coordinacion de protecciones lligua-peninsula

Upload: darkjhesus

Post on 09-Jan-2016

219 views

Category:

Documents


0 download

DESCRIPTION

Coordinacion de Protecciones

TRANSCRIPT

AJUSTES RELES SE LLIGUA PENINS/E LLIGUA - PENINSULAELEMENTO PROTEGIDOIn [A]VOLTAJE [kV]ACTIVADA FUNCION DIRECCIONALCT RATIOI BASE [A]PROTECCION 51PROTECCION 50PROTECCION 51NPROTECCION 50NFUSIBLE MAXIMOMODELO DE RELECURVATAP FASEI PRIMARIA [A]TDSTAP FASEI PRIMARIA [A]TIEMPO [ms]CURVATAP FASEI PRIMARIA [A]TDSTAP FASEI PRIMARIA [A]TIEMPO [ms]Alimentador Izamba46013.8NO40200ANSI Extremely Inverse1.352700.65---IEC Extremely Inverse0.70140.003---65KABB REF630Alimentador Peninsula56613.8NO40200ANSI Extremely Inverse1.352700.7---IEC Extremely Inverse0.70140.003---65KABB REF630Interconexion Oriente-Lligua/Extremo Lligua24313.8SI60300ANSI Very Inverse1.003000.15---IEC Extremely Inverse0.50150.000.25.85175540ABB REF630Transformador 3.5 MVA, 6.9/13.8 kV S/E Peninsula-Lligua292.866.90NO60300ANSI Normal Inverse1.203601.24120040-------ABB RET630