CALCULO DEL SISTEMA DE ABASTECIMIENTO DE AGUA POTABLE 1.- PROYECT A.- POBLACION ACTUAL (ESTIMADO) . 206 AÑO BASE 2013(PADRÓN) 209 AÑO CERO 2014 B.- TASA DE CRECIMIENTO (%) 1.25 C.- PERIODO DE DISEÑO (AÑOS) 20 D.- POBLACION FUTURA 268 Pf = Po * ( 1+ r*t/100 ) E.- DOTACION (LT/HAB/DIA) 120.00 F.- CONSUMO PROMEDIO ANUAL (LT/SEG) Q = Pob.F.* Dot./86,400 A 0 AÑOS 0.29 25.08 QF = Pob.F.* Dot./86,400 A 20 AÑOS 0.37 32.16 G.- CONSUMO MAXIMO DIARIO (LT/SEG) Qmd = 1.30 * QF 0.65 H.- CAUDAL DE LA FUENTE (LT/SEG) 1.82 157.25 I.- VOLUMEN DEL RESERVORIO (M3) V = 0.20 * Qmd *86400/1000 11.15 A UTILIZAR : 15.00 J.- CONSUMO MAXIMO HORARIO (LT/SEG) Qmh = 2 * Qmd = 2.60 Q 1.29 LINEA DE CONDUCCION TRAMO Hf PRESION CAPT. 1 837.32 837.32 PTO 2 785.00 0.740 0.65 70.70 1.03 1.50 0.57 8.41 828.91 43.91 C-7.5 52.32 C-7.5 PTO2 785.00 785.00 PTO3 730.00 0.312 0.65 176.28 0.85 1.00 1.27 25.54 759.46 29.46 C-5 55.00 C-10 PTO3 730.00 730.00 PTO4 675.00 0.129 0.65 426.36 0.71 1.00 1.27 10.56 719.44 44.44 C-7.5 55.00 C-10 “MEJORAMIENTO Y AMPLIACION DEL SERVICIO DE AGUA POTABLE Y DISPOSICION SANITARIA DE EXCRETAS EN EL C.P. EL MILAGRO, DISTRITO DE PICHANAQUI, PROVINCIA DE CHANCHAMAYO, DEPARTAMENTO JUNIN”. NIVEL DINAMICO LONGITUD (KM) CAUDAL DEL TRAMO PENDIENT E DIAMETRO (") DIAM. COMERCI AL VELOCIDAD FLUJO ALTURA PIEZOMETRI CA CLASE DE TUBERIA PRESION ESTATICA

Upload: nilton-hcoca

Post on 11-May-2017

229 views

Category:

Documents


6 download

TRANSCRIPT

CALCULO DEL SISTEMA DE ABASTECIMIENTO DE AGUA POTABLE

1.- PROYECTO

A.- POBLACION ACTUAL (ESTIMADO) . 206 AÑO BASE 2013(PADRÓN)

209 AÑO CERO 2014

B.- TASA DE CRECIMIENTO (%) 1.25

C.- PERIODO DE DISEÑO (AÑOS) 20

D.- POBLACION FUTURA 268

Pf = Po * ( 1+ r*t/100 )

E.- DOTACION (LT/HAB/DIA) 120.00

F.- CONSUMO PROMEDIO ANUAL (LT/SEG)

Q = Pob.F.* Dot./86,400 A 0 AÑOS 0.29 25.08

QF = Pob.F.* Dot./86,400 A 20 AÑOS 0.37 32.16

G.- CONSUMO MAXIMO DIARIO (LT/SEG)

Qmd = 1.30 * QF 0.65

H.- CAUDAL DE LA FUENTE (LT/SEG) 1.82 157.25

I.- VOLUMEN DEL RESERVORIO (M3)

V = 0.20 * Qmd *86400/1000 11.15

A UTILIZAR : 15.00

J.- CONSUMO MAXIMO HORARIO (LT/SEG)

Qmh = 2 * Qmd = 2.60 Q 1.29

LINEA DE CONDUCCION

TRAMO Hf PRESION

CAPT. 1 837.32 837.32

PTO 2 785.00 0.740 0.65 70.70 1.03 1.50 0.57 8.41 828.91 43.91 C-7.5 52.32 C-7.5PTO2 785.00 785.00

PTO3 730.00 0.312 0.65 176.28 0.85 1.00 1.27 25.54 759.46 29.46 C-5 55.00 C-10PTO3 730.00 730.00

PTO4 675.00 0.129 0.65 426.36 0.71 1.00 1.27 10.56 719.44 44.44 C-7.5 55.00 C-10

“MEJORAMIENTO Y AMPLIACION DEL SERVICIO DE AGUA POTABLE Y DISPOSICION SANITARIA DE EXCRETAS EN EL C.P. EL MILAGRO, DISTRITO DE PICHANAQUI, PROVINCIA DE CHANCHAMAYO, DEPARTAMENTO JUNIN”.

NIVEL DINAMICO

LONGITUD (KM)

CAUDAL DEL

TRAMO

PENDIENTE

DIAMETRO (")

DIAM. COMERCI

AL

VELOCIDAD FLUJO

ALTURA PIEZOMETRI

CA

CLASE DE TUBERIA

PRESION ESTATICA

PTO4 675.00 675.00

PTO5 620.00 0.138 0.65 398.55 0.72 1.00 1.27 11.30 663.70 43.70 C-7.5 55.00 C-10PTO 5 620.00 620.00

PTO 6 565.00 0.249 0.65 220.88 0.82 1.00 1.27 20.38 599.62 34.62 C-5 55.00 C-10PTO 6 565.00 565.00

PTO 7 510.00 0.228 0.65 241.23 0.80 1.00 1.27 18.67 546.33 36.33 C-7.5 55.00 C-10PTO 7 510.00 510.00

PTO 8 455.00 0.154 0.65 357.14 0.74 1.00 1.27 12.61 497.39 42.39 C-7.5 55.00 C-10

LINEA DE ADUCCION

TRAMO Hf PRESION

RESERVORIO 455.00 455.00

PTO- 8.1 438.00 0.949 0.21 17.91 0.89 1.50 0.18 1.35 453.65 15.65 C-5 17.00 C-5RESERVORIO 455.00 455.00

PTO-12 445.80 0.214 1.17 42.99 1.43 1.50 1.03 7.31 447.69 1.89 C-5 9.20 C-5

LINEA DE DISTRIBUCION COTA DE TERRENO COTA PIEZOM.

TRAMO INICIAL FINAL LONG. K Q hf D D Comerc. V ideal V INICIAL FINAL PRESIONCOMP( msnm ) ( msnm ) ( m ) (Metros) (lts./ s.) ( m/m. ) ( pulg. ) ( pulg. ) (m./s.) (m./s.) ( m. ) ( msnm ) ( msnm ) INICIO SALIDA

sistema 1PTO - 8.1 PTO - 9 438.00 427.80 198.65 9 0.354 0.477 0.051347 1.00 1 0.412 0.942 9.052 455.00 445.95 17.00 18.15 OKPTO -9 PTO-10 427.80 427.00 46.17 2 1.000 0.300 0.017327 1.05 1 1/2 0.445 0.263 0.124 445.95 445.82 18.15 18.82 OKPTO 9 PTO-11 427.80 424.00 25.86 2 1.000 0.300 0.146945 0.67 1 1/2 0.445 0.263 0.070 445.82 445.75 18.02 21.75 OKPTO 12 PTO13 445.80 438.00 68.00 54 0.137 1.106 0.114706 1.16 1 1/2 0.445 0.970 2.046 455.00 452.95 9.20 14.95 OKPTO-13 PTO-14 438.00 433.00 83.00 54 0.137 1.106 0.060241 1.33 1 1/2 0.445 0.970 2.497 452.95 450.46 14.95 17.46 OKPTO14 PTO-15 433.00 431.50 87.00 54 0.137 1.106 0.017241 1.73 1 1/2 0.445 0.970 2.618 450.46 447.84 17.46 16.34 OKPTO-15 PTO-16 431.50 429.50 85.00 54 0.137 1.106 0.023529 1.62 1 1/2 0.445 0.970 2.558 447.84 445.28 16.34 15.78 OKPTO -16 PTO -17 429.50 429.00 82.00 52 0.140 1.065 0.006098 2.12 1 1/2 0.445 0.934 2.301 445.28 442.98 15.78 13.98 OKPTO -17 PTO-18 429.00 427.30 85.00 51 0.141 1.045 0.020000 1.64 1 1/2 0.445 0.916 2.301 442.98 440.68 13.98 13.38 OKPTO-18 PTO-19 427.30 426.00 85.00 51 0.141 1.045 0.015294 1.74 1 1/2 0.445 0.916 2.301 440.68 438.38 13.38 12.38 OKPTO-16 PTO-30 429.50 430.00 53.00 2 1.000 0.300 0.009434 1.20 1 1/2 0.445 0.263 0.143 445.28 445.14 15.78 15.14 OKPTO-17 PTO-31 429.00 428.00 49.00 1 0.150 0.150 0.020408 0.78 1 0.412 0.296 0.262 442.98 442.72 13.98 14.72 OKPTO-18 PTO-32 427.30 427.00 41.00 1 0.150 0.150 0.007317 0.97 1 0.412 0.296 0.219 440.68 440.46 13.38 13.46 OKPTO-12 PTO-27 446.00 437.00 59.00 54 0.137 1.106 0.152542 1.09 1 1/2 0.445 0.970 1.775 455.00 453.22 9.00 16.22 OKPTO-27 PTO-28 437.00 436.00 49.00 54 0.137 1.106 0.020408 1.67 1 1/2 0.445 0.970 1.474 455.00 453.53 18.00 17.53 OKPTO-27 PTO-26 437.00 434.50 59.00 54 0.137 1.106 0.042373 1.43 1 1/2 0.445 0.970 1.775 455.00 453.22 18.00 18.72 OKPTO-26 PTO-25 434.50 432.50 85.00 54 0.137 1.106 0.023529 1.62 1 1/2 0.445 0.970 2.558 453.22 450.67 18.72 18.17 OKPTO-25 PTO-29 432.50 432.10 29.00 54 0.137 1.106 0.013793 1.81 1 1/2 0.445 0.970 0.873 450.67 449.79 18.17 17.69 OKPTO-25 PTO-24 432.50 430.50 86.00 54 0.137 1.106 0.023256 1.63 1 1/2 0.445 0.970 2.588 450.67 448.08 18.17 17.58 OKPTO-24 PTO-23 430.50 429.80 84.00 54 0.137 1.106 0.008333 2.02 1 1/2 0.445 0.970 2.528 448.08 445.55 17.58 15.75 OKPTO-23 PTO-22 429.80 428.00 83.00 52 0.140 1.065 0.021687 1.63 1 1/2 0.445 0.934 2.329 445.55 443.22 15.75 15.22 OKPTO-22 PTO-21 427.00 426.00 83.00 51 0.141 1.045 0.012048 1.83 1 1/2 0.445 0.916 2.247 443.22 440.98 16.22 14.98 OKPTO-21 PTO-20 427.00 426.00 90.00 2 1.000 0.300 0.011111 1.16 1 1/2 0.445 0.263 0.242 440.98 440.73 13.98 14.73 OK

El criterio de asignaciòn de caudales en tramos terminales es e de Simultaneidad de uso: Q = 0.15xNxK; en donde:0.15 es el caudal en litros por segundo asignado a una conexión domiciliaria. K= (N-1)^-0.5N es el nùmero de conexiones domiciliarias del tramo.K es el coeficiente de simultaneidad, nunca infrior a 0.2.

DATOS :Total Edificaciones 63 vi.Población Actual (Pa) 206.00 hab.Dotación (d) 120 lts./hab./díaConsumo Máximo Diario ( Qmd ) 0.65 lts./seg.Consumo Máximo Horario ( Qmh ) 1.29 lts./seg.Volúmen del Reservorio ( V ) 15 m3.Consumo Unitario ( Q unit. ) 0.020 lts./seg/viv. 0.204820694

NIVEL DINAMICO

LONGITUD (KM)

CAUDAL DEL

TRAMO

PENDIENTE

DIAMETRO (")

DIAM. COMERCI

AL

VELOCIDAD FLUJO

ALTURA PIEZOMETRI

CA

CLASE DE TUBERIA

PRESION ESTATICA

Viviendas Alimentadas

Hf Tramo