Download - Coordinacion de Protecciones Oriente
S/E ORIENTE
In [A]PROTECCION 51 PROTECCION 50 PROTECCION 51N PROTECCION 50N
CURVA TDS CURVA TDS
175 13.8 NO 50 250 1.08 270 3.6 - - - 0.60 150.00 0.75 - - - 65K ABB REF541
460 13.8 NO 40 200 1.35 270 3.6 - - - 0.75 150.00 0.75 - - - 65K ABB REF541
Alimentador Totoras 460 13.8 NO 50 250 1.08 270 3.6 - - - 0.60 150.00 0.75 - - - 65K ABB REF541
300 13.8 NO 40 200 1.35 270 3.6 - - - 0.75 150.00 0.75 - - - 65K ABB REF541
301 13.8 NO 120 600 0.45 270 3.6 - - - 0.25 150.00 0.75 - - - 65K ABB REF541
502.04 13.8 NO 160 502.0 1.24 624 3.3 - - - 0.64 320.00 5.7 - - - - ABB RET541
502.04 13.8 NO 160 502.0 1.24 624 3.3 - - - 0.64 320.00 5.7 - - - - ABB RET541
243 13.8 NO 60 300 1.00 300 5.2 11.08 3324 40 0.50 150.00 0.15 3.56 1068 40 - ABB REF541
112.96 13.8 NO 40 200 0.67 134 2.8 - - - 0.26 52.00 1.2 - - - - ABB REF541
451.00 69 SI 120 600 0.57 342 0.16 2.5 1500 40 0.25 150.00 0.27 5 3000 40 - ABB REF541
401.00 69 NO 80 400 0.44 175.2 6.5 9.75 3900 40 0.20 80.00 0.29 7.5 3000 40 - ABB REF541
ELEMENTO PROTEGIDO
VOLTAJE [kV]
ACTIVADA FUNCION
DIRECCIONAL
CT RATIO
I BASE [A]
FUSIBLE MAXIMO
MODELO DE RELETAP
FASEI PRIMARIA
[A]TAP
FASEI PRIMARIA
[A]TIEMPO
[ms]TAP
FASEI PRIMARIA
[A]TAP
FASEI PRIMARIA
[A]TIEMPO
[ms]
Alimentador Picaihua
IEEE Extremely
Inverse
IEC Extremely
Inverse
Alimentador Universidad
IEEE Extremely
Inverse
IEC Extremely
Inverse
IEEE Extremely
Inverse
IEC Extremely
Inverse
Alimentador Olimpica
IEEE Extremely
Inverse
IEC Extremely
Inverse
Alimentador Bolivariana
IEEE Extremely
Inverse
IEC Extremely
Inverse
Transformador T1 12 MVA, SIEMENS
IEEE Very Inverse
IEEE Very Inverse
Transformador T2 12 MVA, SHENDA
IEEE Very Inverse
IEEE Very Inverse
Interconexion Oriente-Lligua/Extremo Oriente
IEEE Very Inverse
IEC Extremely
Inverse
Banco de Capacitores
IEEE Extremely
Inverse
IEEE Extremely
Inverse
Linea S/T Oriente-Loreto
IEC Very Inverse
IEC Extremely
Inverse
Linea S/T Oriente-Totoras_EEASA
IEEE Extremely
Inverse
IEC Very Inverse