Page 1: Coordinacion de Protecciones Loreto

S/E LORETO

In [A]PROTECCION 51 PROTECCION 50 PROTECCION 51N PROTECCION 50N

CURVA TDS CURVA TDS

175 13.8 NO 60 300 0.90 270 0.95 - - - 0.47 141.00 3 - - - 65K ABB REF630

460 13.8 NO 60 300 0.90 270 0.95 - - - 0.47 141.00 3 - - - 65K ABB REF630

460 13.8 NO 60 300 0.90 270 0.95 - - - 0.47 141.00 3 - - - 65K ABB REF630

300 13.8 NO 60 300 0.90 270 0.95 - - - 0.47 141.00 3 - - - 65K ABB REF630

301 13.8 NO 60 300 0.90 270 0.95 - - - 0.47 141.00 3 - - - 65K ABB REF630

301 13.8 NO 60 300 0.90 270 0.95 - - - 0.47 141.00 3 - - - 65K ABB REF630

301 13.8 NO 60 300 0.90 270 0.95 - - - 0.47 141.00 3 - - - 65K ABB REF630

669.39 13.8 NO 200 1000 0.84 840 0.5 - - - 0.42 420.00 0.7 - - - ABB RET630

ELEMENTO PROTEGIDO

VOLTAJE [kV]

ACTIVADA FUNCION

DIRECCIONAL

CT RATIO

I BASE [A]

FUSIBLE MAXIMO

MODELO DE RELETAP

FASEI PRIMARIA

[A]TAP

FASEI PRIMARIA

[A]TIEMPO

[ms]TAP

FASEI PRIMARIA

[A]TAP

FASEI PRIMARIA

[A]TIEMPO

[ms]

Alimentador Bellavista

ANSI Extremely

Inverse

IEC Extremely

Inverse

Alimentador Ferroviario

ANSI Extremely

Inverse

IEC Extremely

Inverse

Alimentador Subetrranea

ANSI Extremely

Inverse

IEC Extremely

Inverse

Alimentador 12 de Noviembre

ANSI Extremely

Inverse

IEC Extremely

Inverse

Alimentador Vicentina

ANSI Extremely

Inverse

IEC Extremely

Inverse

Alimentador Catiglata

ANSI Extremely

Inverse

IEC Extremely

Inverse

Interconexion Loreto Oriente

ANSI Extremely

Inverse

IEC Extremely

Inverse

Transformador T 16 MVA, 69/13.8 kV S7E Loreto

ANSI Very Inverse

IEC Very Inverse