    ComnCommon

    UTILIZACIN

    Se utilizan para el control y regulacin del nivel de lqui-dos conductores detectando el mximo y mnimo tantoen el llenado como en el vaciado de pozos o depsitos.Permiten controlar el trasvase de lquido entre pozos ydepsitos utilizando el modelo adecuado. No son ade-cuados para lquidos inflamables o para trabajar en zonas

    clasificadas como potencialmente explosivas.

    APPLICATION

    They are employed in the control and regulation of liquidconductor levels, detecting maximum and minimum bothin the filling or draining wells and tanks. They permit thecontrol of liquid transfer between wells and tanks usingthe most adequate model. They are not suitable forinflammable liquids or for working in areas that are clas-

    sified as potentially explosive.

    HOJA TCNICA 5317H000 Edicin 01 (01 de 02)

    Controladores electrnicos de nivelpara lquidos conductores

    Electronic level controllersfor liquid conductors

    Proteccin contra perturbacionesde tormentas mediante varistores.

    Regulacin de sensibilidad.

    Varistor protection againstelectrical storm interference.

    Sensitivity regulation.

    Para ral DIN y bornes enchufables.For DIN rail and plug-in terminals.

    AKO-53173

    Sonda electrodoSensor electrode

    AKO-53171Llenado

    (depsito)o

    Vaciado(pozo)

    Filling(tank)

    orDraining

    (well)

    AKO-53172TrasvaseLlenado

    (depsito)+

    Vaciado(pozo)

    TransferFilling(tank)

    +Draining

    (well)

    R

    www.ako.es

    Llenado /Filling

    Vaciado /Draining

    Llenado /Filling

    Vaciado /Draining

  • 7/25/2019 355317000__1

    2/4

    HOJA TCNICA 5317H000 Edicin 01 (02 de 04) www.ako.es

    ESPECIFICACIONES TCNICAS / TECHNICAL SPECIFICATIONS

    INSTRUCCIONES

    CONTROLADORDebe estar instalado en un sitio protegido de las vibraciones,del agua, de los gases corrosivos y donde la temperaturaambiente no rebase los valores que figuran en las especifica-ciones tcnicas.

    SONDASLas sondas deben instalarse a la profundidad de los nivelesdeseados. Si se utiliza la sonda comn conectada a tierra,debe instalarse a mas profundidad que las otras para queest siempre sumergida. Si no se utiliza la sonda comn, lapared del depsito debe ser conductora y conectarse alborne de tierra del equipo.Los cables de las sondas nunca deben instalarse en una con-duccin junto con cables de potencia, control o alimentacin.

    CONEXIONADOVanse los esquemas en las etiquetas de caractersticas delos aparatos junto con estas instrucciones.Los cables de alimentacin deben ser los adecuados, el cir-cuito debe estar provisto de los dispositivos necesarios paraproteger contra las sobrecargas requeridas en la instalacindel edificio.El interruptor necesario para la desconexin debe estar mar-cado como dispositivo de desconexin del aparato y debe

    ser de mnimo 2A, 230V~, o 400V~ segn sea la alimenta-cin que se utilice y situado cerca del aparato.Los cables sern del tipo H05VV-F 2x0,5mm2 o tipo H05V-K1x0,5mm2.

    ADVERTENCIA: El uso del equipo no respetando las instruc-ciones del fabricante, puede alterar los requisitos de seguridaddel mismo.

    INSTRUCTIONS

    CONTROLLERThis must be installed in a location which is protected againstvibration, water and corrosive gases and where the environ-

    mental temperature does not go outside the values given inthe technical specifications.

    SENSORSThe sensors must be installed at the required depth levels. Ifthe common sensor is used connected to earth, then it must

    be installed at a greater depth so that it is always covered bythe liquid. If the common sensor is not used, then the tankwall must be a conductor and connected to the units earthterminal.The sensor cables must never be installed in the same con-duit as power, control or power supply wiring.

    CONNECTIONSee the diagrams on the specifications labels for the units,together with these instructions.The power supply cables should be suitable for the job andthe circuit should be protected with all necessary devices to

    protect the installation against overloads as required in thebuilding installation.The breaker required to turn off the unit must be marked as

    being the switching device for the unit and must be a mini-

    mum of 2A, 230V~, or 400V~ depending on the powersupply voltage used and should be located close to the unit.The cables shall be of the type H05VV-F 2x0.5mm2 or typeH05V-K 1x0.5mm2.

    WARNING: Using the unit without respecting the manufactu-rers instructions could lead to alterations in its safety requi-rements.

    CARACTERSTICAS

    Proteccin contra perturbaciones de tormentas mediantevaristores.

    A travs de las sondas circula corriente alterna para evi-tar los fenmenos de electrlisis.

    Potencimetro frontal para regular la sensibilidad. Actan por la discriminacin entre la resistencia del lqui-

    do entre dos sondas sumergidas y la ajustada en elpotencimetro de regulacin de sensibilidad.

    LED indicador del status del rel. Rel conmutado que permite realizar la funcin de llena-

    do (depsito) o vaciado (pozo). Bitensin pueden ser alimentados a 230V o 400V. Para ral DIN y bornes enchufables.

    FEATURES

    Varistor protection against electrical storm interference.

    Alternating current flows through the sensors in order toprevent any electrolysis phenomena.

    Front panel potentiometer for sensitivity regulation.

    Operate by discrimination between the liquid resistanceexisting between two submerged sensors and that adjus-ted by the regulation sensitivity potentiometer.

    Relay status LED indicator.

    Double-throw relay permitting the function of filling (tank)or draining (well).

    Dual-voltage, can be powered at 230V or 400V.

    For DIN rail and plug-in terminals.

    Ref. AKO-53171 Control llenado (depsito) o vaciado (pozo) / Filling control (tank) or draining (well)Ref. AKO-53172 Control de trasvase, llenado (depsito) + vaciado (pozo) / Transfer control, filling (tank) + draining (well)

    Alimentacin / Power supply 230/400V~ 10%, 50/60HzPotencia mxima absorbida / Maximum input power 5VATensin en las sondas / Sensor voltage 24V~, 50/60HzRegulacin de la sensibilidad / Sensitivity regulation 3K a / to 65KCable de 1 a 2,5mm2 para sondas / 1 to 2.5mm2 cable for sensors Longitud mx. / Max. length 200mRel de salida / Output relay SPDT, 8A, 250VTemperatura de trabajo / Operating temperature -20C a / to +60CCapacidad de los bornes / Terminal capacity 2,5mm2

    Sistema de montaje / Mounting system Sobre ral / on rail DIN 43880Dimensiones nominales / Nominal dimensions 90 x 58 x 52,5mmGrado de proteccin / Protection degree IP2XCaja de material ABS /ABS box material Grado / degree V0 (UL-94)Categora de instalacin / Installation category II segn /in accordance with CEI 664Ref. AKO-53173 Sonda electrodo de acero inoxidable con protector

    / Stainless steel electrode sensor with protectorAparatos de clase II con doble aislamiento entre alimentacin, circuito secundario y salida de rel.Class II units with double insulation between power supply, secondary circuit and relay output.

  • 7/25/2019 355317000__1

    3/4

    HOJA TCNICA 5317H000 Edicin 01 (03 de 04) www.ako.es

    Mx.

    Min.

    Com.

    7 8 9

    1 2 3 4 5 6

    AKO-53171

    0230V

    400V

    Mx.

    Min.

    Com.

    7 8 9

    1 2 3 4 5 6

    AKO-53171

    0230V

    400V

    RST

    Mx.

    Min.

    Com.

    Mx.

    Min.

    Com.

    7 8 9

    1 2 3 4 5 6

    AKO-53172

    0230V

    400V

    1011

    RST

    RST

    ESQUEMAS DE CONEXIN / WIRING DIAGRAMS

    Para la diferencia de profundidad entre las sondas de nivel mximo y las de nivel mnimo, deber tenerse en cuenta las capa-cidades del pozo y del depsito, junto con las frecuencias de funcionamiento deseadas en la bomba.

    The well and tank capacities must be taken into consideration for the difference in depth between the maximum and minimumlevels sensors, together with the required pump operating frequencies.

    Llenado (depsito)Filling (tank)

    Vaciado (pozo)Draining (well)

    Trasvase entre pozo y depsitoTransfer between well and tank

  • 7/25/2019 355317000__1

    4/4

    AKO-53161

    50mm

    AKO-53162

    50mm

    AKO-53165

    27mm

    AKO-53166

    27mm

    Ref.

    355317000 REV. 00 2002 D.L.: B-38769-02 Nos reservamos el derecho de suministrar materiales que pudieran diferir levemente de los descritos en nuestras hojas tcnicas.

    AKO Electromecnica, S.A.L.Av. Roquetes, 30-3808812 S. PERE DE RIBES (Barcelona)

    Tel. (34) 938 142 700Fax (34) 938 934 054Internet: www.ako.ese-mai l : [email protected]

    Apartado (P.O. Box), 508800 VILANOVA I LA GELTR (Spain)

    HOJA TCNICA 5317H000 Edicin 01 (04 de 04) www.ako.es

    Interruptores de nivel de uso industrialpara aguas residuales y otras aplicaciones

    Level switches of industrial applications

    for sewage and waste water

    Nivel mximoparo en llenado,marchaen vaciado

    Maximum levelstop when filling,start whendraining

    Nivel mnimomarchaen llenado,paro en vaciado

    Minimum levelstart whenfilling, stopwhen draining

    AKO-5310A

    6 m

    AKO-53104

    10 m

    AKO-53105

    15 m

    AKO-53106

    20 m

    AKO-53107

    30 m

    Informacin en Hoja Tcnica 5310H001Information in Data Sheet5310H001

    Ref.

    Cable

    Interruptores de nivel ecolgicos, sin plomoni mercurio, para aguas residuales, fecales, etc.

    Ecological level switches without lead neither

    mercury, for sewage and waste water, etc.

    AKO-53120

    6 m

    AKO-53124

    10 m

    AKO-53125

    15 m

    AKO-53126

    20 m

    AKO-53127

    30 m

    Informacin en Hoja Tcnica 5312H000Information in Data Sheet5312H000

    Ref.

    Cable

    Interruptores de nivel para lquidos,aguas limpias y aplicaciones generales.

    Level switches for liquids,

    clean water and general applications.

    AKO-53112

    2 m

    AKO-53114

    10 m

    Informacin en Hoja Tcnica 5311H000Information in Data Sheet5311H000

    Ref.

    Cable

    Negro/Black

    Azul/Blue

    Marrn/Brown

    Negro/Black

    Azul/Blue

    Marrn/Brown

    Nivel mximoparo en llenado,marchaen vaciado

    Maximum level

    stop when filling,start whendraining

    Nivel mximoparo en llenado,

    marchaen vaciado

    Maximum levelstop when filling,start whendraining

    Nivel mnimomarchaen llenado,paro en vaciado

    Minimum levelstart whenfilling, stopwhen draining

    Nivel mnimomarchaen llenado,paro envaciado

    Minimum levelstart whenfilling, stopwhen draining

    Negro/Black

    Azul/Blue

    Marrn/Brown

    Negro/Black

    Azul/Blue

    Marrn/Brown

    NIVEL MXIMO/ MAXIMUM LEVEL

    Negro/Black

    Azul/Blue

    Marrn/Brown

    NIVEL MNIMO/ MINIMUM LEVEL

    Negro/Black

    Azul/Blue

    Marrn/Brown

    Interruptores de nivel para lquidoscorrosivos y temperaturas hasta 125C

    Level switches for corrosives liquids

    and temperatures up to 125C.

    Informacin en Hoja Tcnica 5316H000Information in Data Sheet5316H000

    AKO-53161

    AKO-53165

    AKO-53162

    Horizontal Vertical

    AKO-53166