MiCOM C264 Hardware Presentation
PCL
PACiS PACiS PACiS PACiS TechnicalTechnicalTechnicalTechnical TrainingTrainingTrainingTraining
CS&P CS&P CS&P CS&P Support TeamSupport TeamSupport TeamSupport Team
-
Schneider Electric 2- CS&P C264 Hardware Presentation E01
Generalities Rack Hardware Main Boards Description I/O Boards description Communication Boards
Content
-
Schneider Electric 3- CS&P C264 Hardware Presentation E01
Generalities Rack Hardware Main Boards Description I/O Boards description Communication Boards
Content
-
Schneider Electric 4- CS&P C264 Hardware Presentation E01
MiCOM C264C4U / 170mm / 40 TE
with 4 or 6 slots for I/O boards
MiCOM C2644U / 170mm / 80 TE
with 14 or 15 slots for I/O boards
Modular Racks
-
Schneider Electric 5- CS&P C264 Hardware Presentation E01
Modular Construction (Back)Easy to Install
Removable connectors for 0.8 to 2.5 mm2 wires I/Os
boards &Power supply
Optional connectorsfor 4 mm2 wires
direct CT/VT connection
Optional : optic/Ethernet IED Com,
IRIG B
Connector Screwing
Connections
Shed Contacts shouldbe grounded
-
Schneider Electric 6- CS&P C264 Hardware Presentation E01
Boards ListShort designation Designation DetailsGHU 2xx Graphic Humain Unit Front panel / LCD
BIU 2x1 Basic Interface Unit Power supply and 2 RS
CPU 2x0 Computer Processing Unit
TMU 2xx Transducerless Measurement Unit4 CT / 4-5 VT DSP 2xx Digital Signal Processor TMU Signal
DSPIO 2xx Digital Signal Processor Input Output TMU Signal + 5 DI / 5 DO (1 slot)
DIU 2xx Digital Input Unit 16 DI
DOU 2xx Digital Output Unit 10 DO
CCU 2xx CB Control Unit 8 DI + 4 DO
AIU 2xx Analog Inputs Unit (4) 8 AI
AOU 2xx Analog Output Unit 4 AO
SWx 2xx SWitch Ethernet max 6 ports SWU 2xx SWitch Unit (standard switch) 2 Fx + 4 Tx
SWR 2xx SWitch Ring Redundancy 2 Fx Redundant + 4 Tx
SWD 2xx SWitch Dual Hamming redundancy 2 Fx Redundant + 4 Tx
CAS 2xx Package CASe (rack 4U) Package CASe (rack 4U)
FBP 2xx Front Back Plane ( Bus ) Front Back Plane ( Bus )
-
Schneider Electric 7- CS&P C264 Hardware Presentation E01
6 (48 AI)6 (48 AI)AIU211 (8 AI, mA)
6 (24AO + 24DO)6 (24AO + 24DO)AOU200 (4AO + 4DO)
C264-P: 1 (4CT, 4VT)C264-P : 1 (4CT, 4VT)TMU210
1 (4 CT, 5 VT)1 (4 CT, 5 VT)TMU220
6 (24 AI)6 (24 AI)AIU201 (4 AI, mA or V)
15 (120 DI + 60 DO)6 (48 DI + 24 DO)CCU211 (8 DI + 4 DO)
15 (150 DO)6 (60 DO)DOU201 (10DO)
15 (240 DI)6 (96 DI)DIU220 (16DI)
15 (240 DI)6 (96 DI)DIU211 (16DI)
11GHU 2xx :20x=LCD, 21x=no LCD, 22x=remote
11CPU260 (2RS + RJ45) / CPU270 options :Optic Fx, IRIG-B, DSP
11BIU 241 (power + 2RS)
MiCOM C26414/15 slots
MiCOM C264C4/6 slots Capabilities
With CPU270, boards 2x1 address is defined in SCE (jumpers optional) :DIU211, CCU211
-
Schneider Electric 8- CS&P C264 Hardware Presentation E01
Example of 80TE Rack Content Front Automatic Production Placement
BIU 241
B
CPU260
C
SWX
D
AIU201
_@0
E
AIU210
_@0
F
AIU210
_@1
G
DOU
200_@
0
H
DOU
200_@
1
I
DOU
200_@
2
J K L
CCU200
_@2
M
CCU200
_@1
N
CCU200
_@0
O
DIU200
_@2
PDIU
200_@
1Q
DIU200
_@0
A
BIU 241
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15
BIU 241
CPU260
SWX
AIU201
_@0
AIU210
_@0
AIU210
_@1
DOU
200_@
0
DOU
200_@
1
DOU
200_@
2
CCU200
_@2
CCU200
_@1
CCU200
_@0
DIU200
_@2
DIU200
_@1
DIU200
_@0
BIU 241
1 2 3 4 5 6 7 8 9 10 11 12 13 14
CT / VT
TMU
200
BIU 241
CPU260
SWX
AIU201
_@0
AIU210
_@0
AIU210
_@1
DOU
200_@
0
DOU
200_@
1
DOU
200_@
2
CCU200
_@2
CCU200
_@1
CCU200
_@0
DIU200
_@2
DIU200
_@1
DIU200
_@0
BIU 241
CT / VT
TMU
210
DSP IO
B C D E F G H I J K L M N O P QA
B C D E F G H I J K L M N O P QA
Basic
With TMU200
With TMU210
ProtectionDSP IO Slot
1 2 3 4 5 6 7 8 9 10 11 12 13
-
Schneider Electric 9- CS&P C264 Hardware Presentation E01
Example of 40TE Rack Content Front Automatic Production Placement
B C D E F G HA
BIU 241
CPU260
SWX
AIU210
_@0
DOU
200_@
0
CCU200
_@0
DIU200
_@1
DIU200
_@0
BIU 241
1 2 3 4 5 6
BIU 241
CPU260
SWX
DOU
200_@
0
DIU200
_@1
DIU200
_@0
BIU 241
1 2 3 4
CT / VT
TMU
200
BIU 241
CPU260
SWX
DOU
200_@
0
DIU200
_@0
BIU 241
CT / VT
TMU
210
DSP IO
1 2 3
B C D E F G HA
B C D E F G HA Basic
With TMU200
With TMU210ProtectionDSP IO Slot
-
Schneider Electric 10- CS&P C264 Hardware Presentation E01
Generalities Rack Hardware Main Boards Description I/O Boards description Communication Boards
Content
-
Schneider Electric 11- CS&P C264 Hardware Presentation E01
Rack Mounting Cubicle Mounting (6 screws) on 19 Rack LCD Removal (6 Poz drive 10)
CabinetMounting
19 Rack Support
Front Face Screwing
C264 Screwing
-
Schneider Electric 12- CS&P C264 Hardware Presentation E01
BIU
CPU
DIU DOU CCU AIU
Board Number Board NameBus
Rack / Board Overview Board + rail removing (torque drive 10)
-
Schneider Electric 13- CS&P C264 Hardware Presentation E01
Each board has an address, unique per type, starting from 0by jumpers
CLOSED = 0 OPEN (see below)
If Open : address = address + 1If Open : address = address + 2If Open : address = address + 4If Open : address = address + 8
Rules :
Example :=> + 2
=> + 8=> 2 + 8 = 10
Board Number (Address)
-
Schneider Electric 14- CS&P C264 Hardware Presentation E01
Generalities Rack Hardware Main Boards Description I/O Boards description Communication Boards
Content
-
Schneider Electric 15- CS&P C264 Hardware Presentation E01
Front Faces
GHU200 40 TE Front Panel Leds + L/R switch + Graphic Display LCD 2071004GHU210 40 TE Front Panel Leds + L/R switch 2071010GHU220 40 TE Front Panel : Simple Blind 2071174GHU201 80 TE Front Panel : Leds + L/R switch + Graphic Display LCD 2070962GHU211 80TE Front Panel : Leds + L/R switch 2070966GHU221 80 TE Front Panel : Simple Blind 2071172
RJ11
-
Schneider Electric 16- CS&P C264 Hardware Presentation E01
Main characteristics : Power Supply (4 possible ranges : 24 / 48 / 110 / 220V) 1 Watchdog contact 2 DI & 2 DO used for redundancy RS1 (232/485) RS2 (232/422/485)
Basic Interface Unit BIU241
-
Schneider Electric 17- CS&P C264 Hardware Presentation E01
Main characteristics : 32-bit Power PC-base processor (80 MHz) DRAM (64Mo) & Flash (16Mo) VxWorks for RT OS Powerful DSP TMS320C6713 for CT/VT Ethernet-Based 10/100Base-FX or Base-TX 2 Serial links up to 64 Kbit/s RS232 IRIG-B port Bus
CentralProcessing Unitboard
CPU260
RJ-45(female)
1 2 3 4 5 6 7 8
RS232
#
Serial
link 4GND
TXD / T+
RXD / T-
DCD
RTS
CTS8
7
5
3
2
1
10/100 Base-Tx
Ethernet-based link
RS232
#
Serial
link 3GND
TXD / T+
RXD / T-
DCD
RTS
CTS8
7
5
3
2
1
OPTIONNAL LINKS:
10/100 Base-Fx
Ethernet-based link
1
2
3
4
5
6
7
8
9
1
2
3
4
5
6
7
8
9
IRIG B
Central Processing Unit CPU260
-
Schneider Electric 18- CS&P C264 Hardware Presentation E01
Main characteristics : 32-bit Power PC-base processor (260 MHz) More DRAM (128Mb) and Flash (64Mb) VxWorks for RT OS Powerful DSP TMS320C6713 for CT/VT 2 Ethernet ports 10/100Base-TX 2 Serial links up to 64 Kbit/s RS232 IRIG-B port New bus
Good Practice : In Boot Parameters from CMT, make sure IP address 1 and IP address 2 are belonging to different domains.
CentralProcessing Unitboard
CPU270
RJ-45(female)
1 2 3 4 5 6 7 8
RS232
#
Serial
link 4GND
TXD / T+
RXD / T-
DCD
RTS
CTS8
7
5
3
2
1
10/100 Base-Tx
Ethernet-based link
RS232
#
Serial
link 3GND
TXD / T+
RXD / T-
DCD
RTS
CTS8
7
5
3
2
1
10/100 Base-Tx
Ethernet-based link
1
2
3
4
5
6
7
8
9
1
2
3
4
5
6
7
8
9
IRIG B
RJ-45(female)
1 2 3 4 5 6 7 8
!
Central Processing Unit CPU270
-
Schneider Electric 19- CS&P C264 Hardware Presentation E01
Generalities Rack Hardware Main Boards Description I/O Boards description Communication Boards
Content
-
Schneider Electric 20- CS&P C264 Hardware Presentation E01
Main characteristics A01 Vnom : 24-30 Vdc A02 Vnom : 40 Vdc (range 20 to 60 Vdc) A03 Vnom : 100 Vdc (range 40 to 150 Vdc) A04 Vnom : 220 Vdc (range 180 to 264 Vdc)
16 Opto Isolated DI but 40% Thresholds Board addressing
SPS, DPSSCT, DCTDM
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
PIN
Digital Input Unit
board
DIU20x
VIN
-
VIN
-- -
++ DI8DI7
VIN
-
VIN
-- -
++ DI2DI1
VIN
-
VIN
-- -
++ DI4DI3
VIN
-
VIN
-- -
++ DI6DI5
VIN
-
VIN
-- -
++ DI10DI9
VIN
-
VIN
-- -
++ DI12DI11
VIN
-
VIN
-- -
++ DI14DI13
VIN
-
VIN
-- -
++ DI16DI15
Signal inputs
Digital Input Unit DIU200
-
Schneider Electric 21- CS&P C264 Hardware Presentation E01
Main characteristics Capabilities : 40TE 80TE A01 Vnom : 24-30 Vdc 2 8 A02 Vnom : 40 Vdc (range 20 to 60 Vdc) 6 15 A03 Vnom : 100 Vdc (range 40 to 150 Vdc) 3 10 A04 Vnom : 220 Vdc (range 180 to 264 Vdc) 1 5
1 ms Time-tag16 Opto Insulated DI 2kV (1mn)Peak > 25mA when Set
SPS, DPSSCT, DCTDM
Digital Input Unit DIU210
-
Schneider Electric 22- CS&P C264 Hardware Presentation E01
Main characteristics : Accept all Nominal Voltages
according on jumpers definition
1 ms Time-tag Opto Isolated (2kV during 1mn) 27mA peak for 2ms Board Auto-addressed (CPU3)
16 DI usable for :SPS, DPSSCT, DCTDM
Board address
Digital Input Unit DIU211
-
Schneider Electric 23- CS&P C264 Hardware Presentation E01
Main characteristics : Accept 2 different Nominal Voltages :
VA, nom : 48 Vdc (range 20 to 60 Vdc)VA, nom : 110 Vdc (range 40 to 125 Vdc)
1 ms Time-tag Opto Isolated (2kV)
16 DI usable for :SPS, DPSSCT, DCTDM
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
PIN
Digital Input Unit
board
DIU20x
VIN
-
VIN
-- -
++ DI8DI7
VIN
-
VIN
-- -
++ DI2DI1
VIN
-
VIN
-- -
++ DI4DI3
VIN
-
VIN
-- -
++ DI6DI5
VIN
-
VIN
-- -
++ DI10DI9
VIN
-
VIN
-- -
++ DI12DI11
VIN
-
VIN
-- -
++ DI14DI13
VIN
-
VIN
-- -
++ DI16DI15
Signal inputs
Digital Input Unit DIU220
-
Schneider Electric 24- CS&P C264 Hardware Presentation E01
Main characteristics 8 outputs NO contacts and 2 outputs NO/NC UN 250 Vdc / 230 Vac Isol. 2kV Making 70 VA/W 2.5 A permanent 100 A peak for 30ms
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
PIN
Digital Output Unitboard
DOU200
Signal outputs
DO 1
DO 2
DO 3
DO 4
DO 5
DO 6
DO 7
DO 8
DO 10
DO 9
Digital output Board DOU200
-
Schneider Electric 25- CS&P C264 Hardware Presentation E01
Main characteristics : 10 DO (8 NO contacts & 2 NO/NC contacts) UN 250 Vdc / 230 Vac Isolation 2kV Making Power : 140 VA/W Permanent : 5 A Peak for 30ms : 250 A
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
PIN
Digital Output Unitboard
DOU200
Signal outputs
DO 1
DO 2
DO 3
DO 4
DO 5
DO 6
DO 7
DO 8
DO 10
DO 9
Digital output Board DOU201
-
Schneider Electric 26- CS&P C264 Hardware Presentation E01
DI main characteristics like DIU2xxDO main characteristics :
4 power output relays (2 NO contacts each)
Making Power 140 VA/W Permanent : 5A 500ms : 30A 30ms : 250A
8DI and 4DO
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
PIN
Circuit breakerControl Unitboard
CCU 200
Signal outputs
VIN
-
VIN
-- -
++DI2DI1
VIN
-
VIN
-- -
++DI4DI3
VIN
-
VIN
-- -
++DI6DI5
VIN
-
VIN
-- -
++DI8DI7
Signal inputs
CO 2
CO 1B
A
B
A
CO 4
CO 3B
A
B
A
CB Control Unit CCU200
-
Schneider Electric 27- CS&P C264 Hardware Presentation E01
CB Control Unit (8DI and 4DO) DI Voltage selected by jumpers DI Trigger threshold selected by jumpers 4 DO Double Cut Board Auto-addressed (CPU3) 1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
PIN
Circuit breakerControl Unitboard
CCU 211
Signal outputs
VIN
-
VIN
-- -
++DI2DI1
VIN
-
VIN
-- -
++DI4DI3
VIN
-
VIN
-- -
++DI6DI5
VIN
-
VIN
-- -
++DI8DI7
Signal inputs
CO 2
CO 1B
A
B
A
CO 4
CO 3B
A
B
A
CB Control Unit CCU211
-
Schneider Electric 28- CS&P C264 Hardware Presentation E01
CCU board wiring :Double pole relays (A&B contacts) wired in serial
CCU pins no
Internal CCU relaysdescriptionCircuit Breaker
side
Vcc+
Open CoilCB1
Vcc-
Close CoilCB1
Vcc+
Open CoilCB2
Vcc-
Close CoilCB2
Simultaneouschange of both contacts A and B
CCU211 Double Cut
-
Schneider Electric 29- CS&P C264 Hardware Presentation E01
Main characteristics : 4 opto-isolated AI (Current or Voltage) 20 ms time tagging (acquisition) 16 bits A/D converter with 0.1% accuracy SMRR : 98dB CMRR : 150dB
Analogue Input Board AIU201
-
Schneider Electric 30- CS&P C264 Hardware Presentation E01
Main characteristics : 8 independent opto-isolated AI (Current only) 20 ms time tagging (acquisition) 16 bits A/D converter 0.1% accuracy SMRR : 98dB CMRR : 150dB Input impedance : 75ohms
This board is replacing the AIU210!
Analogue Input Board AIU211
-
Schneider Electric 31- CS&P C264 Hardware Presentation E01
Main characteristics : 4 AO + 4DO as Read Inhibit signals 100 ms stabilisation time external voltage power source 48VDC 0.1% accuracy 4-20mA, 10mA, 20mA
Analogue Output Board AOU200
N Description1 External power supply +48V2 NIL3 External power supply (0V)4 NIL5 WDOG+6 WDOG-7 NIL8 READ INHIBIT AO n 1+9 READ INHIBIT AO n 1-10 READ INHIBIT AO n 2+11 READ INHIBIT AO n 2-12 READ INHIBIT AO n 3+13 READ INHIBIT AO n 3-14 READ INHIBIT AO n 4+15 READ INHIBIT AO n 4-16 NIL17 AO n 1+18 AO n 1-19 AO n 2+20 AO n 2-21 AO n 3+22 AO n 3-23 AO n 4+24 AO n 4-
-
Schneider Electric 32- CS&P C264 Hardware Presentation E01
4 CT 2 ranges each (1-5A) Range 0.2 In to 4 In accuracy 0.2%
5 VT for TMU220 (4VT on old TMU200) Input Nom: 57 to 500V Range 4V to 500V(800V) acc. 0.2%(possibility to use TMU220 instead of TMU200 on old substations without changing configuration)
Direct measurement RMS values of line/phase voltage (Van, Vab, ...) RMS values of line current (Ia, Ib, Ic) RMS values of residual current and voltage (Ir and Vr) Frequency Active power (Pa, Pb, Pc and Ptotal) Reactive power (Qa, Qb, Qc and Qtotal)
Derived Measurements Fundamental magnitudes and phase angles Apparent Power (Sa, Sb , Sc and Stotal) Import/Export active and reactive energy Power factor (displacement, distortion and true factor) Fundamental Sequence components (Id, Ii, I0, Vd, Vi, V0) Rolling, Peak, Dip demand values Phase and amplitude difference 15th Harmonic 64 samples/period
+ Daughter Board DSP on CPU board
Transducerless Measure Unit TMU220
-
Schneider Electric 33- CS&P C264 Hardware Presentation E01
TMU220 wiring : Transducerless Measure Unit TMU220
-
Schneider Electric 34- CS&P C264 Hardware Presentation E01
3 Phase + 1 neutral current transformer (3*I + Io) Ratings In: 1 or 5 Amperes by jumper Phase Current: 0.1 to 40 In Earth Current: 0.002 to 1 Ien
0.01 to 8 Ien 0.1 to 40 Ien
Thermal heating 4 In permanent, 30 In during10secs,100 In 1sec
Bandwidth : 10th harmonic (no MV) Threshold acc : 2% Compatibility with external CT : 5VA, 5P10
4 Phase voltage transformer (4 VT) Nominal voltage 57 to 130 VRMS Thermal heating : 2 Vn (Phase-N )permanent
2.6 Vn (Phase N) -10seconds Connection options : defined by setting Threshold acc : 2%
CT/VT acquisition module (32 samples/period)
Sensitivity
Transducerless Measure Unit TMU210
-
Schneider Electric 35- CS&P C264 Hardware Presentation E01
CPU Daughter board using one slot CDigital Signal Processor (DSP TMS320C6711)
for protection functions (like P127 + P923)5 Digital Input - isolated
A02_48Vdc , A03_110-125Vdc, A04_220Vdc Consumption 5mA in 48V Settable filtering
4 Digital Output - isolated contacts (NO type) 250Vdc 50W resistive or 25W inductive (L/R=40ms) Carry : 5A 30A during 30s Operation time DSPIO211
-
Schneider Electric 36- CS&P C264 Hardware Presentation E01
Fixed inputs, usage defined in SCE
Blocking Selectivity Cold Load Start Disturbance Start
Evolution DSPIO 210 to DSPIO 211
DSPIO 211 3 Separate trip contacts DO 5 for CloseCB in Auto Rec DO 4 for Blocking
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
PIN
Digital Signal ProcessorInput Output
Board
DSPIO
VIN
-
VIN
-
-
-
+
+
COLD LOAD START
DI7
VIN
--
+BLOCKING
VIN
--
+ SELECTIVITY
Signal inputs
DIST REC START
TRIP C
TRIP B
TRIP A
123456
9101112131415161718192021222324
PIN
Digital Signal ProcessorInput OutputBoard
DSPIO211
COLD LOAD
BLOCKING
Signal inputs
DIST REC
TRIP C
TRIP B
TRIP A
IN
--
+
SELECTIVITYIN
--
+
IN
--
+
IN
--
+
IN
--
+78
K5
K4
Wiring DSPIO210 to DSPIO 211
-
Schneider Electric 37- CS&P C264 Hardware Presentation E01
Pin N. Signal1 DI BLOCKING +2 DI BLOCKING Common3 DI SELECTIVITY +4 Not Configurable5 DI SELECTIVITY Common6 COLD LOAD START +7 DISTURBANCE START +8 STARTS COLD LOAD / DREC Common9 K5/1 + Close CB
10 K5/1 - Close CB11 K5/2 + Close CB12 K5/2 - Close CB13 K4/1 + Not Configurable14 K4/1 - Not Configurable15 K4/2 + Not Configurable16 K4/2 - Not Configurable17 Not connected18 Trip Phase C +19 Trip Phase C -20 Trip Phase B +21 Trip Phase B -22 Trip Phase A +23 Trip Phase A -24 Trip Phase A -
123456
9101112131415161718192021222324
PIN
Digital Signal ProcessorInput OutputBoard
DSPIO211
COLD LOAD
BLOCKING
Signal inputs
DIST REC
TRIP C
TRIP B
TRIP A
IN
--
+
SELECTIVITYIN
--
+
IN
--
+
IN
--
+
IN
--
+78
K5
K4
DSPIO 211 Wiring
-
Schneider Electric 38- CS&P C264 Hardware Presentation E01
Generalities Rack Hardware Main Boards Description I/O Boards description Communication Boards
Content
-
Schneider Electric 39- CS&P C264 Hardware Presentation E01
SWU200 4 TXSWU202 -multimode - 2FX - 4 TX
Switch Board SWU2xx
-
Schneider Electric 40- CS&P C264 Hardware Presentation E01
SWR202 - multimode 2FX -> 4 TX SWR204 - monomode 2FX -> 4 TX
! SWR21x is new version able to communicate with Switch Manager software Switch Board SWR2xx
Good Practice : switch number = end of BCU IP
-
Schneider Electric 41- CS&P C264 Hardware Presentation E01
SWD202 - multimode 2FX -> 4 TX SWD204 - monomode 2FX -> 4 TX
! SWD21x is new version able to communicate with Switch Manager software Switch Board SWD2xx
Good Practice : switch number = end of BCU IP
-
Schneider Electric 42- CS&P C264 Hardware Presentation E01
ECU200 / ECU201 Extended Communication Unit for CPU
ECU200 : converts RS232 -> Fx ST connector Wavelength : 820nm Jumper set : Light On Jumper reset : Light Off
ECU201 : converts RS232 -> RS4xx Jumper set : RS422 (4 wires) Jumper reset : RS485 (2 wires)
Communication Module ECU20x