losa aligerada 2.pdf

2
b = 10.00 cm d = 17.00 cm f'c = 210.00 kg/cm² fy = 4200.00 kg/cm² Mu = 0.44 Tn.m RESULTADOS w = 0.085 p = 0.0042 As Calculado = 0.72 cm² AS min = 0.31 cm² USAMOS = 0.72 cm² VARILLAS A USAR TRAMO 1 - 2 # varillas Diametro ARA 1 1/2 pulg 1.27 1.27 VERDADERO Apoyo 1 1 Ø 3/8" Tramo 1 - 2 1 Ø 1/2" Apoyo 2 1 Ø 1/2" Tramo 2 - 3 1 Ø 1/2" Apoyo 3 1 Ø 1/2" Tramo 3 - 4 1 Ø 1/2" Apoyo 4 1 Ø 1/2" Tramo 4- 5 1 Ø 1/2" Apoyo 4 1 Ø 3/8" Diseño Losa Aligerada

Upload: anthony-villegas-calero

Post on 04-Sep-2015

229 views

Category:

Documents


0 download

TRANSCRIPT

  • b = 10.00 cmd = 17.00 cmf'c = 210.00 kg/cmfy = 4200.00 kg/cmMu = 0.44 Tn.m

    RESULTADOSw = 0.085p = 0.0042

    As Calculado = 0.72 cmAS min = 0.31 cmUSAMOS = 0.72 cm

    VARILLAS A USAR TRAMO 1 - 2 # varillas Diametro ARA

    1 1/2 pulg 1.271.27 VERDADERO

    Apoyo 1 1 3/8"Tramo 1 - 2 1 1/2" Apoyo 2 1 1/2"Tramo 2 - 3 1 1/2" Apoyo 3 1 1/2"Tramo 3 - 4 1 1/2" Apoyo 4 1 1/2"Tramo 4- 5 1 1/2" Apoyo 4 1 3/8"

    Diseo Losa Aligerada

  • EJE DE REFERENCIA DEL PLANO

    1 2 3 4 5METRADO DE CARGAS

    tn/m2 m tn/mpeso propio aligerado 0.3 0.4 0.12

    piso terminado 0.1 0.4 0.04CM 0.16

    Wcv (departamentos) 0.2 0.4 0.08CV 0.08

    Wu= 0.36 tn/m

    EJE 1-1