configuracion de regleta de alarmas ver220712

Upload: silvajc30

Post on 03-Apr-2018

213 views

Category:

Documents


0 download

TRANSCRIPT

  • 7/29/2019 Configuracion de Regleta de Alarmas Ver220712

    1/10

    X1.1 White and orange 1

    X1.2 Orange 1

    X1.3 White and green 2

    X1.6 Green 2

    X1.5 White and blue 3

    X1.4 Blue 3

    X1.7 White and brown 4

    X1.8 Brown 4

    X1.1 White and orange 5

    X1.2 Orange 5

    X1.3 White and green 6

    X1.6 Green 6

    X1.5 White and blue 7

    X1.4 Blue 7

    X1.7 White and brown 8

    X1.8 Brown 8

    9

    9

    10

    10

    Consideraciones:

    1.- Huawei debe instalar 3 cables UTP desde la regleta de alarmas hacia el APM30 (EXT ALARM0, EX ALARM

    ONLY PCS WITH GENERATOR

    EXT ALARM 0

    Low Fuel Tank level

    GE Warning

    HACIA EL APM REGLETA D

    GE RunningNODOB

    EXT ALARM 1

    AC Surge Protector

    Low Oil Pressure/High Temperature Cooling

    Water (enseriadas)

    ALM1 (Port 4)/ALM0

    (Port 1)Radio MW RTN910/ RTN950 Remote Start GE

    Battery Breaker has been Disconnected

    Site Door has been Opened

    Intrusion Alarm

  • 7/29/2019 Configuracion de Regleta de Alarmas Ver220712

    2/10

    HACIA LOS DISPOSITIVOS (Sensores, GE, etc)

    1

    1

    2

    2

    3

    3

    4

    4

    5

    5

    6

    6

    7

    7

    8

    8

    9

    9

    10

    10

    Y AUX DEL RADIO MW)

    AC Surge Protector

    GE Warning

    Low Fuel Tank level

    E ALARMAS

    Intrusion Alarm

    GE Running

    GE

    Low Oil Pressure/High Temperature Cooling Water (enseriadas)

    Remote Start GE

    DISPOSITIVOS(Sensores,

    GE,e

    tc)Battery Breaker has been Disconnected

    Site Door has been Opened

  • 7/29/2019 Configuracion de Regleta de Alarmas Ver220712

    3/10

    PUERTO RJ45 PIN

    1 The first external alarm input signal

    2 Grounding end for the first external alarm input signal

    3 The second external alarm input signal6 Grounding end for the second external alarm input signal

    4 The third external alarm input signal

    5 Grounding end for the third external alarm input signal

    7 The forth external alarm input signal

    8 Grounding end for the forth external alarm input signal

    1 The first external alarm input signal

    2 Grounding end for the first external alarm input signal

    3 The second external alarm input signal

    6 Grounding end for the second external alarm input signal

    4 The third external alarm input signal

    5 Grounding end for the third external alarm input signal7 The forth external alarm input signal

    8 Grounding end for the forth external alarm input signal

    1 The first external alarm output signal (+)

    2 The first external alarm output signal (-)

    Consideraciones:

    1.- Huawei debe instalar 3 cables UTP desde la regleta de alarmas hacia los radios de

    ALM0 (primer

    radio RTN950)

    ALMI (primer radio

    RTN950)

    ALMI (segundo radio

    RTN950)

  • 7/29/2019 Configuracion de Regleta de Alarmas Ver220712

    4/10

    HACIA EL APM

    1 1

    1 1

    2 2

    2 2

    3 3

    3 3

    4 4

    4 4

    5 5

    5 5

    6 6

    6 6

    7 7

    7 7

    8 88 8

    9 9

    9 9

    10 10

    10 10

    W

    ONLY REPEATER with RTN950 (2 radios)

    AC Surge Protector

    Remote Start GE

    Intrusion Alarm

    Battery Breaker has been Disconnected

    REGLETA DE ALARMAS

    GE Running

    Low Oil Pressure/High Temperature Cooling

    Water (enseriadas)

    GE Warning

    Low Fuel Tank level

    Site Door has been Opened

  • 7/29/2019 Configuracion de Regleta de Alarmas Ver220712

    5/10

    HACIA LOS DISPOSITIVOS (Sensores, GE, etc) Destino

    GE

    GE

    GE

    GE

    Sensores de puertas

    Cercos Electricos

    Hacia el APM

    GE

    Hacia el APM

    Low Oil Pressure/High Temperature Cooling Water (enseriadas)

    AC Surge Protector

    Remote Start GE

    Intrusion Alarm

    GE Running

    Battery Breaker has been Disconnected

    GE Warning

    Low Fuel Tank level

    Site Door has been Opened

  • 7/29/2019 Configuracion de Regleta de Alarmas Ver220712

    6/10

    X1.1 White and orange

    X1.2 Orange

    X1.3 White and green

    X1.6 Green

    X1.5 White and blue

    X1.4 Blue

    X1.7 White and brown

    X1.8 Brown

    X1.1 White and orange

    X1.2 Orange

    X1.3 White and green

    X1.6 Green

    X1.5 White and blue

    X1.4 Blue

    X1.7 White and brown

    X1.8 Brown

    1e rs ex erna a arm ou pu s gna

    2The first external alarm output signal

    (-)

    GE Warning

    ONLY PCS WITH GENER

    HACIA EL APM

    NODOB

    EXT ALARM 1

    Air Conditioning 1 AC Power Failure

    EXT ALARM 0

    Low Fuel Tank level

    ALM0 (primer radio

    RTN950)

    Low Oil Pressure/High Temperature Cooling

    Water (enseriadas)

    Remote Start GE

    Air Conditioning 2 AC Power Failure

    Site Door has been Opened

    Mayor Rectifier

    GE Running

  • 7/29/2019 Configuracion de Regleta de Alarmas Ver220712

    7/10

    HACIA LOS DISPOSITIVOS (Sensores, GE, etc)

    1 1

    1 1

    2 2

    2 2

    3 3

    3 3

    4 4

    4 4

    5 5

    5 5

    6 6

    6 6

    7 7

    7 7

    8 8

    8 8

    9 9

    9 9

    10 10

    10 10

    TOR

    REGLETA DE ALARMAS

    Air Conditioning 1 AC Power Failure

    GE Warning

    GE

    Low Fuel Tank level

    Low Oil Pressure/High Temperature Cooling Water (enseriadas)

    Remote Start GE

    DISPOSITIVOS(Sensores,

    GE,e

    tc)Air Conditioning 2 AC Power Failure

    Site Door has been Opened

    Intrusion Alarm

    GE Running

  • 7/29/2019 Configuracion de Regleta de Alarmas Ver220712

    8/10

    PUERTO RJ45 PIN

    1 The first external alarm input signal

    2 Grounding end for the first external alarm input signal

    3 The second external alarm input signal

    6 Grounding end for the second external alarm input signal

    4 The third external alarm input signal

    5 Grounding end for the third external alarm input signal

    7 The forth external alarm input signal

    8 Grounding end for the forth external alarm input signal

    1 The first external alarm input signal

    2 Grounding end for the first external alarm input signal

    3 The second external alarm input signal

    6 Grounding end for the second external alarm input signal

    4 The third external alarm input signal

    5 Grounding end for the third external alarm input signal

    7 The forth external alarm input signal

    8 Grounding end for the forth external alarm input signal

    1 The first external alarm output signal (+)

    2 The first external alarm output signal (-)

    ALMI (primer radio

    RTN950)

    ALM0 (primer

    radio RTN950)

    ALMI (segundo radio

    RTN950)

  • 7/29/2019 Configuracion de Regleta de Alarmas Ver220712

    9/10

    HACIA EL APM

    1 1

    1 1

    2 22 2

    3 3

    3 3

    4 4

    4 4

    5 5

    5 5

    6 6

    6 6

    7 7

    7 7

    8 8

    8 8

    9 9

    9 9

    10 10

    10 10

    Battery Breaker has been Disconnected

    ONLY REPEATER with RTN950 (2 radios)

    REGLETA DE ALARMAS

    GE 1 Running

    GE 1 Warning

    Low Fuel Tank level

    Site Door has been Opened

    Remote Start GE

    GE 2 Running

    GE 2 Warning

    Intrusion Alarm

  • 7/29/2019 Configuracion de Regleta de Alarmas Ver220712

    10/10

    HACIA LOS DISPOSITIVOS (Sensores, GE, etc) Destino

    GE 1 Running GE

    GE 1 Warning GE

    Low Fuel Tank level GE

    Site Door has been Opened Sensores de puertas

    Remote Start GE GE

    Battery Breaker has been Disconnected Hacia el APM

    GE 2 Running GE

    GE 2 Warning Hacia el APM

    Intrusion Alarm Cercos Electricos