juntas-tuberias vrv-iii r410a (nov 2007)
TRANSCRIPT
7/23/2019 Juntas-Tuberias VRV-III R410A (Nov 2007)
http://slidepdf.com/reader/full/juntas-tuberias-vrv-iii-r410a-nov-2007 1/2
TIPO J20 J21 J22 J23
INDICE <200 >=200-290 >=290-640 >=640DERIVACION KHRQ22M20T7 KHRQ22M29T9 KHRQ22M64T7 KHRQ22M75T7
Primera Junta RXYQ5P;RXYSQ 4,5 y 6P
RXYQ8,10P RXYQ12 a 22P RXYQ24 a 54P
TIPO C20 C21 C22 C23
INDICE <200 >=200-290 >=290-640 >=640COLECTOR KHRQ22M64H7 KHRQ22M75H7
Numero Uds ExterioresKit de Conexión
TIPO J24 J25 J26 J27
INDICE <200 >=200-290 >=290-640 >=640DERIVACION KHRQ23M20T7 KHRQ23M29T7 KHRQ23M64T7 KHRQ23M75T7Primera Junta REYQ8,10P REYQ12 a 22P REYQ24 a 48P
TIPO C24 C25 C26 C27
INDICE <200 >=200-290 >=290-640 >=640COLECTOR KHRQ23M64H7 KHRQ23M75H7
Numero Uds ExterioresKit de Conexión
KIT DE CONEXIÓN DE EXTERIORES (INCLUYE LINEA DE ACEITE)
2 3
BHFQ23P907 BHFQ23P1357
2 3
BHFQ22P1007 BHFQ22P1517
COLECTORES REFNET
KHRQ23M29H7
SISTEMA DE DERIVACION REFNET
RECUPERACION DE CALOR (REYQ8P a REYQ48P)DERIVACIONES REFNET
SOLO FRIO (RXQ5P a RXQ18P) BOMBA DE CALOR (RXYQ5P a RXYQ54P)
DERIVACIONES REFNET
COLECTORES REFNET
KHRQ22M29H7KIT DE CONEXIÓN DE EXTERIORES
12 Noviembre 2007
7/23/2019 Juntas-Tuberias VRV-III R410A (Nov 2007)
http://slidepdf.com/reader/full/juntas-tuberias-vrv-iii-r410a-nov-2007 2/2
mm pulg mm pulg
Q 6,4 1/4' 12,7 1/2' FX*Q..20 a 50 NO Q
R 9,5 3/8' 15,9 5/8'FX*Q..63 a 125
RXYQ5P - RXYSQ 4 y 5P< 150 R
S 9,5 3/8' 19,1 3/4'FX*Q..200
RXYQ8P - RXYS 6P≥ 150 - 200 S
T 9,5 3/8' 22,2 7/8' FX*Q..250 - RXYQ10P ≥ 200 - 290 T
U 12,7 1/2' 28,6 1 1/8' RXYQ12 a 16P ≥ 290 - 420 U
W 15,9 5/8' 28,6 1 1/8' RXYQ18 a 22P ≥ 420 - 640 W
X 15,9 5/8' 34,9 1 3/8' RXYQ24P NO X
Y 19,1 3/4' 34,9 1 3/8' RXYQ26 a 34P ≥ 640 - 920 Y
Z 19,1 3/4' 41,3 1 5/8' RXYQ36 a 54P ≥ 920 Z
mm pulg mm pulg
A 6,4 1/4' 12,7 1/2' FX*Q..20 a 50 NO A
B 9,5 3/8' 15,9 5/8' FX*Q..63 a 125 < 150 B
C 9,5 3/8' 19,1 3/4' FX*Q..200 ≥ 150 - 200 C
D 9,5 3/8' 22,2 7/8' FX*Q..250 ≥
200 - 290 D
mm pulg mm pulg mm pulg
E 6,4 1/4' 9,5 3/8' 12,7 1/2' NO NO E
F 9,5 3/8' 12,7 1/2' 15,9 5/8' NO < 150 F
G 9,5 3/8' 15,9 5/8' 19,1 3/4' REYQ8P ≥ 150 - 200 G
H 9,5 3/8' 19,1 3/4' 22,2 7/8' REYQ10P ≥ 200 - 290 H
I 12,7 1/2' 19,1 3/4' 28,6 1 1/8' REYQ12P ≥ 290 - 420 I
J 12,7 1/2' 22,2 7/8' 28,6 1 1/8' REYQ14-16P NO J
K 15,9 5/8' 22,2 7/8' 28,6 1 1/8' REYQ18P NO K
L 15,9 5/8' 28,6 1 1/8' 28,6 1 1/8' REYQ20-22P ≥ 420 - 640 L
M 15,9 5/8' 28,6 1 1/8' 34,9 1 3/8' REYQ24P NO M
N 19,1 3/4' 28,6 1 1/8' 34,9 1 3/8' REYQ26 a 34P ≥ 640 - 920 N
O 19,1 3/4' 28,6 1 1/8' 41,3 1 5/8' REYQ36P ≥ 920 O
P 19,1 3/4' 34,9 1 3/8' 41,3 1 5/8' REYQ38 a 48P NO P
ÍNDICE NOMBRENOMBRE LÍQUIDO
NOMBRE
TRAMOS A 2 TUBOS (AGUAS ABAJO DE LA BSVQ)
2 TUBOS
RECUPERACIÓN DE CALOR (REYQ-P)
MODELOSLÍQUIDO GAS
¡¡IMPORTANTE!! PARA DIMENSIONAR TUBERÍAS AGUAS ABAJO DE LAS BSVQ, SEUTILIZA LA TABLA DE TRAMOS A DOS TUBOS.
NOMBRE ÍNDICE
CIRCUITOS FRIGOR FICOS R410-A
MODELOS ÍNDICE NOMBRELÍQUIDO
FRIO SOLO (RXQ-P) Y BOMBA DE CALOR (RXYQ-P)
GASNOMBRE
PARA CUALQUIER DUDA CONSULTE CON EL DEPARTAMENTO TÉCNICO.
· uan o a on tu e u va ente tota e as tu er as sea e m o m s, se e e aumentar e tama o e a nea r nc a e u o ( o amenteNOTAS IMPORTANTES:
Estos datos son válidos siempre y cuando la longitud equivalente (entre la unidad exterior y la unidad
interior más desfavorable) sea inferior a 90 metros.
No permitir que el tamaño de ninguna tubería sea superior al tamaño escogido para la tubería de la línea principal (desde la unidad
exterior hasta la primera derivación) elegido según el modelo de unidad exterior.
TUBER A DE ECUALIZACI N: REYQ18-48P ………. 19,1 mm - 3/4'
DESCARGA GAS MODELOS
TRAMOS A 3 TUBOS (AGUAS ARRIBA DE LA BSVQ)
12 de Noviembre de 2007