protecciones

15
LÌNEAS DE TRANSMISIÓN EN 230 KV (1) PROTECCIÓN PRIMARIA LINEA S/E RTC K RELÉ DE DISTANCIA AJUSTE FASE-FASE AJUSTE FASE-TIERRA ZONA 1 ZONA2 ZONA3 ZONA 1 ZONA2 (%) Fabricante Característica (ohmios) (ohmios) (ohmios) (ohmios) (ohmios) POMASQUI JAMONDNO POMASQUI 300 53.26 ALSTOM Cuadrilateral 10,89+j13.4 10,89+j18.91 (300) 0,89+j18.91 (1000) 10,89+j13.4 10,89+j18.91 (300) 212,2 km (2). --- --- --- --- --- --- --- --- STA. ROSA - POMASQUI ROSA 300 55.67 ALSTOM Cuadrilateral 10,89+j2.92 10,89+j5.26 (300) 0,89+j19,12 (1000) 10,89+j2.92 10,89+j5.26 (300) 45,91 km POMASQUI 300 ALSTOM Cuadrilateral 10,89+j2.92 10,89+j5.17 (300) 0,89+j12,49 (1000) 10,89+j2.92 10,89+j5.17 (300) STA ROSA - STO DOMINGO STO DOMINGO 160 74.00 GEC MHO --- --- --- 77,7 km STA ROSA 160 EPAC 3000 Cuadrilateral 1,35+j2.70 3.50+j7.00 (300) 4.07+j8.14 (800) 1,35+j2.70 3.50+j7.00 (300) STO DOMINGO - QUEVEDO STO DOMINGO 160 78.80 GEC MHO --- --- --- 104 km QUEVEDO 160 EPAC 3000 Cuadrilateral 1,59+j3.17 2.78+j5.55 (300) 3.45+j6.90 (800) 1,59+j3.17 2.78+j5.55 (300) QUEVEDO - PASCUALES PASCUALES 160 78.85 GEC MHO --- --- --- 145,25 km QUEVEDO 160 EPAC 3000 Cuadrilateral 2,2+j4.43 3.32+j5.72 (300) 3.87+j7.75 (800) 2,2+j4.43 3.32+j5.72 (300) PASCUALES - TRINITARIA PASCUALES 160 78.75 MITSUBISHI Cuadrilateral 3.00+j0.90 3.00+j1.60 (300) 3.00+j2.50 (800) 3.00+j0.90 3.00+j1.60 (300) 28,28 km TRINITARIA 160 MITSUBISHI Cuadrilateral 3.00+j0.90 3.00+j1.60 (300) 3.00+j2.50 (800) 3.00+j0.90 3.00+j1.60 (300) PASCUALES - DOS CERRITOS PASCUALES 160 78.98 EPAC 3000 Cuadrilateral 0,15+j0.32 6.00+j1.19 (300) 6.00+j2.41 (800) 0,15+j0.32 6.00+j1.19 (300) 9.9 km DOS CERROS 160 MITSUBISHI Cuadrilateral 6.00+j0.32 6.00+j0.91 (300) 6.00+j1.90 (800) 6.00+j0.32 6.00+j0.91 (300) MILAGRO - DOS CERRITOS MILAGRO 240 78.81 GEC MHO --- --- --- 42.8 km DOS CERROS 160 MITSUBISHI Cuadrilateral 6.00+j1.40 6.00+j2.6 (300) 6.00+j9.00 (800) 6.00+j1.40 6.00+j2.6 (300) MILAGRO - PASCUALES MILAGRO 240 78.80 GEC MHO --- --- 52,7 km PASCUALES 160 EPAC 3000 Cuadrilateral 0,81+j1.61 1.51+j3.01 (300) 2.29+j4.58 (800) 0,81+j1.61 1.51+j3.01 (300) MOLINO - MILAGRO MILAGRO 240 75.31 GEC MHO --- --- --- 135,74 km MOLINO 240 EPAC 3000 Cuadrilateral 3,33+j6.66 4.99+j9.87 (350) 6.24+j12.48 (750) 3,33+j6.66 4.99+j9.87 (350) MOLINO - PASCUALES PASCUALES 160 76.66 MITSUBISHI Cuadrilateral 3.00+j6.00 3.00+j10.00 (300) 3.00+j14.00 (800) 3.00+j6.00 3.00+j10.00 (300) 188,43 km MOLINO 240 EPAC 3000 Cuadrilateral 4,39+j8.77 6.58+j13.15 (300) 8.22+j16.44 (800) 4,39+j8.77 6.58+j13.15 (300) MOLINO - RIOBAMBA MOLINO 240 74.09 BBC MHO 12,00/83° (300) 13.33/83° (800) 12,00/75° (300) 157,3 km RIOBAMBA 120 GENERAL ELECTRIC MHO --- --- --- TOTORAS - MOLINO TOTORAS 120 74.12 EPAC 3000 Cuadrilateral 2,38+j4.76 4.46+j8.92 (300) 5.35+j10.70 (800) 2,38+j4.76 4.46+j8.92 (300) 200,2 km MOLINO 240 BBC MHO 15/75° (600) 18.46/75° (800) 15/75° (600) TOTORAS - RIOBAMBA RIOBAMBA 120 74.26 GENERAL ELECTRIC MHO --- --- --- 42,88 km TOTORAS 120 EPAC 3000 Cuadrilateral 0,51+j1.02 0.95j+1.91 (300) 2.39+j4.77 (800) 0,51+j1.02 0.95j+1.91 (300) STA ROSA - TOTORAS TOTORAS 120 74.10 GEC MHO --- --- --- 110,09 km STA ROSA 160 EPAC 3000 Cuadrilateral 1,80+j3.60 2.71+j5.42 (300) 4.16+j8.32 (800) 1,80+j3.60 2.71+j5.42 (300) (1) Los datos para todos los relés corresponden a impedancia en ohmios secundarios NOTA: la RTP para todos los casos es de 2000/1. (2) Jamondino no es responsabilidad de TRANSELECTRIC. NOMENCLATURA: ohmios/grados (tiempo de operación en milisegundos) R+jX ohmios (tiempo de operación en milisegundos) 4.75L75º 4.62L75º 7.22L75º 7.35L75º 8.56L75º 8.80L75º 3.55L60º 3.55L60º 4.33L60º 4.33L60º 14.59L60º 14.59L60º 12.00L83° 12.00L75° 8.11L60° 9.38L85° 9.79L75° 9.79L75° 4.00L60° 3.30L85° 5.18L60º 5.18L60º

Upload: rdelgranado

Post on 24-Oct-2015

29 views

Category:

Documents


7 download

TRANSCRIPT

Page 1: protecciones

LÌNEAS DE TRANSMISIÓN EN 230 KV

(1) PROTECCIÓN PRIMARIA

LINEA S/E RTCK RELÉ DE DISTANCIA

AJUSTE FASE-FASE AJUSTE FASE-TIERRA

ZONA 1 ZONA2 ZONA3 ZONA 1 ZONA2 ZONA3

(%) Fabricante Característica (ohmios) (ohmios) (ohmios) (ohmios) (ohmios) (ohmios)

POMASQUI JAMONDNO POMASQUI 30053.26

ALSTOM Cuadrilateral 10,89+j13.4 10,89+j18.91 (300) 10,89+j18.91 (1000) 10,89+j13.4 10,89+j18.91 (300) 10,89+j18.91 (1000)

212,2 km (2). --- --- --- --- --- --- --- --- ---

STA. ROSA - POMASQUI ROSA 30055.67

ALSTOM Cuadrilateral 10,89+j2.92 10,89+j5.26 (300) 10,89+j19,12 (1000) 10,89+j2.92 10,89+j5.26 (300) 10,89+j19,12 (1000)

45,91 km POMASQUI 300 ALSTOM Cuadrilateral 10,89+j2.92 10,89+j5.17 (300) 10,89+j12,49 (1000) 10,89+j2.92 10,89+j5.17 (300) 10,89+j12,49 (1000)

STA ROSA - STO DOMINGO STO DOMINGO 16074.00

GEC MHO --- --- --- ---

77,7 km STA ROSA 160 EPAC 3000 Cuadrilateral 1,35+j2.70 3.50+j7.00 (300) 4.07+j8.14 (800) 1,35+j2.70 3.50+j7.00 (300) 4.07+j8.14 (800)

STO DOMINGO - QUEVEDO STO DOMINGO 16078.80

GEC MHO --- --- --- ---

104 km QUEVEDO 160 EPAC 3000 Cuadrilateral 1,59+j3.17 2.78+j5.55 (300) 3.45+j6.90 (800) 1,59+j3.17 2.78+j5.55 (300) 3.45+j6.90 (800)

QUEVEDO - PASCUALES PASCUALES 16078.85

GEC MHO --- --- --- ---

145,25 km QUEVEDO 160 EPAC 3000 Cuadrilateral 2,2+j4.43 3.32+j5.72 (300) 3.87+j7.75 (800) 2,2+j4.43 3.32+j5.72 (300) 3.87+j7.75 (800)

PASCUALES - TRINITARIA PASCUALES 16078.75

MITSUBISHI Cuadrilateral 3.00+j0.90 3.00+j1.60 (300) 3.00+j2.50 (800) 3.00+j0.90 3.00+j1.60 (300) 3.00+j2.50 (800)

28,28 km TRINITARIA 160 MITSUBISHI Cuadrilateral 3.00+j0.90 3.00+j1.60 (300) 3.00+j2.50 (800) 3.00+j0.90 3.00+j1.60 (300) 3.00+j2.50 (800)

PASCUALES - DOS CERRITOS PASCUALES 16078.98

EPAC 3000 Cuadrilateral 0,15+j0.32 6.00+j1.19 (300) 6.00+j2.41 (800) 0,15+j0.32 6.00+j1.19 (300) 6.00+j2.41 (800)

9.9 km DOS CERROS 160 MITSUBISHI Cuadrilateral 6.00+j0.32 6.00+j0.91 (300) 6.00+j1.90 (800) 6.00+j0.32 6.00+j0.91 (300) 6.00+j1.90 (800)

MILAGRO - DOS CERRITOS MILAGRO 24078.81

GEC MHO --- --- --- ---

42.8 km DOS CERROS 160 MITSUBISHI Cuadrilateral 6.00+j1.40 6.00+j2.6 (300) 6.00+j9.00 (800) 6.00+j1.40 6.00+j2.6 (300) 6.00+j9.00 (800)

MILAGRO - PASCUALES MILAGRO 24078.80

GEC MHO --- ---

52,7 km PASCUALES 160 EPAC 3000 Cuadrilateral 0,81+j1.61 1.51+j3.01 (300) 2.29+j4.58 (800) 0,81+j1.61 1.51+j3.01 (300) 2.29+j4.58 (800)

MOLINO - MILAGRO MILAGRO 24075.31

GEC MHO --- --- --- ---

135,74 km MOLINO 240 EPAC 3000 Cuadrilateral 3,33+j6.66 4.99+j9.87 (350) 6.24+j12.48 (750) 3,33+j6.66 4.99+j9.87 (350) 6.24+j12.48 (750)

MOLINO - PASCUALES PASCUALES 16076.66

MITSUBISHI Cuadrilateral 3.00+j6.00 3.00+j10.00 (300) 3.00+j14.00 (800) 3.00+j6.00 3.00+j10.00 (300) 3.00+j14.00 (800)

188,43 km MOLINO 240 EPAC 3000 Cuadrilateral 4,39+j8.77 6.58+j13.15 (300) 8.22+j16.44 (800) 4,39+j8.77 6.58+j13.15 (300) 8.22+j16.44 (800)

MOLINO - RIOBAMBA MOLINO 24074.09

BBC MHO 12,00/83° (300) 13.33/83° (800) 12,00/75° (300) 13.33/75° (800)

157,3 km RIOBAMBA 120 GENERAL ELECTRIC MHO --- --- --- ---

TOTORAS - MOLINO TOTORAS 12074.12

EPAC 3000 Cuadrilateral 2,38+j4.76 4.46+j8.92 (300) 5.35+j10.70 (800) 2,38+j4.76 4.46+j8.92 (300) 5.35+j10.70 (800)

200,2 km MOLINO 240 BBC MHO 15/75° (600) 18.46/75° (800) 15/75° (600) 18.46/75° (800)

TOTORAS - RIOBAMBA RIOBAMBA 12074.26

GENERAL ELECTRIC MHO --- --- --- ---

42,88 km TOTORAS 120 EPAC 3000 Cuadrilateral 0,51+j1.02 0.95j+1.91 (300) 2.39+j4.77 (800) 0,51+j1.02 0.95j+1.91 (300) 2.39+j4.77 (800)

STA ROSA - TOTORAS TOTORAS 12074.10

GEC MHO --- --- --- ---

110,09 km STA ROSA 160 EPAC 3000 Cuadrilateral 1,80+j3.60 2.71+j5.42 (300) 4.16+j8.32 (800) 1,80+j3.60 2.71+j5.42 (300) 4.16+j8.32 (800)

(1) Los datos para todos los relés corresponden a impedancia en ohmios secundarios. NOTA: la RTP para todos los casos es de 2000/1.

(2) Jamondino no es responsabilidad de TRANSELECTRIC. NOMENCLATURA: ohmios/grados (tiempo de operación en milisegundos)

R+jX ohmios (tiempo de operación en milisegundos)

4.75L75º 4.62L75º

7.22L75º 7.35L75º

8.56L75º 8.80L75º

3.55L60º 3.55L60º

4.33L60º 4.33L60º

14.59L60º 14.59L60º

12.00L83° 12.00L75°

8.11L60° 9.38L85°

9.79L75° 9.79L75°

4.00L60° 3.30L85°

5.18L60º 5.18L60º

Page 2: protecciones

LÌNEAS DE TRANSMISIÓN EN 230 KV

(1) PROTECCIÓN SECUNDARIA

LINEA S/E RTCK RELÉ DE DISTANCIA

AJUSTE FASE-FASE AJUSTE FASE-TIERRA

ZONA 1 ZONA2 ZONA3 ZONA 1 ZONA2 ZONA3

(%) Modelo Característica (ohmios) (ohmios) (ohmios) (ohmios) (ohmios) (ohmios)

POMASQUI JAMONDNO POMASQUI 30053.26

ALSTOM Cuadrilateral 10,89+j13.40 10,89+j18.91 (300) 10,89+j18.91 (1000) 10,89+j13.40 10,89+j18.91 (300) 10,89+j18.91 (1000)

212,2 km (2). --- --- --- --- --- --- --- --- ---

STA. ROSA - POMASQUI ROSA 30055.67

ALSTOM Cuadrilateral 10,89+j2.92 10,89+j5.26 (300) 10,89+19.12 (1000) 10,89+j2.92 10,89+j5.26 (300) 10,89+19.12 (1000)

45,91 km POMASQUI 300 ALSTOM Cuadrilateral 10,89+j2.92 10,89+j5.17 (300) 10,89+j12.49 (1000) 10,89+j2.92 10,89+j5.17 (300) 10,89+j12.49 (1000)

STA ROSA - STO DOMINGO STO DOMINGO 16074.00

MM3T GEC MHO 2.56/75º 3.66/75º (300) 5.73/75º (800) 2.54/75º 3.66/75º (300) 5.37/75º (800)

77,7 km STA ROSA 160 MM3T GEC MHO 2.95/75º 5.09/75º (300) 8.04/75º (800) 2.89/75º 4.69/75º (300) 10.72/75º (800)

STO DOMINGO - QUEVEDO STO DOMINGO 16078.80

MM3T GEC MHO 3.61/75º 7.54/75º (300) 9.84/75º (800) 3.54/75º 5.41/75º (300) 9.84/75º (800)

104 km QUEVEDO 160 MM3T GEC MHO 3.41/75º 6.72/75º (400) 9.84/75º (1000) 3.41/75º 5.58/75º (400) 9.84/75º (1000)

QUEVEDO - PASCUALES PASCUALES 16078.85

MM3T GEC MHO 4.59/60º 8.20/60º (300) 10.25/60º (800) 4.92/60º 7.67/60º (300) 11.28/60º (800)

145,25 km QUEVEDO 160 MM3T GEC MHO 4.28/75º 6.00/75º (400) 11.12/75º (1000) 4.12/75º 6.00/75º (400) 10.80/75º (1000)

PASCUALES - TRINITARIA PASCUALES 16078.75

MITSUBISHI Cuadrilateral 6.00+j0.90 6.00+j1.60 (300) 6.00+j1.50 (600) 6.00+j0.90 6.00+j1.60 (300) 6.00+j1.50 (600)

28,28 km TRINITARIA 160 MITSUBISHI Cuadrilateral 6.00+j1.35 6.00+j3.60 (300) 6.00+j9.50 (800) 6.00+j1.35 6.00+j3.60 (300) 6.00+j9.50 (800)

PASCUALES - DOS CERRITOS PASCUALES 16078.98

MM3T GEC MHO 0.34/75º 1.22/75º (300) 2.29/75º (800) 0.34/75º 1.22/75º (300) 2.29/75º (800)

9.9 km DOS CERROS 160 MITSUBISHI Cuadrilateral 6.00+j0.32 6.00+j0.91 (300) 6.00+j1.90 (800) 6.00+j0.32 6.00+j0.91 (300) 6.00+j1.90 (800)

MILAGRO - DOS CERRITOS MILAGRO 24078.81

MM3T GEC MHO 2.01/60º 4.46/60º (300) 6.79/60º (800) 2.02/60º 3.00/60º (300) 6.37/60º (800)

42.8 km DOS CERROS 160 MITSUBISHI Cuadrilateral 6.00+j1.40 6.00+j2.60 (300) 6.00+j9.00 (800) 6.00+j1.40 6.00+j2.60 (300) 6.00+j9.00 (800)

MILAGRO - PASCUALES MILAGRO 24078.80

MM3T GEC MHO 2.01/60º 4.46/60º (300) 6.79/60º (800) 2.02/60º 3.75/60º (300) 6.37/60º (800)

52,7 km PASCUALES 160 MM3T GEC MHO 1.97/75º 3.35/75º (300) 4.69/75º (800) 1.37/75º 2.35/75º (300) 3.62/75º (800)

MOLINO - MILAGRO MILAGRO 24075.31

MM3T GEC MHO 7.13/60º 10.70/60º (300) 14.94/60º (800) 6.50/60º 10.57/60º (300) 15.91/60º (800)

135,74 km MOLINO 240 MM3T GEC MHO 6.96/60º 10.14/60º (300) 13.51/60º (800) 6.96/60º 10.14/60º (300) 13.51/60º (800)

MOLINO - PASCUALES PASCUALES 16076.66

MITSUBISHI Cuadrilateral 3.00+j6.00 3.00+j9.00 (300) 3.00+j14.00 (800) 3.00+j6.00 3.00+j9.00 (300) 3.00+j14.00 (800)

188,43 km MOLINO 240 GENERAL ELECTRIC MHO 8.82/60º 11.11/60º (300) --- 9.38/85º 15.00/85º (300) ---

MOLINO - RIOBAMBA MOLINO 24074.09

BBC Cuadrilateral 7.69+j7.69 11.76+j11.76 (300) 15.38+j15.38 (800) 7.69+j7.69 11.76+j11.76 (300) 15.38+j15.38 (800)

157,3 km RIOBAMBA 120 GENERAL ELECTRIC MHO 4.17/60º 6.38/60º (300) --- 4.41/85º 6.82/85º (300) ---

TOTORAS - MOLINO TOTORAS 12074.12

MM3T GEC MHO 5.24/60º 7.49/60º (300) 10.48/60º (800) 5.24/60º 7.49/60º (300) 10.48/60º (800)

200,2 km MOLINO 240 BBC Cuadrilateral 10+j10 14.28+j14.28 (300) 18.18+j18.18 (600) 10+j10 14.28+j14.28 (300) 18.18+j18.18 (600)

TOTORAS - RIOBAMBA RIOBAMBA 12074.26

GENERAL ELECTRIC MHO 1.09/60º 4.00/60º (300) --- 1.00/85º 4.00/85º (300) ---

42,88 km TOTORAS 120 MM3T GEC MHO 1.10/60º 1.79/60º (300) 5.10/60º (800) 1.08/60º 1.68/60º (300) 5.10/60º (800)

STA ROSA - TOTORAS TOTORAS 12074.10

MM3T GEC MHO 2.71/60º 4.48/60º (300) 6.22/60º (800) 2.71/60º 4.48/60º (300) 6.22/60º (800)

110,09 km STA ROSA 160 MM3T GEC MHO 3.61/60º 5.74/60º (300) 8.45/60º (800) 3.86/60º 6.00/60º (300) 10.31/60º (800)

(1) Los datos para todos los relés corresponden a impedancia en ohmios secundarios. NOTA: la RTP para todos los casos es de 2000/1

(2) Jamondino no es responsabilidad de TRANSELECTRIC. NOMENCLATURA: ohmios/grados (tiempo de operación en milisegundos)

R+jX ohmios (tiempo de operación en milisegundos)

Page 3: protecciones

LÌNEAS DE TRANSMISIÓN EN 138 KV

120 (1) PROTECCIÓN PRIMARIA

LINEA S/E RTC

IMPEDANCIAK RELÉ DE DISTANCIA

AJUSTE FASE-FASE AJUSTE FASE-TIERRA

PRIMARIA ZONA 1 ZONA2 ZONA3 ZONA 1 ZONA2

(ohmios) (grados) (%) Modelo Característica (ohmios) (ohmios) (ohmios) (ohmios) (ohmios)

STO DOMINGO - ESMERALDAS DOMINGO 160 80.8 71.9473.91

EPAC3000 Cuadrilateral 7,54+j9,69 7,54+j15,08 (300) 10,77+j21,54 (1000) 7,54+j9,69 7,54+j15,08 (300)

158,8 Km ESMERALDAS 120 259.96 76.37 GEC MHO 11,96/75° --- --- 11,96/75° ---

QUEVEDO - DAULE QUEVEDO 100 22.55 71.9573.91

MITSUBISHI MHO 2,91/75° --- --- 2,91/75° ---

43,2 Km (2). --- 72.55 76.36 --- --- --- --- --- --- ---

DAULE - CHONE (2). --- 32.2 83 --- --- --- --- --- --- ---

63,75 km CHONE 120 MITSUBISHI Cuadrilateral 3,00+j2,80 0,40+j3,85 3,00+j3,85 3,00+j2,80 0,40+j3,85

SEVERINO - CHONE (2). --- 15.245514094 71.29 --- --- --- --- --- --- ---

CHONE 120 MITSUBISHI Cuadrilateral 3,00+j1,25 0,40+j1,70 3,00+j1,70 3,00+j1,25 0,40+j1,70

INTERCONEXION TULCAN 240 4.3 75.43234.11

(3) ABB REL512 MHO 1,20/75° --- --- 1,20/75° ---

15.8 km (2). --- 34.5 78 --- --- --- --- --- --- ---

IBARRA - TULCAN IBARRA 80 38.36 74.8378.02

GENERAL ELECTRIC MHO 3,00/60° --- --- 3,00/85° ---

74.48 km TULCAN 120 128.3 77.41 GENERAL ELECTRIC MHO 6,00/60° --- --- 6,00/85° ---

DAULE - PORTOVIEJO (2). --- 47.61 71.9473.90

--- --- --- --- --- --- ---

91,2 Km PORTOVIEJO 120 153.16 76.37 GEC MHO 7,20/60° --- --- 7,20/60° ---

PASCUALES - POLICENTRO PASCUALES 240 7.66 74.5876.15

GENERAL ELECTRIC MHO 2,83/60° --- --- 2,83/85° ---

15,1 Km POLICENTRO 160 25.16 77.18 GEC - SHPM MHO 0,76/ 1,44/ (250) 1,51/ (600) 0,76/ 1,44/ (250)

PASCUALES - SALITRAL PASCUALES 240 8.83 74.6176.07

GEC MHO 3,08/75° --- --- 3,26/75° ---

17,4 Km SALITRAL 160 28.98 77.21 MITSUBISHI MHO 3,00/75° --- --- 3,00/75° ---

PASCUALES - ELECTROQUIL PASCUALES 19.85 71.9573.90

WESTINHOUSE MHO 14,82/75° --- --- 12,22/75° 40,07/75°

38,03 Km (2). --- 63.86 76.37 --- --- --- --- --- --- ---

PASCUALES - STA ELENA PASCUALES 240 54.01 71.677.18

MITSUBISHI MHO 12,75/75° --- --- 11,84/75° ---

105,48 Km STA ELENA 240 179.06 76.37 MITSUBISHI MHO 3,00/75° --- --- 3,00/75° ---

MILAGRO - IDELFONSO MILAGRO 120 58.8 71.9473.96

ABB REL316 Cuadrilateral 1,96+j4,48 2,68+j6,72 (400) 3,235+j8,40 (800) 3,19+j4,48 3,90+j6,72 (400)

112,7 Km IDELFONSO 400 189.26 76.37 ABB REL316 Cuadrilateral 6,46+j14,77 9,77+j22,16 (400) 10,67+j27,69 (800) 10,50+j14,77 13,81+j22,16 (400)

IDELFONSO - MACHALA IDELFONSO 400 10.96 71.9473.91

ABB REL316 Cuadrilateral 2,54+j2,75 3,02+j4,17 (400) 3,32+j5,16 (800) 6,58+j2,75 7,06+j4,17 (400)

21 Km MACHALA 120 35.26 76.37 ABB REL316 Cuadrilateral 0,77+j0,84 0,96+j1,25 (400) 1,01+j1,57 (800) 2,00+j0,84 2,19+j1,25 (400)

IDELFONSO - MPP IDELFONSO ABB REL316 Cuadrilateral 1,87+j1,54 2,02+j2,32 (400) 2,06+j2,89 (800) 4,62+j1,54 5,32+j2,32 (400)

(2). --- --- --- --- --- --- --- ---

MOLINO - CUENCA MOLINO 300 35.53 72.1873.15

MITSUBISHI MHO 13,65/75° --- --- 13,73/75° ---

67,08 Km CUENCA 100 113.5 74.28 MITSUBISHI MHO 6,82/75° --- --- 4,63/75° ---

TOTORAS - AGOYAN TOTORAS 120 16.38 78.1978.04

GEC MHO 3,04/60° --- --- 3,03/60° ---

33 Km AGOYAN 240 54.73 76.11 GEC MHO 7,06/75| --- --- 7,25/75° ---

TENA - FCO. DE ORELLANA TENA 600/5 67.622277268 60.375775673772.83

SIEMENS Cuadrilateral 30 + J 0,25 30 + J 7,08 30 + J 8,35 30 + J 9,15 30 + J12,50

139 Km ORELLANA 600/5 215.3632763 62.2491788882 SIEMENS Cuadrilateral 31 + J 0,25 31 + J 7,08 31 + J 8,33 31 + J 7,5 31 + J 10,83

(1) Los datos para todos los relés corresponden a impedancia en ohmios secundarios. NOTA: la RPT es 1200/1 en todos los casos a ecepción de la S/E Esmeraldas cuya relación es 1150/1

(2) Estas posiciones no son responsabilidad de TRANSELECTRIC NOMENCLATURA: ohmios/grados (tiempo de operación en milisegundos)

(3) Tiene otras funciones a mas de la de distancia. R+jX ohmios (tiempo de operación en milisegundos)

Page 4: protecciones

(1) PROTECCIÓN PRIMARIA

ABB REL512

AJUSTE FASE-TIERRA Prot. 67P - 67N

ZONA3 67P 67N

(ohmios) (A) (A)

10,77+j21,54 (1000) --- ---

--- --- ---

--- --- ---

--- --- ---

--- --- ---

3,00+j3,85 --- ---

--- --- ---

3,00+j1,70 --- ---

--- 8.00 8.00

--- --- ---

--- --- ---

--- --- ---

--- --- ---

--- --- ---

--- --- ---

1,51/ (600) --- ---

--- --- ---

--- --- ---

--- --- ---

--- --- ---

--- --- ---

--- --- ---

4,46+j8,40 (800) --- ---

14,71+j27,69 (800) --- ---

7,36+j5,16 (800) --- ---

2,24+j1,57 (800) --- ---

5,36+j2,89 (800) --- ---

--- --- ---

--- --- ---

--- --- ---

--- --- ---

--- --- ---

30 + J 13,3 --- ---

31 + J 11,67 --- ---

Page 5: protecciones

LÌNEAS DE TRANSMISIÓN EN 138 KV

(1) PROTECCIÓN SECUNDARIA

PROTECCION SOBRECORRIENTE

LINEA S/E RTC

IMPEDANCIAK RELÉ DE DISTANCIA

AJUSTE FASE-FASE AJUSTE FASE-TIERRA PROTECCION DE FASE

PRIMARIA ZONA 1 ZONA2 ZONA3 ZONA 1 ZONA2 ZONA3TAP DIAL

INST

(ohmios) (grados) (%) Modelo Característica (ohmios) (ohmios) (ohmios) (ohmios) (ohmios) (ohmios) (A)

INTERCONEXION TULCAN 240 4.3 75.43234.11

(4) ABB REL512 MHO 0,68/ 1,00/ (250) 1,20/ (600) 0,68/ 1,00/ (250) 1,20/ (600) --- --- ---

15.8 km (3). --- 34.5 78 --- --- --- --- --- --- --- --- --- --- ---

STA. ROSA - VICENTINA STA ROSA 80 9.53 74.8378.14

GENERAL ELECTRIC MHO 1,06/75° 4,47/75° (500) --- 1,13/75° 4,50/75° (500) --- --- --- ---

18,5 Km VICENTINA 80 31.87 77.4 GENERAL ELECTRIC MHO 0,51/90° 0,85/90° (300) 3,03/60° (800) 0,51/90° 0,85/90° (300) 3,03/60° (800) --- --- ---

VICENTINA - IBARRA VICENTINA 80 41.19 74.7775.29

GENERAL ELECTRIC MHO 2,27/60° 3,41/60° (300) 5,00/75° (800) 2,33/90° 3,51/90° (300) 4,76/60° (800) --- --- ---

80 Km IBARRA 120 134.23 75.09 GENERAL ELECTRIC MHO 3,67/60° 6,00/60° (300) 10,00/75° (800) 3,51/90° 5,00/90° (300) 10,00/60° (800) --- --- ---

IBARRA - TULCAN IBARRA 120 38.36 74.8378.15

GENERAL ELECTRIC MHO 3,61/60° 5,00/60° (300) --- 3,61/75° 5,45/75° (300) --- --- --- ---

74,48 Km TULCAN 120 128.3 77.41 GENERAL ELECTRIC MHO 3,17/60° 6,52/60° (300) --- 3,19/75° 6,25/75° (300) --- --- --- ---

GUANGOPOLO - VICENTINA GUANGOPOLO 80 3.61 74.7278.02

GENERAL ELECTRIC MHO 0,21/90° 1,67/90° (300) 2,70/60° (1200) 3,07/90° 4,49/90° (300) 6,0060° (1200) --- --- ---

7 Km VICENTINA 80 12.06 77.41 GENERAL ELECTRIC MHO 0,23/90° 0,40/90° (300) 1,00/60° (800) 0,22/90° 0,40/90° (300) 1,00/60° (800) --- --- ---

MULALO - VICENTINA MULALO 80 38.12 74.8378.14

GENERAL ELECTRIC MHO 2,21/60° 3,33/60° (300) 4,0075° (800) 2,13/90° 3,33/90° (300) 4,0060° (800) --- --- ---

74 Km VICENTINA 80 127.48 77.41 GENERAL ELECTRIC MHO 2,21/60° 3,33/60° (300) 4,00/75° (800) 2,13/90° 3,33/90° (300) 4,00/60° (800) --- --- ---

PUCARA - AMBATO PUCARA 80 14.28 74.8578.22

GENERAL ELECTRIC MHO 0,68/90° 1,03/90° (300) 1,43/60° (800) 0,68/90° 1,03/90° (300) 1,43/60° (800) --- --- ---

27.74 Km AMBATO 80 47.79 77.41 GENERAL ELECTRIC MHO 0,68/90° 1,67/90° (300) 2,38/60° (800) 0,79/90° 1,52/90° (300) 2,00/60° (800) --- --- ---

PUCARA - MULALO PUCARA 80 18.04 74.8278.09

GENERAL ELECTRIC MHO 1,00/90° 2,00/90° (300) 3,00/75° (800) 0,93/90° 2,00/90° (300) 2,53/60° (800) --- --- ---

35 Km MULALO 80 60.3 77.41 GENERAL ELECTRIC MHO 1,00/90° 2,00/90° (300) 2,00/75° (800) 0,93/90° 2,00/90° (300) 2,67/60° (800) --- --- ---

TOTORAS - AGOYAN TOTORAS 120 16.38 78.1978.04

GEC MHO 1,38/60° 2,41/60° (300) 3,58/60° (1000) 1,46/60° 2,41/60° (300) 3,44/60° (1000) --- --- ---

33 Km AGOYAN 240 54.73 76.11 GEC MHO 2,61/75° 4,62/75° (400) --- 2,73/75° 5,30/75° (450) --- --- --- ---

TOTORAS - AMBATO TOTORAS 120 3.7 72.3176.22

(2) Sobrecorriente --- --- --- --- --- --- --- 5.00 0.30 13.00

7 Km AMBATO 120 12.16 76.59 (2) Sobrecorriente --- --- --- --- --- --- --- 5.00 0.50 7.00

STO DOMINGO - ESMERAL DOMINGO 160 80.8 71.9473.91

GEC MHO 8,56/75° 13,60/75° (300) 22,40/75° (800) 8,56/75° 13,60/75° (300) 22,40/75° (800) --- --- ---

158,8 Km ESMERALDAS 120 259.96 76.37 GEC MHO 7,02/75° 10,20/75° (300) 14,63/75° (800) 7,15/75° 12,53/75° (300) 16,27/75° (800) --- --- ---

DAULE - CHONE (3). --- 32.2 83 --- --- --- --- --- --- --- --- --- --- ---

CHONE 120 MITSUBISHI Cuadrilateral 3,00+j2,81 3,00+j3,37 (300) 3,00+j3,53 (600) 3,00+j2,81 3,00+j3,37 (300) 3,00+j3,53 (600) --- --- ---

QUEVEDO - DAULE QUEVEDO 100 22.55 71.9573.91

WESTINHOUSE MHO 1,65/75° 2,50/75° (300) --- 1,64/75° 2,45/75° (300) --- --- --- ---

43,2 Km (3). --- 72.55 76.36 --- --- --- --- --- --- --- --- --- --- ---

SEVERINO - CHONE (3). --- 15.2455140943164 71.29 --- --- --- --- --- --- --- --- --- --- ---

CHONE 120 MITSUBISHI Cuadrilateral 3,00+j1,27 3,00+j1,73 (300) 3,00+j1,73 (600) 3,00+j1,27 3,00+j1,73 (300) 3,00+j1,73 (600) --- --- ---

DAULE - PORTOVIEJO (3). --- 47.61 71.9473.90

--- --- --- --- --- --- --- --- --- --- ---

91,2 Km PORTOVIEJO 120 153.16 76.37 GEC MHO 4,69/60° 6,32/60° (300) 7,67/60° (800) 5,3/60° 7,00/60° (300) 8,76/60° (800) --- --- ---

PASCUALES - POLICENTRO PASCUALES 240 7.66 74.5876.15

GENERAL ELECTRIC MHO 1,16/60° 2,30/60° (300) --- 1,14/75° 2,59/75° (300) --- --- --- ---

15,1 Km POLICENTRO 160 25.16 77.18 GEC SHPM MHO 0,76/ 1,15/ (250) 1,87/ (600) 0,76/ 1,15/ (250) 1,87/ (600) --- --- ---

PASCUALES - SALITRAL PASCUALES 240 8.83 74.6176.07

GEC MHO 1,60/75° 2,52/75° (300) 2,96/75° (1000) 1,71/75° 2,38/75° (300) 2,95/75° (1000) --- --- ---

17,4 Km SALITRAL 240 28.98 77.21 WESTINHOUSE MHO 1,43/75° 2,08/75° (300) --- 1,64/75° 2,48/75° (300) --- --- --- ---

PASCUALES - ELECTROQUIL PASCUALES 240 19.85 71.9573.90

WESTINHOUSE MHO 2,68/75° 13,85/75° (300) --- 2,46/75° 14,87/75° (300) --- --- --- ---

38,03 Km (3). --- 63.86 76.37 --- --- --- --- --- --- --- --- --- --- ---

ELECTROQUIL - POSORJA (3). --- 42.67 71.5860.15

--- --- --- --- --- --- --- --- --- --- ---

83,34 Km POSORJA 119.67 76.38 --- --- --- --- --- --- --- --- --- --- ---

PASCUALES - STA ELENA PASCUALES 240 54.01 71.677.18

WESTINHOUSE MHO 12,75/75° 17,40/75° (300) --- 11,84/75° 16,88/75° (300) --- --- --- ---

105,48 Km STA ELENA 240 179.06 76.37 WESTINHOUSE MHO 3,00/75| 4,80/75° (500) --- 3,00/75° 4,77/754° (500) --- --- --- ---

MILAGRO - BABAHOYO MILAGRO 120 23.72 71.3279.74

GENERAL ELECTRIC MHO 1,81/60° 3,19/60° (300) --- 1,50/75° 3,00/75| (300) --- --- --- ---

47,3 Km BABAHOYO --- 80.46 76.38 --- --- --- --- --- --- --- --- --- --- ---

MILAGRO - IDELFONSO MILAGRO 120 58.8 71.9473.96

GENERAL ELECTRIC MHO 5,00/60° 6,98/60° (300) --- 5,00/75° 7,89/75° (300) --- --- --- ---

112,7 Km IDELFONSO 400 189.26 76.37 ABB REL316 Cuadrilateral 6,46+j14,77 9,77+j22,16 (400) 10,67+j27,69 (800) 10,50+j14,77 13,81+j22,16 (400) 14,71+j27,69 (800) --- --- ---

IDELFONSO - MACHALA IDELFONSO 400 10.96 71.9473.91

ABB REL316 Cuadrilateral 2,54+j2,75 3,02+j4,17 (400) 3,32+j5,16 (800) 6,58+j2,75 7,06+j4,17 (400) 7,36+j5,16 (800) --- --- ---

21 Km MACHALA 120 35.26 76.37 GENERAL ELECTRIC MHO 0,95/60° 3,37/60° (300) --- 0,93/75° 2,0075° (300) --- --- --- ---

IDELFONSO - MPP IDELFONSO 400 ABB REL316 Cuadrilateral 1,87+j1,54 2,02+j2,32 (400) 2,06+j2,89 (800) 4,62+j1,54 5,32+j2,32 (400) 5,36+j2,89 (800) --- --- ---

(3). --- --- --- --- --- --- --- --- --- --- --- ---

CUENCA LOJA CUENCA 100 71.09 72.2375.90

GENERAL ELECTRIC MHO 4,17/60° 6,38/60° (300) --- 5,56/75° 6,12/75° (300) --- --- --- ---

134,2 Km LOJA 80 232.97 76.6 GENERAL ELECTRIC MHO 4,30/60° 7,69/60° (300) --- 3,90/75° 7,69/75° (300) --- --- --- ---

MOLINO - CUENCA MOLINO 300 35.53 72.1873.15

WESTINHOUSE MHO 7,50/75° 12,75/75° (300) --- 7,43/75° 12,98/75° (300) --- --- --- ---

67,08 Km CUENCA 100 113.5 74.28 WESTINHOUSE MHO 2,61/75° 5,04/75° (300) --- 2,82/75° 5,04/75° (300) --- --- --- ---

TENA - FCO. DE ORELLANA TENA 600/5 67.6222772677681 60.375775673693272.83

SIEMENS Cuadrilateral 30 + J 0,25 30 + J 7,08 30 + J 8,35 30 + J 9,15 30 + J12,50 30 + J 13,3 --- --- ---

139 Km ORELLANA 600/5 215.363276300209 62.2491788882159 SIEMENS Cuadrilateral 31 + J 0,25 31 + J 7,08 31 + J 8,33 31 + J 7,5 31 + J 10,83 31 + J 11,67 --- --- ---

Page 6: protecciones

(1) Los datos para todos los relés corresponden a impedancia en ohmios secundarios. NOTA: la RPT para todos los casos es 1200/1 a excepción de Esmeraldas que tiene 1150/1

(2) Solo se tienen protección 21. NOMENCLATURA: ohmios/grados (tiempo de operación en milisegundos)

(3) Estas posiciones no son de responsabilidad de TRANSELECTRIC R+jX ohmios (tiempo de operación en milisegundos)

(4) El REL512 de la ABB tiene otras funciones a mas de la distancia

Page 7: protecciones

(1) PROTECCIÓN SECUNDARIA

PROTECCION SOBRECORRIENTE

PROTECCION DE TIERRA

TAP DIALINST

(A)

--- --- ---

--- --- ---

--- --- ---

--- --- ---

--- --- ---

--- --- ---

--- --- ---

--- --- ---

--- --- ---

--- --- ---

--- --- ---

--- --- ---

--- --- ---

--- --- ---

--- --- ---

--- --- ---

--- --- ---

--- --- ---

2.00 0.50 25.00

2.50 0.50 35.00

--- --- ---

--- --- ---

--- --- ---

--- --- ---

--- --- ---

--- --- ---

--- --- ---

--- --- ---

--- --- ---

--- --- ---

--- --- ---

--- --- ---

--- --- ---

--- --- ---

--- --- ---

--- --- ---

--- --- ---

--- --- ---

--- --- ---

--- --- ---

--- --- ---

--- --- ---

--- --- ---

--- --- ---

--- --- ---

--- --- ---

--- --- ---

--- --- ---

--- --- ---

--- --- ---

--- --- ---

--- --- ---

--- --- ---

--- --- ---

Page 8: protecciones

AJUSTE DE LOS RELES DE SOBRECORRIENTE DE LOS TRANSFORMADORESFECHA DE ACTUALIZACION: 5/30/2005

SUBESTACION UBICACIÓN POSICIONRELE

RTC TAP DIAL MVAPROTECCION TIPO

Ambato T1 69 kV 652-T1 51 IAC53 400/5 6 3.5 57T1 neutro 69 kV --- 51N IAC53 400/5 2 9

Ibarra

ATQ 138 kV 52-1Q2 51 IAC52 300/5 6 3 86ATQ neutro --- 51N IAC52 200/5 4 4ATQ 69 kV 52-0Q2 51 CO-9I 600/5 4 2.5 57ATQ 69 kV 52-0Q2 51N CO-9I 600/5 2.5 5T1 34.5 kV 352-T1 51 ICM21P 400/5 10 0.1 47T1 34.5 kV 352-T1 51N ICM22P 400/5 1.25 0.4

Mulaló ATQ 138 kV 52-1Q2 51-1Q2 IAC52A 300/5 5 2 71ATQ neutro --- 51N-1Q2 IAC52A 200/5 3.5 3

PomasquiATU 230 kV 52-2U2 F51-2U2 P442 (ALSTOM) 2200/5 2.2 0.2 385ATU 138 kV 52-1U2 F51-1U2 P126 (ALSTOM) 1800/5 4.5 0.15 387ATU neutro 51N-ATU P442 (ALSTOM) 1600/5 1.5 0.3

Riobamba TRK 230 kV 52-2K2 51 IFC51 600/5 2 2 95TRK neutro --- 51N IFC53 200/5 4 9

Sta. Rosa

ATU 230 kV 52-2U2 51A-2U2 CDG 11 (3s) 1000/5 6.25 0.05 498ATU neutro --- 51N-1U2 CDG13 200/5 3.75 0.4TRN 138 kV 52-1N2 51-1N2-A CO-8 (Mitsubishi) 400/5 6 0.5 114TRN neutro --- 51-1N2-N CO-9 (Mitsubishi) 200/5 6 7TRP138 52-1P2 51-1P2 7SJ61 (Siemens) 400/5 6 0.5 114TRP neutro --- 51-1P2-N 7SJ61 (Siemens) 300/5 4 7

Totoras

ATT 230 kV 52-2T2 51-2T2 CDG31 500/5 5 0.3 199ATT neutro --- 51N CDG13 400/5 2 0.3ATQ 138 kV 52-1Q2 51-1Q2 CDG31 600/5 3.75 0.6 107ATQ neutro --- 51N CDG13 400/5 2 0.7Ambato 138 67-132 (Inst=13) CDD 600/5 5 0.3

Tulcán ATQ 138 52-1Q2 51-1Q2 IFC51 (Gen. Elec.) 300/5 3 2.5 43ATQ neutro --- 51N-ATQ IFC53 (Gen. Elec.) 200/5 4 5

Vicentina

T1 46 kV 52-T1 51T1-138 IAC 53 (Gen. Electric) 400/5 8 2 50T1 neutro 138 kV --- 51N IAC 53 (Gen. Electric) 200/5 1.2 5T1 neutro 46 kV --- 51N IAC 53 (Gen. Electric) 600/5 2 5T2 138 kV 52-T2 51T2-138 IAC53 (Gen.Electric) 600/5 5 0.75 143Terciario --- 51T2-13.8 IAC53 (Gen.Electric) 2400/5 4 0.5 45T2 neutro --- 51G-T2 IAC53 (Gen.Electric) 3000/5 0.5 4.5T2 residual 138 --- 51N-T2 IAC53 (Gen.Electric) 600/5 2 2.5

Esmeraldas AA1 138 kV 452-AA1 51A-A1 CDG31 (1.3) 300/5 6.25 0.55 89AA1 69 kV 352-AA1 51B-A1 CDG31 (1.3) 600/5 6.25 0.5 89AA1 69 kV 352-AA1 51N-A1 CDG13 600/5 2 0.7

ChoneATQ 138 kV 52-1Q2 51-1Q2 COC3-20-M1 400/5 4 1.5 76ATQ 138 kV 52-1Q2 51N-ATQ COC1-20-M1 400/5 1.5 2ATQ neutro --- 51N-OQ2 COC1-20-M1 500/5 2 2.5

Portoviejo

AA1 138 kV 452-A1 51 CDG31 300/5 6.25 0.3 89AA1 138 kV 51N CDG13 300/5 0.75 0.6AA1 69 kV 352-A1 51 CDG31 600/5 6.25 0.35 89AA1 69 kV 51N CDG13 600/5 2 0.5AA2 138 kV 452-A2 51 SPAJ140C 300/5 6.25 0.4 89AA2 138 kV 51N SPAJ140C 300/5 2.5 1AA2 69 kV 352-A2 51 SPAJ140C 600/5 6.25 0.4 89AA2 69 kV 51N SPAJ140C 600/5 2 0.15

Quevedo

ATT 230 kV 52-2T2 51-2T2 CDG11 (3s) 600/5 5 0.12 239ATT neutro --- 51N-1T2 CDG13 200/5 4 0.55ATR 138 kV 52-1R2 51-1R2 CO-8 (Mitsubishi) 800/5 5 0.5 191ATR neutro --- 51N-ATR CO-9 (Mitsubishi) 600/5 5 3

Sto. Domingo

ATU 230 kV 52-2U2 51-2U2 CDG11 (3s) 600/5 3.75 0.2 179ATU neutro --- 51N CDG13 200/5 4 0.7ATR 138 kV 52-1R2 51-1R2 CDG11 (3s) 600/5 3.75 0.15 107ATR neutro --- 51N CDG13 200/5 4 0.6

Page 9: protecciones

AJUSTE DE LOS RELES DE SOBRECORRIENTE DE LOS TRANSFORMADORESFECHA DE ACTUALIZACION: 5/30/2005

57365.5227466812

SUBESTACION UBICACIÓN POSICIONRELE

RTC TAP DIAL MVAPROTECCION TIPO

Babahoyo ATQ 138 kV 52-1Q2 51 IAC52 300/5 5 5 71ATQ neutro --- 51N IAC52 200/5 4 3.5

Dos Cerritos ATK 230 KV 52-2K2 51-2K2 CO-C3-20M1 800/5 3.5 1.5 (MI) 223ATK neutro --- 51N-ATK CO-C1-20M1 1200/5 2 5 (MI)

Machala

ATQ 138 kV 52-1Q2 51 IFC51 600/5 4 1.5 114

ATQ neutro 51N IFC53 600/5 4 2

ATQ 69 kV 52-0Q2 51 7SJ61 (SIEMENS) 1200/5 4 1.5 113

ATQ residual 69 kV 51N 7SJ61 (SIEMENS) 1200/5 2.6 1.4

TRK 69 kV 52-0K2 51 7SJ61 (SIEMENS) 1500/5 3 1.1 106

TRK residual 69 kV 51N 7SJ61 (SIEMENS) 1500/5 2 1.2

TRK neutro 51N 7UT63 (SIEMENS) 1200/5 2.5 1.3

Milagro

ATK 230 kV 52-2K2 51 CDG11 600/5 5 0.1 239ATK neutro --- 51N CDG13 200/5 4 0.6ATQ 69 kV (vacío) 52-0Q2 51 DPU (ABB) 1200/5 28ATQ neutro --- 51N DPU (ABB) 1200/5ATU 230 kV 52-2U2 51-2U2 KCGG142 1200/5 2.5 0.125 239ATU 138 51-2U2 Residual KCGG142 1200/5 1.75 0.175ATU neutro --- 51N-ATU KCGG142 600/5 4 0.225

Pascuales

ATU 230 kV 52-2U2 51-2U2 CDG11 (3 s) 1200/5 6.25 0.1 597ATU neutro --- 51N-ATU CDG13 600/5 2.5 0.4ATT 230 kV 52-2T2 51-2T2 CO-8 (Mitsubishi) 1200/5 6 1 573ATT 230 kV (residual) 51N-ATT CO-9 (Mitsubishi) 1200/5 2 4ATR 138 kV 52-1R2 51-1R2 CO-9 (Westinghouse) 1200/5 5 2.5 286ATR neutro --- 51N-ATR CO-9 (Westinghouse) 600/5 2 6

Policentro ATQ 138 kV 52-1Q2 51 (Inst=25) MCGG (GEC) 800/5 5 0.125 191ATQ neutro --- 51N 800/5 3 0.15

Posorja ATQ 138 kV 52-1Q2 51-1Q2 IFC51 AD1A 600/5 1.5 2 43ATQ neutro --- 51N-1Q2 IFC53 BD2A 200/5 4 5

Sta. Elena ATQ 138 kV 52-142 51-1Q2 IFC51 AD1A (G.E.) 600/5 2 2.5 57ATQ neutro --- 51N-ATQ IFC53 BD2A (G.E.) 200/5 4 6.5

Salitral

ATQ 138 kV 52-1Q2 51-1Q2 CO-8 1000/5 4 0.75 191ATQ neutro --- 51N CO-9 200/5 6 6.8ATR 138 kV 52-1R2 51-1R2 Microshield (ABB) 1200/5 3.5 1.5 ###ATR neutro --- 51N-ATR Microshield (ABB) 600/5 2 7

Trinitaria

ATT 230 kV 52-2T2 51-2T2 CO-C3-20M1 1200/5 3.5 1 334ATT neutro --- 51N-ATT CO-C1-20M1 600/5 4 2ATQ 138 kV 52-1Q2 51-1Q2 CO-C3-20M1 1200/5 3.5 1.5 200ATQ neutro --- 51N-ATQ CO-C1-20M1 800/5 3 2

Cuenca ATQ 138 kV 52-0Q2 51-ATQ CDG11 (3 seg.) 600/5 5 0.2 143ATQ neutro --- 51N-1Q2 CDG13 200/5 4 0.8

Loja ATQ 138 kV 52-142 51 IFC51 600/5 2 2 57ATQ neutro --- 51N IFC53 200/5 4 8

Molino

AT1 138 kV 152-2AT1 51 CO-8 (Mitsubishi) 2000/5 6 0.5 573AT1 neutro --- 51N CO-8 (Mitsubishi) 1200/5 2 1AT2 138 kV 152-2AT2 51 CO-8 (Mitsubishi) 2000/5 6 0.5 573AT2 neutro --- 51N CO-8 (Mitsubishi) 1200/5 2 1

Móvil (Ibarra)

Transf. 138 50/51 (Inst=30) CO-8I (Mits.) 200/5 4 1.2 38

Alim. F1 67-F1 fase (Inst=12) 35

67-F1 tierra (Inst=15)

Tena

TRQ 138 kV 52-112 51-112 7UT613 (SIEMENS) 600/5 0.8 0.6 23

TRQ 138 kV 51N-112 7UT613 (SIEMENS) 600/5 0.4 1

TRQ 69 kV 52-0Q2 51-ATQ 7SJ602 (SIEMENS) 600/5 1.6 0.6 23

TRQ 69 kV 51N-0Q2 7SJ602 (SIEMENS) 600/5 0.7 1.3

Fco OrellanaATQ 69 kV 52-0Q2 51-0Q2 7UT613 (SIEMENS) 600/5 0.8 0.7 23

ATQ 138 kV 52-0Q2 51-ATQ 7SJ602 (SIEMENS) 600/5 0.8 0.7 23

CR-81 (Mits.) CR-8I (Mits.)

600/5 600/5

2.5 2.0

0.5 0.5

Page 10: protecciones

Fco Orellana

ATQ 138 kV 51N-0Q2 7SJ602 (SIEMENS) 600/5 0.6 2.1

Page 11: protecciones

AJUSTES DE LOS RELES DE SOBRECORRIENTE DE LOS ALIMENTADORES DEL SNTFECHA DE ACTUALIZACION: 5/30/2005

SUBESTACION POSICION ALIMENTADORRELE

RTC RTP TAP DIAL INST. MVAPROTECCION TIPO

Ambato

652-A1 Ambato 1 (Samanga 69) 50/51 IAC53 (Gen. Electric) 300/5 6 3 65 4350/51N IAC53 (Gen. Electric) 300/5 2 7 50

652-A2 Ambato 2 (Oriente 69) 50/51 IAC53 (Gen. Electric) 300/5 6 3 65 4350/51N IAC53 (Gen. Electric) 300/5 2 5 50

652-L Latacunga ELEPCO 69) 50/51 IAC53 (Gen. Electric) 300/5 5 3 36 3550/51N IAC53 (Gen. Electric) 300/5 2 5.5 28

Ibarra 34.5 kV352-L1 El Ambi 50/51 ICM21P (BB) 1200/5 2.5 0.1 11.25 35

50/51N ICM22P (BB) 80/1 1 0.3 Bloq.

352-L2 S. Alegre 50/51 ICM21P (BB) 1200/5+1/10 8 0.1 11 1150/51N ICM22P (BB) 1200/5+1/10 2 0.3 Bloq.

Ibarra 69 kV

52-012 Otavalo 67 CR-9I (Mitsubishi) 500/5 69/0.115 4 1.5 12 4767N CRP-9I (Mitsubishi) 500/5 anul. direcc. 2.5 3 12

52-022 Cotacachi 50/51 CO-9I (Mitsubishi) 500/5 2 2.5 20 2350/51N CO-9I (Mitsubishi) 500/5 2 3.5 12

52-032 Tulcan 50/51 CO-9I (Mitsubishi) 500/5 4 1.5 12 4750/51N CO-9I (Mitsubishi) 500/5 2.5 3 12

Mulaló52-0Q2 ELEPCO

Pomasqui 138kV52-132 Quito 1 F21P / F21S P442 (ALSTOM) 1500/5 2.5 0.25 179

F21P / F21S P442 (ALSTOM) 1500/5 1.5 0.3

52-152 Quito 2 F21P / F21S P442 (ALSTOM) 1500/5 2.5 0.25 179F21P / F21S P442 (ALSTOM) 1500/5 1.5 0.3

Riobamba

52-032 Riobamba 1 (S/E 4) 50/51 IFC51 (Gen. Electric) 600/5 4 2 32 5750/51N IFC53 (Gen. Electric) 600/5 4 2 32

52-042 Guaranda 50/51 IFC51 (Gen. Electric) 600/5 2 1.5 12 2850/51N IFC53 (Gen. Electric) 600/5 2 2 12

52-052 Riobamba 2 (S/E 1 ) 50/51 IFC51 (Gen. Electric) 600/5 4 1.75 28 3550/51N IFC53 (Gen. Electric) 600/5 2.5 5 28

52-082 Riobamba 3 ( S/E SAN JUAN ) 50/51 IFC51 (Gen. Electric) 600/5 2.5 2.5 25 3550/51N IFC53 (Gen. Electric) 600/5 2.5 4 25

Totoras

52-012 Ambato 67 CDD 600/5 69/0.115 3.75 0.4 Blq. 5367N CDD 600/5 2 0.4 Blq.

52-022 Montalvo 67 CDD 600/5 69/0.115 2.5 0.3 25 3567N CDD 600/5 2 0.3 25

52-032 Baños 67 CDD 600/5 69/0.115 3.75 0.4 Blq. 5367N CDD 600/5 2 0.4 Blq.

Tulcán

52-062 Tulcán 50/51 IFC51 (Gen. Electric) 600/5 2.5 2.5 11.5 3550/51N IFC53 (Gen. Electric) 600/5 1 4 14

52-042 S. Gabriel 50/51 IFC51 (Gen. Electric) 600/5 2 1.5 8 2850/51N IFC53 (Gen. Electric) 600/5 1 4 7

52-082 S. Miguel de Car 50/51 IFC51 (Gen. Electric)50/51N IFC53 (Gen. Electric)

calculo de MVA: 71706.903433

I43
cot: cambio realizado el 27/07/04 16:30 oficio gxpl-sop-009-04
Page 12: protecciones

AJUSTES DE LOS RELES DE SOBRECORRIENTE DE LOS ALIMENTADORES DEL SNTFECHA DE ACTUALIZACION: 5/30/2005

SUBESTACION POSICION ALIMENTADORRELE

RTC RTP TAP DIAL INST. MVAPROTECCION TIPO

Babahoyo52-0Q2 EMELRIOS

Dos Cerritos

52-012 L1 (Emelgur) 67 DPU 2000 600/5 69/0.115 3.5 1 (MI) 15.75 5067N DPU 2000 600/5 69/0.115 5 0.4s (TD) 15

52-022 L2(Emelgur) 67 SPAS 348C 600/5 69/0.115 3.5 0.07 (MI) 15 5067N SPAS 348C 600/5 69/0.115 5 0.4s (TD) 15

52-032 L3 (Emelgur) 67 SPAS 348C 600/5 69/0.115 3.5 0.07 (MI) 15 5067N SPAS 348C 600/5 69/0.115 5 0.4s (TD) 15

52-042 L4 (Emelgur) 67 SPAS 348C 600/5 69/0.115 3.5 0.07 (MI) 15 5067N SPAS 348C 600/5 69/0.115 5 0.4s (TD)

Machala

52-012 EMELORO 1 67 7SJ622 (SIEMENS) 1200/5 69/0.115 1.6 1.6 10.5 45

67N 7SJ622 (SIEMENS) 1200/5 2 1.1 10.5

52-022 EMELORO 2 67 7SJ622 (SIEMENS) 1200/5 69/0.115 2.65 1.2 15.5 75

67N 7SJ622 (SIEMENS) 1200/5 2 1.2 15

Milagro

52-012 Emelgur ( Duran sur ) 50/51 CDG21 (3 s) 600/5 5 0.15 25 7150/51N CDG23 600/5 1.5 0.2 25

52-032 Milagro 1 (Milagro Norte,yahuachi) 50/51 CDG21 (3 s) 800/5 2.5 0.15 20 4750/51N CDG23 800/5 1.2 0.5 20

52-042 Milagro 2 (Milagro Sur) 50/51 CDG21 (3 s) 800/5 2.5 0.15 20 4750/51N CDG23 800/5 1.2 0.5 20

52-022 Milagro 3 (Marcelino Maridueña ) 50/51 CDG21 (3 s) 800/5 2.5 0.15 20 4750/51N CDG23 800/5 1.2 0.5 25

Pascuales

52-062 Daule (Emelgur) 50/51 CO-9 (Westinghouse) 600/5 4 2 40 5750/51N CO-9 (Westinghouse) 600/5 2 3 30

52-072 La Toma (Emelgur) 50/51 CO-9 (Westinghouse) 600/5 4 3 40 5750/51N CO-9 (Westinghouse) 600/5 2 4 30

52-082 Cerveceria (Emelec) 50/51 CO-9 (Westinghouse) 600/5 5 3 40 7150/51N CO-9 (Westinghouse) 600/5 2 4 30

52-042 V Guayas (Emelgur) 67 IRV9 (Westinghouse) 600/5 69/0.115 5 2 40 7167N IRD9 (Westinghouse) 600/5 2 4 30

52-052 Vergeles (Emelec) 67 IRV9 (Westinghouse) 600/5 69/0.115 5 3 40 7167N IRD9 (Westinghouse) 600/5 2 4 30

52-022 Gas Pascuales

Policentro

52-012 Tres Cerritos 50/51 MCGG62 (GEC) 600/5 6 0.1 (SI) 30 8650/51N 600/5 6 0.075 36

52-022 Cristavid 50/51 MCGG62 (GEC) 600/5 6 0.1 (SI) 30 8650/51N 600/5 6 0.075 36

52-032 Piedrahita 50/51 MCGG62 (GEC) 600/5 6 0.1 (SI) 30 8650/51N 600/5 6 0.075 36

52-052 Fco. De Orellana 50/51 Fuera de servicio 600/5 ###50/51N 600/5

Posorja52-052 Posorja ( Central y s/e Posorja ) 50/51-052 IFC51 BD1A(Gen. Electric) 600/5 2.5 1.2 8 35

50/51N-052 IFC53 BD2A(Gen. Electric) 600/5 2.5 1.4 8.5

52-042 Playas (Ceresita, Playas ) 50/51-042 IFC51 BD1A(Gen. Electric) 600/5 2.5 1.2 7 3550/51N-042 IFC53 BD2A(Gen. Electric) 600/5 2.5 1.2 7

Santa Elena

52-082 Salinas (Salinas, Chichipe, San Vicente) 50/51-082 IFC51 BD1A(Gen. Electric) 600/5 2 2 25 2850/51N-082 IFC53 BD2A(Gen. Electric) 600/5 2 3 20

52-062 Libertad ( Libertad , Santa Rosa ) 50/51-062 IFC51 (Gen. Electric) 600/5 2 2 25 2850/51N-062 IFC53 (Gen. Electric) 600/5 2 3 20

52-042 Colonche ( Colonche, Manglar Alto ) 50/51-042 IFC51 (Gen. Electric) 600/5 2 1.5 11 2850/51N-042 IFC53 (Gen. Electric) 600/5 2 1.4 9

52-022 Chanduy ( Chanduy, Cedege ) 50/51-022 IFC51 (Gen. Electric) 600/5 2 2 8 2850/51N-022 IFC53 (Gen. Electric) 600/5 2 2 8

Trinitaria

52-012 Guasmo (Emelec) 50/51-012 COC1 (Mitsubishi) 800/5 4.5 1 36 8650/51N-012 COC1 (Mitsubishi) 800/5 2 1.5 24

52-062 P. Canals (Emelec) 50/51-062 COC1 (Mitsubishi) 800/5 4.5 1 36 8650/51N-062 COC1 (Mitsubishi) 800/5 2 1.5 24

52-042 Pradera (Emelec) 50/51-042 COC1 (Mitsubishi) 800/5 4.5 1 36 8650/51N-042 COC1 (Mitsubishi) 800/5 2 1.5 24

52-022 Universal (Emelec) 50/51-02250/51N-022

Page 13: protecciones

AJUSTES DE LOS RELES DE SOBRECORRIENTE DE LOS ALIMENTADORES DEL SNTFECHA DE ACTUALIZACION: 5/30/2005

SUBESTACION POSICION ALIMENTADORRELE

RTC RTP TAP DIAL INST. MVAPROTECCION TIPO

Cuenca

52-022 Cuenca # 1 ( s/e Monay ) 67-022 CDD (3 seg) 600/5 69/0.115 6 0.15 40 8667N-022 CDD (3 seg) 600/5 3.5 0.2 40

52-012 Cuenca # 2 ( s/e Ricaurte ) 67 CDD 600/5 69/0.115 6 0.15 30 8667N CDD 600/5 3.5 0.15 25

52-032 Morona ( s/e Gualaceo, Mendez ) 50/51 IFC51 (Gen. Electric) 600/5 2 3 30 2850/51N IFC53 (Gen. Electric) 600/5 1.5 5.5 30

52-042 Azogues 50/51 SPAJ140C (ABB) 600/5 0.5 In 0.1 14.5 3650/51N SPAJ140C (ABB) 600/5 0.2 In 0.4 14.5

Loja52-082 Loja # 1 (Obra Pia) 50/51 IFC51 (Gen. Electric) 300/5 5 2 34 35

50/51N IFC53 (Gen. Electric) 300/5 1.5 9 27

52-062 Loja # 2 (Catamayo) 50/51 IFC51 (Gen. Electric) 300/5 5 2 21 3550/51N IFC53 (Gen. Electric) 300/5 1.5 9 27

Chone

52-012 Calceta 67S-012 MCGG22 400/5 69/0.115 3.75 0.075 9.375 3550/51N-012 IFC51B 400/5 2 1.5 24

52-022 Tosagua 67S-022 MCGG22 400/5 69/0.115 3.75 0.125 18.75 3550/51N-022 IFC51B 400/5 2 2 18

52-032 Chone 67S-032 MCGG22 400/5 69/0.115 3.75 0.125 26.25 3550/51N IFC51B 400/5 2 1.5 30

Esmeraldas 352-L3 Refinería 67 CDD (3s) 600/5 2.5 0.1 20 35

67N CDD 600/5 anul. direcc. 2 0.15 Bloq.

352-L4 EMELESA 67-L4 CDD (3s) 600/5 5 0.15 35 7167N-L4 CDD (CDG13) 600/5 anul. direcc. 2 0.4 Bloq.

Portoviejo

352-L3 Portoviejo 1 (S/E 2) 67-l3 CDD (3s) 600/5 69/0.115 3.75 0.1 11 5367N CDD43 600/5 1 0.9 50

352-L4 Portoviejo 2 (S/E 1) 67 CDD (3s) 600/5 69/0.115 5 0.1 15 7167N CDD43 600/5 1 0.4 Blq.

352-L5 Portoviejo 3 (S/E 1) 67 CDD41 (3s) 600/5 69/0.115 5 0.1 15 7167N CDD43 600/5 1 0.4 Blq.

352-L6 Portoviejo 4 (Jipijapa) 67 CDD41 600/5 69/0.115 2.5 0.15 15 3567N CDD43 600/5 1 0.2 Blq.

Quevedo52-012 Quevedo Norte 50/51-012 CO-8I (Mitsubishi) 600/5 3 1.4 20 43

50/51N-012 CO-9I (Mitsubishi) 600/5 2 4.5 20

52-022 Quevedo Sur 50/51 CO-8I (Mitsubishi) 600/5 3 1.4 25 4350/51N CO-9I (Mitsubishi) 600/5 2 3.8 25

Sto. Domingo52-022 Sto. Domingo # 1(DOM1 QUITO ) 50/51 CDG 21 (3s) 400/5 3.75 0.15 56 35

50/51N CDG23 400/5 4 0.3 42

52-012 Sto. Domingo # 2 (DOM2, QUEVEDO) 50/51 CDG 21 (3s) 400/5 5 0.1 48 4750/51N CDG23 400/5 4 0.3 43

Tena

52-012 Puyo 67-012 7SJ622 (SIEMENS) 600/5 69/0.115 0.5 - 3 7

67N-012 7SJ622 (SIEMENS) 600/5 0.5 - 4