitario memoria tÉcnica colonias “ santa marÍa, 25 de febrero, sitramedhys y santa eduviges ” Índice 1. generalidades

COLONIAS: SANTA MARÍA, 25 DE FEBRERO, SITRAMEDHYS Y SANTA EDUVIGES

Preparado por: Ing. Rodrigo G. Cárcamo M. CICH 3062

CONSULTORIA Y DISEÑO CÁRCAMO MURILLO CODICAM

red siempre y cuando estos no excedan una longitud de 100 metros y en los tramos

subsiguientes de la red se podrá utilizar un diámetro mayor de 203 mm. Cada unidad

habitacional deberá tener una conexión domiciliaria para su uso exclusivo y con un

diámetro mínimo de tubería de 102 mm de PVC. SDR-50, bajo una buena compactación.

Bajo condiciones de niveles friáticos altos, el sistema podrá construirse usando tubería

de PVC con los diámetros especificados.

2.7. Volúmenes de Aguas Negras: El cálculo del volumen de aguas negras generado se

estimará multiplicando el consumo total por la población servida. Se considerará un

promedio de seis personas por lote.

2.8. Pendientes Permisibles:

a. La pendiente mínima será la necesaria para producir una velocidad real mínima de

0.45 m/s.

b. La pendiente máxima será la necesaria para producir una velocidad límite de 5.00

m/s.

2.9. Velocidades Permisibles:

a. Velocidad Mínima: Para evitar la sedimentación de materia sólida, materia mineral o

partículas discretas, la velocidad mínima auto-limpiante para cualquier tramo será

de 0.45 m/s, respetando las normas vigentes del País. Sin embargo, por razones

justificables, esta velocidad podrá ser menor cuando el tirante de flujo

correspondiente al gasto mínimo, sea menor que un cuarto (¼) del diámetro de la

sección tratada, pero en ningún caso la velocidad será menor a 0.30 m/s.

b. Velocidad Máxima: Para evitar que la materia en suspensión o partículas discretas

causen el deterioro a las tuberías y estructuras del sistema, mediante la acción

erosiva, la velocidad máxima permisible en cualquier tramo será de 5.00 m/s, a

sección parcialmente llena.

Page 7: ALCANTARILLADO SANITARIO - · PDF filealcantarillado sanitario memoria tÉcnica colonias “ santa marÍa, 25 de febrero, sitramedhys y santa eduviges ” Índice 1. generalidades

COLONIAS: SANTA MARÍA, 25 DE FEBRERO, SITRAMEDHYS Y SANTA EDUVIGES

Preparado por: Ing. Rodrigo G. Cárcamo M. CICH 3062

CONSULTORIA Y DISEÑO CÁRCAMO MURILLO CODICAM

3. INSTALACIÓN DE TUBERÍAS

3.1. Ancho de Zanja: Para un correcto comportamiento de las tuberías es necesario tener en

cuenta anchos de zanja mínimos de acuerdo al análisis de los resultados de diferentes

instalaciones efectuadas. La excavación de la zanja debe ser lo suficientemente ancha

para permitir a un hombre trabajar en condiciones de seguridad, adecuada alineación,

ensamble de las uniones y compactación del material de relleno.

El ancho será el diámetro exterior más 0.30 m para cada lado de la tubería.

3.2. Instalación de Tubería. El interior de los tubos debe conservarse siempre libre de tierra

y otros materiales a medida que el trabajo progresa y se dejará perfectamente limpio en

el momento de la terminación.

Para el caso de tubería plástica la inspección de la tubería instalada se realizará con la

verificación de las máximas deflexiones diametrales iniciales, de acuerdo a las

establecidas por la fábrica de tubería.

La verificación del cumplimiento de estas deflexiones se debe efectuar inmediatamente

después de realizar el lleno máximo de la brecha y en forma posterior. Los tubos

instalados cuyas deflexiones iniciales excedan el porcentaje establecido por el

fabricante, deberán ser liberados de sus cargas de forma que la deflexión inicial se

ajuste.

Cuando la zanja queda abierta durante la noche o la instalación de tuberías se

suspenda, los extremos de los tubos se mantendrán parcialmente cerrados para evitar

que penetren basuras, barro y sustancias extrañas, pero permitiendo el drenaje de la

zanja.

Los lubricantes utilizados para la colocación de empaques, en caso de requerirse, deben

Page 8: ALCANTARILLADO SANITARIO - · PDF filealcantarillado sanitario memoria tÉcnica colonias “ santa marÍa, 25 de febrero, sitramedhys y santa eduviges ” Índice 1. generalidades

COLONIAS: SANTA MARÍA, 25 DE FEBRERO, SITRAMEDHYS Y SANTA EDUVIGES

Preparado por: Ing. Rodrigo G. Cárcamo M. CICH 3062

CONSULTORIA Y DISEÑO CÁRCAMO MURILLO CODICAM

ser los especificados por el fabricante de la tubería, en ningún caso se usarán materiales

derivados del petróleo.

Las uniones de caucho y sus sellos se almacenarán en sus empaques y no se expondrán

a los rayos del sol, grasas y aceites derivados del petróleo, solventes y sustancias que

puedan deteriorarlos.

Para la instalación de tubería, se requiere contar con una comisión de topografía

permanente.

3.3. Relleno de Zanja:

a. Afirmado para Soporte de Tubería: La función primordial de la cama es la de ofrecer

un apoyo firme, continuo y homogéneo en donde se pueda posar

convenientemente la tubería retirando cualquier objeto extraño que pueda

impedirlo.

Si se presentara el caso de un material poco consistente en el fondo de la zanja o la

existencia de niveles freáticos altos, se recomienda un encamado en piedra y

gravilla con suficiente espesor como para mejorar las condiciones del suelo y drenar

el agua permitiendo el trabajo en seco.

b. Cimentación de Tubería: La cama de tubería estará conformada por una capa

continua de material selecto compuesto por gravilla ó relleno Tipo 2. Esto permitirá

absorber las irregularidades que queden en el fondo de la zanja al realizar la

excavación.

c. Atraque de Tubería: La zona de atraque de tubería estará conformada por gravilla o

arena, y será colocado a partir de la cimentación, hasta una altura del diámetro

exterior de la tubería, la cuál será definida por el fabricante de tubería

d. Atraque de Tubería: La zona de atraque de tubería estará conformada por gravilla

Page 9: ALCANTARILLADO SANITARIO - · PDF filealcantarillado sanitario memoria tÉcnica colonias “ santa marÍa, 25 de febrero, sitramedhys y santa eduviges ” Índice 1. generalidades

COLONIAS: SANTA MARÍA, 25 DE FEBRERO, SITRAMEDHYS Y SANTA EDUVIGES

Preparado por: Ing. Rodrigo G. Cárcamo M. CICH 3062

CONSULTORIA Y DISEÑO CÁRCAMO MURILLO CODICAM

o material selecto, y será colocado a partir de la cimentación, hasta una altura del

diámetro exterior de la tubería, la cuál será definida por el fabricante de tubería.

e. Material Selecto: Este relleno se construirá desde el atraque de la tubería hasta 0.20

m sobre la corona de la tubería. La plasticidad de este material no será superior al

8% y en su defecto deberá estabilizarse con arena. Dicho relleno se colocará y

compactará en capas de 20 cm. con especial cuidado a cada lado de la tubería.

f. Relleno Material del Sitio. Este relleno será colocado a partir del relleno de material

selecto, se efectuará el relleno con material seleccionado de la excavación del sitio

en capas de 20 cm. compactadas con medios mecánicos.

El material seleccionado de la excavación será el que presente el menor grado de

humedad para que la compactación sea la adecuada.

El acabado final de este relleno compactado deberá dar la apariencia del estado original,

cuando estos rellenos se realicen en tramos que crucen vías sin pavimentar se deberá

mejorar la compactación hasta un 70% del próctor modificado.

4. OBRAS COMPLEMENTARIAS.

4.1. Pozos de Inspección:

a. La distancia máxima entre pozos de inspección será de 100 metros para tuberías de

diámetros menores o iguales a 450 mm y para tuberías mayores o iguales a 600

mm será de 120 metros.

b. La cobertura mínima sobre la corona de la tubería será de 1.00 metro para calles

vehiculares y 0.80 metros en pasajes peatonales. Las profundidades máximas de la

invertida dependerán de la zona a urbanizar.

c. Todos los conductos serán ubicados en los ejes de las calles y avenidas, a las

Page 10: ALCANTARILLADO SANITARIO - · PDF filealcantarillado sanitario memoria tÉcnica colonias “ santa marÍa, 25 de febrero, sitramedhys y santa eduviges ” Índice 1. generalidades

COLONIAS: SANTA MARÍA, 25 DE FEBRERO, SITRAMEDHYS Y SANTA EDUVIGES

Preparado por: Ing. Rodrigo G. Cárcamo M. CICH 3062

CONSULTORIA Y DISEÑO CÁRCAMO MURILLO CODICAM

profundidades tales que puedan drenar por gravedad desde todos los lotes, también

deberá preverse la contaminación a los conductos de agua potable.

d. Los pozos de inspección deberán construirse según las especificaciones y detalles

suministrados por la Municipalidad de Juticalpa, Departamento de Olancho. Deberán

ser repellados por fuera y por dentro bajo condiciones normales, y en condiciones

de nivel friático elevado estos deberán ser impermeabilizados por fuera y por

dentro.

e. Las caídas en los pozos de caída no deben ser mayor de 0.60 metros.

f. Si la urbanización ha de ser pavimentada con concreto hidráulico o Asfáltico, las

tapaderas y casquetes de los pozos deberán ser de hierro fundido según diseño

proporcionado por la Municipalidad de Juticalpa, Departamento de Olancho. Los

casquetes y tapaderas podrán ser de concreto reforzado de 210 kg/cm², según

diseño proporcionado por el Departamento de Ingeniería Municipal, siempre y

cuando se tenga la respectiva aprobación.

4.2. Estructuras Complementarias:

a. Pozos de Inspección: Se construirán un total de 29 pozos de Inspección de tipo

común, la mayoría con una altura promedio de 1.50 m, encontrándose pozos con

profundidades de hasta 2.75 m. No será necesario la construcción de pozos de

caída, ya que las pendientes son moderadas. Los pozos se situaron al inicio de

cada ramal, en los cambios de alineamiento, ya sea vertical u horizontal, en todas

las intersecciones o sitios de concurrencia de tubería y cambios de diámetro.

El mortero para los pozos deberá fabricarse con una relación cemento-arena de 1:2.

Además el pozo será impermeabilizado con un afinado de cemento en sus paredes

interiores. El cono de reducción se empezará a construir a partir de 0.60 metros

desde el nivel del casquete terminado para los pozos cuya altura sea de 1.20

Page 11: ALCANTARILLADO SANITARIO - · PDF filealcantarillado sanitario memoria tÉcnica colonias “ santa marÍa, 25 de febrero, sitramedhys y santa eduviges ” Índice 1. generalidades

COLONIAS: SANTA MARÍA, 25 DE FEBRERO, SITRAMEDHYS Y SANTA EDUVIGES

Preparado por: Ing. Rodrigo G. Cárcamo M. CICH 3062

CONSULTORIA Y DISEÑO CÁRCAMO MURILLO CODICAM

metros o menos, y a partir de 0.80 metros para los pozos de mayor altura. El

concreto para la base de cimentación tendrá una resistencia a la compresión de 210

Kg./cm².

Sobre la base del pozo se construirán las medias cañas de transición, cuya forma

será la de una “U”. La pendiente del piso del pozo será del 15.0% hacia las medias

cañas. Se instalarán peldaños de varilla corrugada No. 5, espaciados 0.40 metros y

alineados en forma alterna. Las tapaderas serán de concreto reforzado con varillas

No. 4, espaciadas a 0.10 metros, en ambas direcciones y tendrá un espesor de 7.5

cm.

b. Conexión Domiciliaria: Las acometidas domiciliarias se construirán conjuntamente

con el alcantarillado principal y se llevará hasta la acera, donde se construirá una

caja de inspección con ladrillo rafón con dimensiones de 0.60 x 0.60 x 0.60 m,

repellada e impermeabilizada interiormente con un mortero con relación 1:2 y

tendrá su respectiva media caña, la caja deberá tener una tapa removible a nivel de

la superficie con el objeto de facilitar las labores de mantenimiento en la conexión

domiciliar. Tendrán una base de concreto simple de 0.10 metros de espesor y en su

fondo se construirá una media caña de transición. Todas serán de forma cuadrada,

estando sus dimensiones en función de su profundidad.

El diámetro de la acometida será mínimo de 100 mm, la pendiente mínima será del

2%. La acometida se conectará al alcantarillado en la parte media superior de este.

Todas las conexiones de acometidas de alcantarillado a las redes principales que

sean de material diferente a tuberías de concreto, se harán por medio de “yees”

facilitadas por la constructora de tubería, en caso contrario podrán ser

prefabricadas para evitar la rotura posterior de la tubería. Cuando esto no sea

posible por existir de antemano la tubería, el empate a ella se hará por medio de un

Page 12: ALCANTARILLADO SANITARIO - · PDF filealcantarillado sanitario memoria tÉcnica colonias “ santa marÍa, 25 de febrero, sitramedhys y santa eduviges ” Índice 1. generalidades

COLONIAS: SANTA MARÍA, 25 DE FEBRERO, SITRAMEDHYS Y SANTA EDUVIGES

Preparado por: Ing. Rodrigo G. Cárcamo M. CICH 3062

CONSULTORIA Y DISEÑO CÁRCAMO MURILLO CODICAM

tubo recortado cuidadosamente en ángulo de 45° con su propio eje.

4.3. Descarga: Se deberán descargar las aguas residuales en los pozos de la red pública

existente. En el caso de que se requiera una estación de bombeo, se deberá presentar

el sistema adicional de bombeo que impulsarán las aguas residuales de la colonia al

colector, incluyendo en la memoria de diseño los cálculos respectivos para la selección

del equipo de bombeo y dimensionamiento de la cámara de aspiración. Estos datos

deberán ser presentados al Departamento de Ingeniería Municipal para la compra del

equipo de bombeo.

4.4. Pruebas de los Sistemas: Todas las tuberías deberán ser probadas contra fugas y antes

del relleno de las zanjas, dejando las juntas y accesorios libres y descubiertos para su

revisión.

Procedimiento de Prueba: En el tramo seleccionado se colocará un tapón de ladrillo

ligado en la entrada del pozo inferior. Se tapará también las entradas y salidas del pozo

superior, excepto la salida hacia el tramo en prueba. Se llena el tramo y el pozo

superior, hasta alcanzar una carga mínima de 0.80 metros sobre la corona de salida del

pozo superior, dejando lleno durante 20 minutos para saturar la tubería y el pozo; se

llena al mismo nivel anterior y se observa durante 12 horas, tomando la primera lectura

a los 30 minutos, luego a cada hora, midiendo el volumen perdido. La fuga por cada 30

metros de tubería no debe exceder 1.30 galones por hora por pulgada de diámetro.

4.5. Deposición Final de las Excretas: El flujo recolectado por el sistema será vertido en la

red municipal en la intercepción de las calles del cementerio y COHDEFOR, dicha red

traslada los flujos para su tratamiento en un sistema de lagunas de oxidación.

Page 13: ALCANTARILLADO SANITARIO - · PDF filealcantarillado sanitario memoria tÉcnica colonias “ santa marÍa, 25 de febrero, sitramedhys y santa eduviges ” Índice 1. generalidades

COLONIAS: SANTA MARÍA, 25 DE FEBRERO, SITRAMEDHYS Y SANTA EDUVIGES

Preparado por: Ing. Rodrigo G. Cárcamo M. CICH 3062

CONSULTORIA Y DISEÑO CÁRCAMO MURILLO CODICAM

5. MEMORIA DE CALCULO Y PLANOS

5.1. Memoria de Cálculo: Deberá presentarse una memoria de cálculo así como también un

resumen de las especificaciones. En esta aparecerá el cuadro por tramos numerados con

velocidades y caudales reales y las capacidades del sistema.

5.2. Planos:

a. Deberá presentarse una planta general mostrando las redes de alcantarillado

sanitario, en la cual se representará:

• Numeración de calles y avenidas

• Detallar los lotes en los bloques

• Numeración y ubicación de los pozos de inspección

• El colector principal de aguas negras hasta su punto de descarga

b. Presentar en las hojas de planta y perfil lo siguiente:

• La rasante de las calles.

• La rasante de tuberías de aguas negras.

Page 14: ALCANTARILLADO SANITARIO - · PDF filealcantarillado sanitario memoria tÉcnica colonias “ santa marÍa, 25 de febrero, sitramedhys y santa eduviges ” Índice 1. generalidades

COLONIAS: SANTA MARÍA, 25 DE FEBRERO, SITRAMEDHYS Y SANTA EDUVIGES

Preparado por: Ing. Rodrigo G. Cárcamo M. CICH 3062

CONSULTORIA Y DISEÑO CÁRCAMO MURILLO CODICAM

CÁLCULOS DE MEMORIA DESCRIPTIVA

Page 15: ALCANTARILLADO SANITARIO - · PDF filealcantarillado sanitario memoria tÉcnica colonias “ santa marÍa, 25 de febrero, sitramedhys y santa eduviges ” Índice 1. generalidades

Diseño Hidráulico

Material a usar:PVC 0.011 Tipos de Diámetros: Coeficiente de Manning según Tipo de Tubería: 4 101.6 341 58 -PVC 0.011 - 0.015 6 152.4 2,053 351 248Concreto ( C ) 0.012 - 0.015 8 203.2 767 131 89Dotación: 40.00 GPPD 151.4 LPPD 10 254.0 855 146 4Área tributaria 294.00 m² 12 304.8 0 0 0Ancho de lote 12.00 m 15 381.0 0 0 0Fondo de lote 20.00 m 18 457.2 0 0 0Ancho de calle 9.00 m

Tramo De A Longitud Diam Lotes Total Poblac Área QInfit. Caudal Veloc. Caudal Tirante Qr/Qll Vr/Vll Veloc.No. Pozo Pozo en en Locales Lotes Total Local & Q ilicit Real Lleno lleno d' en en Real

(m) (mm) (hab.) (Ha) L/s L/s m/s L/s (mm) % % m/sSub colector 1 1 2 58.67 152.4 6 6 38 0.23 0.09 0.85 1.11 20.21 21.46 4.20 49.70 0.55

2 3 30.20 152.4 3 9 57 0.12 0.05 1.09 1.06 19.27 24.82 5.64 54.35 0.573 4 41.75 152.4 2 11 69 0.10 0.04 1.26 1.69 30.74 21.17 4.08 49.28 0.83

Sub colector 2 3 6 40.60 152.4 6 6 38 0.21 0.09 0.84 1.38 25.21 19.18 3.34 46.35 0.646 8 48.25 152.4 5 19 120 0.19 0.08 1.94 1.62 29.61 26.69 6.54 56.79 0.92

Sub colector 3 7 8 20.00 152.4 5 5 32 0.17 0.07 0.72 0.73 13.28 24.42 5.46 53.81 0.398 9 24.00 152.4 2 26 164 0.08 0.04 2.41 0.73 13.28 44.11 18.14 76.09 0.559 10 33.90 152.4 3 29 183 0.12 0.05 2.63 0.83 15.13 43.23 17.41 75.25 0.62

Sub colector 4 9 11 62.28 152.4 8 8 50 0.29 0.12 1.06 1.04 19.03 24.67 5.57 54.15 0.5711 12 20.00 152.4 3 11 69 0.11 0.05 1.26 3.30 60.26 15.22 2.09 40.08 1.3212 13 45.79 152.4 4 15 95 0.16 0.07 1.61 1.12 20.39 29.30 7.90 60.07 0.67

Sub colector 5 4 14 80.27 152.4 12 23 145 0.43 0.16 2.32 1.14 20.78 34.72 11.15 66.40 0.7614 10 14.30 152.4 1 24 151 0.04 0.02 2.25 1.12 20.47 34.46 10.98 66.11 0.7410 15 66.03 152.4 6 59 372 0.24 0.10 4.59 1.13 20.67 48.73 22.21 80.35 0.9115 16 45.86 152.4 5 70 441 0.19 0.08 5.21 1.14 20.75 51.79 25.13 83.00 0.9416 17 68.46 152.4 7 77 485 0.27 0.11 5.64 2.53 46.23 36.28 12.20 68.12 1.73

Sub colector 6 18 19 100.00 152.4 9 16 101 0.35 0.14 1.76 1.66 30.22 25.22 5.83 54.88 0.9119 20 102.61 152.4 15 31 195 0.53 0.20 2.92 0.81 14.71 46.11 19.84 77.97 0.6320 21 50.83 152.4 5 36 227 0.19 0.08 3.14 2.37 43.28 28.08 7.25 58.56 1.39

Sub colector 7 22 23 41.40 152.4 5 5 32 0.18 0.08 0.73 0.77 14.00 23.91 5.23 53.12 0.4123 21 58.28 152.4 4 9 57 0.17 0.07 1.11 0.79 14.34 28.97 7.72 59.67 0.4721 24 19.09 152.4 2 47 296 0.08 0.03 3.80 1.62 29.46 37.28 12.89 69.20 1.1224 31 30.57 152.4 2 49 309 0.09 0.04 3.93 1.72 31.31 36.78 12.54 68.66 1.18

Sub colector 8 13 27 73.71 203.2 11 26 164 0.39 0.15 2.52 1.63 52.87 30.47 4.77 51.66 0.8427 28 7.48 203.2 0 34 214 0.01 0.00 2.93 1.02 33.06 41.32 8.86 62.11 0.6328 17 25.19 203.2 2 53 334 0.08 0.04 4.17 1.02 33.22 49.07 12.55 68.68 0.7017 29 81.16 203.2 10 140 882 0.37 0.14 8.96 1.04 33.59 71.12 26.67 84.30 0.8729 30 28.23 203.2 5 145 914 0.17 0.07 9.13 2.29 74.18 48.60 12.31 68.31 1.5630 31 8.26 203.2 0 154 970 0.01 0.00 9.50 2.30 74.45 49.47 12.76 69.01 1.5831 32 39.80 203.2 3 206 1,298 0.12 0.05 11.97 1.52 49.23 67.95 24.32 82.30 1.2532 33 48.00 203.2 1 214 1,348 0.07 0.03 12.31 1.00 32.50 88.19 37.88 93.84 0.9433 34 53.90 203.2 5 228 1,436 0.20 0.08 12.98 0.99 32.12 91.43 40.42 95.43 0.95

Colonias "Santa María, 25 de Febrero, Sitramedhys y Santa EduvigesALCANTARILLADO SANITARIO

Mayo de 2005

Cant yees

Pulgadas mm Longitud Cant Tubos

Preparado por: Ing. Rodrigo G. Cárcamo M.

Page 16: ALCANTARILLADO SANITARIO - · PDF filealcantarillado sanitario memoria tÉcnica colonias “ santa marÍa, 25 de febrero, sitramedhys y santa eduviges ” Índice 1. generalidades

Diseño Hidráulico

Material a usar:PVC 0.011 Tipos de Diámetros: Coeficiente de Manning según Tipo de Tubería: 4 101.6 341 58 -PVC 0.011 - 0.015 6 152.4 2,053 351 248Concreto ( C ) 0.012 - 0.015 8 203.2 767 131 89Dotación: 40.00 GPPD 151.4 LPPD 10 254.0 855 146 4Área tributaria 294.00 m² 12 304.8 0 0 0Ancho de lote 12.00 m 15 381.0 0 0 0Fondo de lote 20.00 m 18 457.2 0 0 0Ancho de calle 9.00 m

Tramo De A Longitud Diam Lotes Total Poblac Área QInfit. Caudal Veloc. Caudal Tirante Qr/Qll Vr/Vll Veloc.No. Pozo Pozo en en Locales Lotes Total Local & Q ilicit Real Lleno lleno d' en en Real

(m) (mm) (hab.) (Ha) L/s L/s m/s L/s (mm) % % m/s

Colonias "Santa María, 25 de Febrero, Sitramedhys y Santa EduvigesALCANTARILLADO SANITARIO

Mayo de 2005

Cant yees

Pulgadas mm Longitud Cant Tubos

Sub colector 9 24 38 70.00 152.4 8 8 50 0.30 0.12 1.06 1.24 22.55 22.72 4.72 51.49 0.6438 39 16.93 152.4 2 10 63 0.07 0.03 1.16 0.87 15.81 28.24 7.33 58.76 0.5139 40 10.00 152.4 0 15 95 0.01 0.01 1.55 0.86 15.71 32.68 9.86 64.09 0.5540 41 60.00 152.4 9 24 151 0.32 0.13 2.35 0.85 15.52 40.38 15.16 72.43 0.6241 42 47.18 152.4 0 57 359 0.04 0.02 4.40 0.85 15.46 55.03 28.42 85.68 0.73

Sub colector 10 34 45 106.39 203.2 17 245 1,544 0.60 0.22 13.86 1.44 46.55 75.08 29.78 86.69 1.2445 46 23.74 203.2 2 70 441 0.08 0.04 5.17 1.09 35.21 53.01 14.69 71.79 0.7846 47 58.95 203.2 5 44 277 0.20 0.08 3.66 1.08 34.94 44.87 10.47 65.20 0.70

Sub colector 11 42 48 76.29 203.2 15 102 643 0.51 0.19 7.08 1.32 42.93 56.12 16.49 74.13 0.9848 49 87.50 203.2 13 115 725 0.46 0.17 7.74 2.07 67.11 47.05 11.53 67.04 1.3949 50 87.00 152.4 17 20 126 0.58 0.21 2.15 0.73 13.35 41.56 16.08 73.61 0.54

Sub colector 12 45 49 48.14 203.2 0 315 1,985 0.04 0.02 16.62 1.30 42.03 90.31 39.54 94.89 1.2349 51 52.20 254.0 0 450 2,835 0.05 0.02 21.95 1.02 51.74 117.47 42.41 96.64 0.99

Sub colector 13 53 52 62.74 152.4 4 24 151 0.17 0.07 2.30 1.87 34.19 27.07 6.73 57.29 1.0752 51 30.00 254.0 4 454 2,860 0.14 0.06 22.14 1.02 51.84 117.93 42.70 96.81 0.99

Ramal 1 5 6 27.85 152.4 8 8 50 0.26 0.10 1.05 1.26 23.06 22.33 4.55 50.94 0.64Ramal 2 14 18 66.05 152.4 7 7 44 0.27 0.11 0.96 0.73 13.27 28.03 7.22 58.49 0.43Ramal 3 25 27 45.90 152.4 8 8 50 0.28 0.11 1.06 1.96 35.82 18.03 2.95 44.60 0.88Ramal 4 26 26a 60.00 152.4 9 9 57 0.32 0.13 1.16 2.60 47.50 16.45 2.45 42.09 1.10

26a 28 48.50 152.4 8 17 107 0.28 0.11 1.81 1.49 27.10 27.00 6.69 57.19 0.85Ramal 5 35 30 36.49 152.4 9 9 57 0.30 0.12 1.15 0.83 15.23 28.71 7.58 59.34 0.50Ramal 6 36 32 51.85 152.4 7 7 44 0.25 0.10 0.95 0.80 14.52 26.75 6.57 56.87 0.45Ramal 7 37 33 43.45 152.4 9 9 57 0.30 0.12 1.16 0.88 16.11 27.94 7.18 58.39 0.52Ramal 8 43 40 40.00 152.4 5 5 32 0.18 0.08 0.73 1.96 35.75 15.06 2.05 39.82 0.78Ramal 9 44 41 69.70 152.4 9 33 208 0.33 0.13 2.98 1.80 32.82 31.40 9.09 62.59 1.13Ramal 10 47 50 50.68 152.4 3 3 19 0.13 0.06 0.50 1.21 22.07 15.80 2.25 41.04 0.50Ramal 11 11 15 55.46 152.4 6 6 38 0.23 0.09 0.85 0.85 15.54 24.41 5.45 53.80 0.46

Preparado por: Ing. Rodrigo G. Cárcamo M.

Page 17: ALCANTARILLADO SANITARIO - · PDF filealcantarillado sanitario memoria tÉcnica colonias “ santa marÍa, 25 de febrero, sitramedhys y santa eduviges ” Índice 1. generalidades

Diseño Hidráulico

Material a usar:PVC 0.011 Tipos de Diámetros: Coeficiente de Manning según Tipo de Tubería: 4 101.6 341 58 -PVC 0.011 - 0.015 6 152.4 2,053 351 248Concreto ( C ) 0.012 - 0.015 8 203.2 767 131 89Dotación: 40.00 GPPD 151.4 LPPD 10 254.0 855 146 4Área tributaria 294.00 m² 12 304.8 0 0 0Ancho de lote 12.00 m 15 381.0 0 0 0Fondo de lote 20.00 m 18 457.2 0 0 0Ancho de calle 9.00 m

Tramo De A Longitud Diam Lotes Total Poblac Área QInfit. Caudal Veloc. Caudal Tirante Qr/Qll Vr/Vll Veloc.No. Pozo Pozo en en Locales Lotes Total Local & Q ilicit Real Lleno lleno d' en en Real

(m) (mm) (hab.) (Ha) L/s L/s m/s L/s (mm) % % m/s

Colonias "Santa María, 25 de Febrero, Sitramedhys y Santa EduvigesALCANTARILLADO SANITARIO

Mayo de 2005

Cant yees

Pulgadas mm Longitud Cant Tubos

Colector principal 52 54 80.00 254.0 0 478 3,011 0.07 0.03 23.01 1.18 59.68 111.32 38.56 94.27 1.1154 55 38.00 254.0 0 478 3,011 0.03 0.02 23.00 1.15 58.27 112.77 39.47 94.84 1.0955 56 65.00 254.0 0 478 3,011 0.06 0.03 23.01 1.02 51.44 121.16 44.72 97.98 0.9956 57 63.68 254.0 0 478 3,011 0.06 0.03 23.01 1.03 51.97 120.43 44.27 97.72 1.0057 58 32.30 254.0 0 478 3,011 0.03 0.01 22.99 1.02 51.60 120.90 44.56 97.89 1.0058 59 70.53 254.0 0 478 3,011 0.06 0.03 23.01 1.03 52.38 119.89 43.93 97.52 1.0159 60 57.18 254.0 0 478 3,011 0.05 0.02 23.00 1.01 51.31 121.34 44.84 98.05 0.9960 61 65.70 254.0 0 478 3,011 0.06 0.03 23.01 1.01 51.17 121.55 44.96 98.12 0.9961 62 66.63 254.0 0 478 3,011 0.06 0.03 23.01 1.66 84.26 89.93 27.31 84.80 1.4162 63 40.00 254.0 0 478 3,011 0.04 0.02 23.00 2.73 138.14 70.48 16.65 74.33 2.0363 64 34.90 254.0 0 478 3,011 0.03 0.02 23.00 1.55 78.49 93.10 29.30 86.33 1.3464 65 76.57 254.0 0 478 3,011 0.07 0.03 23.01 1.49 75.41 94.98 30.51 87.22 1.3065 66 82.25 254.0 0 478 3,011 0.07 0.03 23.01 1.51 76.27 94.46 30.17 86.98 1.31

Nota: Pozo 66 existente, hacia colector municipal

Longitud Total 3,674.60

Notas: - Rellenar las casillas en rojo Obs.: La Velocidad Real (Vr) estará en el rango- Si Qr/Qll > 100.0 aumente el diámetro 0.45 m/s < Vr < 5.0 m/s- Si d' > Diam, aumente el diámetro- Si Vr/Vll > 100.0 considere aumentar el diámetro Las longitudes entre tramos no serán mayores (no obligatorio) 100.0 m en cabeceras y diámetros menores que 15"

120.0 m en diámetros mayores o iguales que 15"

Preparado por: Ing. Rodrigo G. Cárcamo M.

Page 18: ALCANTARILLADO SANITARIO - · PDF filealcantarillado sanitario memoria tÉcnica colonias “ santa marÍa, 25 de febrero, sitramedhys y santa eduviges ” Índice 1. generalidades

Diseño Hidráulico

Material a usar:PVC 0.011Coeficiente de Manning según Tipo de Tubería:PVC 0.011 - 0.015Concreto ( C ) 0.012 - 0.015Dotación: 40.00 GPPD 151.4 LPPDÁrea tributaria 294.00 m²Ancho de lote 12.00 m Fondo de lote 20.00 mancho de calle 9.00 m

Tramo De A Longitud Pendiente Rasante Rasante Invertida Invertida Profundidad Profundidad Ancho VolumenNo. Pozo Pozo en Salida Llegada Salida Llegada Pozo Salida Pozo Llegada Zanjo Excavación

(m) m/m (m) (m) (m) (m) (m) (m) (m) (m³)Sub colector 1 1 2 58.67 0.012 500.00 499.32 498.80 498.12 1.20 1.20 0.80 56.32

2 3 30.20 0.011 499.32 499.00 498.12 497.80 1.20 1.20 0.80 28.993 4 41.75 0.027 499.00 497.88 497.80 496.68 1.20 1.20 0.80 40.08

Sub colector 2 3 6 40.60 0.018 499.00 499.27 497.80 497.07 1.20 2.20 0.80 55.226 8 48.25 0.025 499.27 498.17 497.07 495.87 2.20 2.30 0.80 86.85

Sub colector 3 7 8 20.00 0.005 497.17 498.17 495.97 495.87 1.20 2.30 0.80 28.008 9 24.00 0.005 498.17 497.66 495.87 495.75 2.30 1.91 0.80 40.429 10 33.90 0.006 497.66 497.03 495.75 495.53 1.91 1.50 0.80 46.24

Sub colector 4 9 11 62.28 0.010 497.66 496.31 495.75 495.11 1.91 1.20 0.80 77.4811 12 20.00 0.103 496.31 492.45 493.31 491.25 3.00 1.20 0.80 33.6012 13 45.79 0.012 492.45 491.40 490.74 490.20 1.71 1.20 0.80 53.30

Sub colector 5 4 14 80.27 0.012 497.88 497.27 496.68 495.70 1.20 1.57 0.80 88.9414 10 14.30 0.012 497.27 497.03 495.70 495.53 1.57 1.50 0.80 17.5610 15 66.03 0.012 497.03 496.49 495.53 494.73 1.50 1.76 0.80 86.1015 16 45.86 0.012 496.49 495.37 494.73 494.17 1.76 1.20 0.80 54.3016 17 68.46 0.061 495.37 490.28 492.87 488.72 2.50 1.56 0.80 111.18

Sub colector 6 18 19 100.00 0.026 496.92 493.98 495.37 492.78 1.55 1.20 0.80 110.0019 20 102.61 0.006 493.98 493.35 492.78 492.15 1.20 1.20 0.80 98.5120 21 50.83 0.053 493.35 490.65 492.15 489.45 1.20 1.20 0.80 48.80

Sub colector 7 22 23 41.40 0.006 491.20 491.58 490.00 489.77 1.20 1.81 0.80 49.8523 21 58.28 0.006 491.58 490.63 489.77 489.43 1.81 1.20 0.80 70.1721 24 19.09 0.025 490.63 490.16 489.43 488.96 1.20 1.20 0.80 18.3324 31 30.57 0.028 490.16 489.31 488.96 488.11 1.20 1.20 0.80 29.35

Sub colector 8 13 27 73.71 0.017 491.40 490.14 490.20 488.94 1.20 1.20 0.80 70.7627 28 7.48 0.007 490.14 490.21 488.94 488.89 1.20 1.32 0.80 7.5428 17 25.19 0.007 490.21 490.28 488.89 488.72 1.32 1.56 0.80 29.0217 29 81.16 0.007 490.28 489.36 488.72 488.16 1.56 1.20 0.80 89.6029 30 28.23 0.034 489.36 489.40 488.16 487.21 1.20 2.19 0.80 38.2830 31 8.26 0.034 489.40 489.31 487.21 486.93 2.19 2.38 0.80 15.1031 32 39.80 0.015 489.31 488.57 486.93 486.34 2.38 2.23 0.80 73.3932 33 48.00 0.006 488.57 488.26 486.34 486.03 2.23 2.23 0.80 85.6333 34 53.90 0.006 488.26 488.09 486.03 485.69 2.23 2.40 0.80 99.82

ALCANTARILLADO SANITARIO

Junio de 2008

Colonias "Santa María, 25 de Febrero, Sitramedhys y Santa Eduviges

Y

r = D/2

Ya°

D

d'

SECCIÓN MOJADA

d'

DY

r = D/2

SECCIÓN MOJADA

a° r

r

X

X

Y

CONDICIONES DE FLUJO

Preparado por: Ing. Rodrigo G. Cárcamo M.

Page 19: ALCANTARILLADO SANITARIO - · PDF filealcantarillado sanitario memoria tÉcnica colonias “ santa marÍa, 25 de febrero, sitramedhys y santa eduviges ” Índice 1. generalidades

Diseño Hidráulico

Material a usar:PVC 0.011Coeficiente de Manning según Tipo de Tubería:PVC 0.011 - 0.015Concreto ( C ) 0.012 - 0.015Dotación: 40.00 GPPD 151.4 LPPDÁrea tributaria 294.00 m²Ancho de lote 12.00 m Fondo de lote 20.00 mancho de calle 9.00 m

Tramo De A Longitud Pendiente Rasante Rasante Invertida Invertida Profundidad Profundidad Ancho VolumenNo. Pozo Pozo en Salida Llegada Salida Llegada Pozo Salida Pozo Llegada Zanjo Excavación

(m) m/m (m) (m) (m) (m) (m) (m) (m) (m³)

ALCANTARILLADO SANITARIO

Junio de 2008

Colonias "Santa María, 25 de Febrero, Sitramedhys y Santa Eduviges

Y

r = D/2

Ya°

D

d'

SECCIÓN MOJADA

d'

DY

r = D/2

SECCIÓN MOJADA

a° r

r

X

X

Y

CONDICIONES DE FLUJO

Sub colector 9 24 38 70.00 0.014 490.16 489.15 488.96 487.95 1.20 1.20 0.80 67.2038 39 16.93 0.007 489.15 489.68 487.95 487.83 1.20 1.85 0.80 20.6539 40 10.00 0.007 489.68 489.06 487.83 487.76 1.85 1.30 0.80 12.6040 41 60.00 0.007 489.06 489.15 487.76 487.35 1.30 1.80 0.80 74.4041 42 47.18 0.007 489.15 489.03 487.35 487.03 1.80 2.00 0.80 71.71

Sub colector 10 34 45 106.39 0.013 488.09 485.88 485.69 484.28 2.40 1.60 0.80 170.2245 46 23.74 (0.008) 485.88 485.66 484.28 484.46 1.60 1.20 0.80 26.5946 47 58.95 (0.007) 485.66 486.10 484.46 484.90 1.20 1.20 0.80 56.59

Sub colector 11 42 48 76.29 0.011 489.03 487.37 487.03 486.17 2.00 1.20 0.80 97.6548 49 87.50 0.028 487.37 485.76 486.17 483.76 1.20 2.00 0.80 112.0049 50 87.00 (0.005) 485.76 485.20 483.76 484.20 2.00 1.00 0.80 104.40

Sub colector 12 45 49 48.14 0.011 485.88 485.76 484.28 483.76 1.60 2.00 0.80 69.3249 51 52.20 0.005 485.76 485.05 483.76 483.50 2.00 1.55 1.00 92.66

Sub colector 13 53 52 62.74 0.033 486.63 485.45 485.43 483.35 1.20 2.10 0.80 82.8252 51 30.00 (0.005) 485.45 485.05 483.35 483.50 2.10 1.55 1.00 54.75

Ramal 1 5 6 27.85 0.015 498.69 499.27 497.49 497.07 1.20 2.20 0.80 37.88Ramal 2 14 18 66.05 0.005 497.27 496.92 495.70 495.37 1.57 1.55 0.80 82.43Ramal 3 25 27 45.90 0.036 491.81 490.14 490.61 488.94 1.20 1.20 0.80 44.06Ramal 4 26 26a 60.00 0.064 494.94 491.10 493.74 489.90 1.20 1.20 0.80 57.60

26a 28 48.50 0.021 491.10 490.21 489.90 488.89 1.20 1.32 0.80 48.89Ramal 5 35 30 36.49 0.007 488.65 489.40 487.45 487.21 1.20 2.19 0.80 49.48Ramal 6 36 32 51.85 0.006 487.65 488.57 486.65 486.34 1.00 2.23 0.80 66.99Ramal 7 37 33 43.45 0.007 487.45 488.26 486.35 486.03 1.10 2.23 0.80 57.88Ramal 8 43 40 40.00 0.036 490.48 489.68 489.28 487.83 1.20 1.85 0.80 48.80Ramal 9 44 41 69.70 0.031 490.68 489.15 489.48 487.35 1.20 1.80 0.80 83.64Ramal 10 47 50 50.68 0.014 486.10 485.20 484.90 484.20 1.20 1.00 0.80 44.60Ramal 11 11 15 55.46 0.007 496.31 496.49 495.11 494.73 1.20 1.76 0.80 65.66

Preparado por: Ing. Rodrigo G. Cárcamo M.

Page 20: ALCANTARILLADO SANITARIO - · PDF filealcantarillado sanitario memoria tÉcnica colonias “ santa marÍa, 25 de febrero, sitramedhys y santa eduviges ” Índice 1. generalidades

Diseño Hidráulico

Material a usar:PVC 0.011Coeficiente de Manning según Tipo de Tubería:PVC 0.011 - 0.015Concreto ( C ) 0.012 - 0.015Dotación: 40.00 GPPD 151.4 LPPDÁrea tributaria 294.00 m²Ancho de lote 12.00 m Fondo de lote 20.00 mancho de calle 9.00 m

Tramo De A Longitud Pendiente Rasante Rasante Invertida Invertida Profundidad Profundidad Ancho VolumenNo. Pozo Pozo en Salida Llegada Salida Llegada Pozo Salida Pozo Llegada Zanjo Excavación

(m) m/m (m) (m) (m) (m) (m) (m) (m) (m³)

ALCANTARILLADO SANITARIO

Junio de 2008

Colonias "Santa María, 25 de Febrero, Sitramedhys y Santa Eduviges

Y

r = D/2

Ya°

D

d'

SECCIÓN MOJADA

d'

DY

r = D/2

SECCIÓN MOJADA

a° r

r

X

X

Y

CONDICIONES DE FLUJO

Colector principal 52 54 80.00 0.007 485.45 484.23 483.35 482.82 2.10 1.41 1.00 140.4054 55 38.00 0.006 484.23 483.68 482.82 482.58 1.41 1.10 1.00 47.6955 56 65.00 0.005 483.68 483.42 482.58 482.26 1.10 1.16 1.00 73.4556 57 63.68 0.005 483.42 483.92 482.26 481.94 1.16 1.98 1.00 99.9857 58 32.30 0.005 483.92 484.74 481.94 481.78 1.98 2.96 1.00 79.7858 59 70.53 0.005 484.74 485.75 481.78 481.42 2.96 4.33 1.00 257.0859 60 57.18 0.005 485.75 484.67 481.42 481.14 4.33 3.53 1.00 224.7260 61 65.70 0.005 484.67 483.09 481.14 480.82 3.53 2.27 1.00 190.5361 62 66.63 0.013 483.09 481.14 480.82 479.94 2.27 1.20 1.00 115.6062 63 40.00 0.035 481.14 479.72 479.94 478.52 1.20 1.20 1.00 48.0063 64 34.90 0.011 479.72 479.32 478.52 478.12 1.20 1.20 1.00 41.8864 65 76.57 0.011 479.32 478.93 478.12 477.31 1.20 1.62 1.00 107.9665 66 82.25 0.011 478.93 477.62 477.31 476.42 1.62 1.20 1.00 115.97

Total Excavación (m³): 3,339.61

Obs.: La Pendiente del tubo no será menor que 0.5 % (0.005 m/m).

Preparado por: Ing. Rodrigo G. Cárcamo M.

Page 21: ALCANTARILLADO SANITARIO - · PDF filealcantarillado sanitario memoria tÉcnica colonias “ santa marÍa, 25 de febrero, sitramedhys y santa eduviges ” Índice 1. generalidades

COLONIAS: SANTA MARÍA, 25 DE FEBRERO, SITRAMEDHYS Y SANTA EDUVIGES

Preparado por: Ing. Rodrigo G. Cárcamo M. CICH 3062

CONSULTORIA Y DISEÑO CÁRCAMO MURILLO CODICAM

PLANOS

Page 22: ALCANTARILLADO SANITARIO - · PDF filealcantarillado sanitario memoria tÉcnica colonias “ santa marÍa, 25 de febrero, sitramedhys y santa eduviges ” Índice 1. generalidades
Page 23: ALCANTARILLADO SANITARIO - · PDF filealcantarillado sanitario memoria tÉcnica colonias “ santa marÍa, 25 de febrero, sitramedhys y santa eduviges ” Índice 1. generalidades
Page 24: ALCANTARILLADO SANITARIO - · PDF filealcantarillado sanitario memoria tÉcnica colonias “ santa marÍa, 25 de febrero, sitramedhys y santa eduviges ” Índice 1. generalidades
Page 25: ALCANTARILLADO SANITARIO - · PDF filealcantarillado sanitario memoria tÉcnica colonias “ santa marÍa, 25 de febrero, sitramedhys y santa eduviges ” Índice 1. generalidades
Page 26: ALCANTARILLADO SANITARIO - · PDF filealcantarillado sanitario memoria tÉcnica colonias “ santa marÍa, 25 de febrero, sitramedhys y santa eduviges ” Índice 1. generalidades
Page 27: ALCANTARILLADO SANITARIO - · PDF filealcantarillado sanitario memoria tÉcnica colonias “ santa marÍa, 25 de febrero, sitramedhys y santa eduviges ” Índice 1. generalidades
Page 28: ALCANTARILLADO SANITARIO - · PDF filealcantarillado sanitario memoria tÉcnica colonias “ santa marÍa, 25 de febrero, sitramedhys y santa eduviges ” Índice 1. generalidades
Page 29: ALCANTARILLADO SANITARIO - · PDF filealcantarillado sanitario memoria tÉcnica colonias “ santa marÍa, 25 de febrero, sitramedhys y santa eduviges ” Índice 1. generalidades
Page 30: ALCANTARILLADO SANITARIO - · PDF filealcantarillado sanitario memoria tÉcnica colonias “ santa marÍa, 25 de febrero, sitramedhys y santa eduviges ” Índice 1. generalidades
Page 31: ALCANTARILLADO SANITARIO - · PDF filealcantarillado sanitario memoria tÉcnica colonias “ santa marÍa, 25 de febrero, sitramedhys y santa eduviges ” Índice 1. generalidades
Page 32: ALCANTARILLADO SANITARIO - · PDF filealcantarillado sanitario memoria tÉcnica colonias “ santa marÍa, 25 de febrero, sitramedhys y santa eduviges ” Índice 1. generalidades
Page 33: ALCANTARILLADO SANITARIO - · PDF filealcantarillado sanitario memoria tÉcnica colonias “ santa marÍa, 25 de febrero, sitramedhys y santa eduviges ” Índice 1. generalidades
Page 34: ALCANTARILLADO SANITARIO - · PDF filealcantarillado sanitario memoria tÉcnica colonias “ santa marÍa, 25 de febrero, sitramedhys y santa eduviges ” Índice 1. generalidades
Page 35: ALCANTARILLADO SANITARIO - · PDF filealcantarillado sanitario memoria tÉcnica colonias “ santa marÍa, 25 de febrero, sitramedhys y santa eduviges ” Índice 1. generalidades
Page 36: ALCANTARILLADO SANITARIO - · PDF filealcantarillado sanitario memoria tÉcnica colonias “ santa marÍa, 25 de febrero, sitramedhys y santa eduviges ” Índice 1. generalidades
Page 37: ALCANTARILLADO SANITARIO - · PDF filealcantarillado sanitario memoria tÉcnica colonias “ santa marÍa, 25 de febrero, sitramedhys y santa eduviges ” Índice 1. generalidades

COLONIAS: SANTA MARÍA, 25 DE FEBRERO, SITRAMEDHYS Y SANTA EDUVIGES

Preparado por: Ing. Rodrigo G. Cárcamo M. CICH 3062

CONSULTORIA Y DISEÑO CÁRCAMO MURILLO CODICAM

PRESUPUESTO

Page 38: ALCANTARILLADO SANITARIO - · PDF filealcantarillado sanitario memoria tÉcnica colonias “ santa marÍa, 25 de febrero, sitramedhys y santa eduviges ” Índice 1. generalidades

SISTEMA DE ALCANTARILLADO SANITARIOCOLONIAS: STA. MARÍA, 25 DE FEBRERO, SITRAMEDHYS Y STA. EDUVIGES

PresupuestoDescripción Unidad Cantidad Precio U. TotalSistema de alcantarillado sanitario Colonias Sta. María,25 de Febrero, Sitramedhys y Sta. Eduviges.

Sistema de Alcantarillado Sanitario

Urbanización

Levantamineto topográfico ml 3,687.85 13.12 48,384.59

Excavación de zanjería m³ 3,339.59 29.20 97,516.03

Suministro e instalación tubería Ø=6" PVC RD-50 ml 2,053.00 128.44 263,687.32

Suministro e instalación tubería Ø=8" PVC RD-50 ml 767.00 219.26 168,172.42

Suministro e instalación tubería Ø=10" PVC RD-50 ml 855.00 354.56 303,148.80

Excavación para pozos (global) m³ 637.15 28.40 18,095.06

Pozo de inspección 1.00 a 1.19 m prof unidad 5.00 6,856.10 34,280.50

Pozo de inspección 1.20 a 1.39 m prof unidad 32.00 7,305.55 233,777.60

Pozo de inspección 1.40 a 1.59 m prof unidad 5.00 7,757.73 38,788.65

Pozo de inspección 1.60 a 1.79 m prof unidad 4.00 8,210.13 32,840.52

Pozo de inspección 1.80 a 1.99 m prof unidad 4.00 8,662.40 34,649.60

Pozo de inspección 2.00 a 2.19 m prof unidad 4.00 9,114.66 36,458.64

Pozo de inspección 2.20 a 2.39 m prof unidad 6.00 9,567.06 57,402.36

Pozo de inspección 2.40 a 2.59 m prof unidad 2.00 10,019.28 20,038.56

Pozo de inspección 2.80 a 2.99 m prof unidad 1.00 10,923.50 10,923.50

Pozo de inspección 3.00 a 3.19 m prof unidad 1.00 11,377.81 11,377.81

Pozo de inspección 3.40 a 3.59 m prof unidad 1.00 12,280.27 12,280.27

Pozo de inspección 4.20 a 4.39 m prof unidad 1.00 14,090.82 14,090.82

Relleno material selecto m³ 1,180.11 275.94 325,639.55

Relleno material del sitio m³ 2,159.48 114.09 246,375.07

Prueba hidrostática global 1.00 10,150.00 10,150.00

2'018,077.67Total de Urbanización** DOS MILLONES DIECIOCHO MIL SETENTA Y SIETE LEMPIRAS 67/100 M.N. **

Conexiones domiciliarias

Excavación para cajas de registro AN m³ 174.60 127.20 22,209.12

Caja de registro unidad 341.00 714.34 243,589.94

Acometida tubería Ø=4" PVC RD-50 unidad 341.00 235.08 80,162.28

Suministro e instalación de yees de 6" x 4" unidad 248.00 164.55 40,808.40

Suministro e instalación de yees de 8" x 4" unidad 89.00 222.43 19,796.27

Suministro e instalación de yees de 10" x 4" unidad 4.00 300.30 1,201.20

Relleno material selecto m³ 43.65 275.94 12,044.78

Relleno material del sitio m³ 130.95 114.09 14,940.09

434,752.08Total de Conexiones domiciliarias** CUATROCIENTOS TREINTA Y CUATRO MIL SETECIENTOS CINCUENTA Y DOS LEMPIRAS 08/100 M.N. **

2'452,829.75Total de Sistema de Alcantarillado Sanitario** DOS MILLONES CUATROCIENTOS CINCUENTA Y DOS MIL OCHOCIENTOS VEINTINUEVE LEMPIRAS 75/100 M.N. **

2'452,829.75Total de Sistema de alcantarillado sanitario Colonias Sta. María, 25 de Febrero, Sitramedhys y Sta. Eduviges.

** DOS MILLONES CUATROCIENTOS CINCUENTA Y DOS MIL OCHOCIENTOS VEINTINUEVE LEMPIRAS 75/100 M.N. **

Preparado por: Ing. Rodrigo G. Cárcamo M. CICH 3062