51-51n_cooper_form 6 (cto 24 de julio)

2
13,8 kV ? S/E BACHAQUERO ? No se tiene potencial FALLA 3F 2190 AMP 52,35 MVA FALLA 1F 2856 AMP 68,26 MVA D-205 Tipo de Conductor: 1/0 AWG 24 DE JULIO Longitud del Troncal: 15,00 Km Corriente Nominal: 302 Amp Corriente Emergencia: 380 Amp 13,65 MVA X X 3 x kV 3 x kV Ipri (seleccionado) = 900 A Ipri (seleccionado) = 900 A Ajuste I (pri) = 300 7,17 72 Ajuste MVA = 1,72 AJUSTE 8,25 6,90 10,85 28,44 15,00 Indicate PT Connection: Wye or Delta System Zero Seq. Source Impedance in ohms (pri) Bushings Configuration (Wye/Delta) Parametro Minimum Trip Block Trips Overcurrent Alarm Alarm Time Delay Parametro Curve Type Nota: Curva utilizada unicamente para la primera operación Time Multiplier (inicio de la falla) con la sobrecorriente instantanea habilitada TCC1 Mult Enable Time Adder TCC1 Add Enable Minimum Response Time TCC1 MRTA Enable High Current Trip TCC1 HCT Enable Reset Coefficient TCC1 Disk Reset Parametro Curve Type Nota: Se utiliza unicamente para el ciclo de recierre, pues se Time Multiplier desea que durante la actuacion del mismo la instantanea TCC2 Mult Enable permanezca deshabilitada Time Adder TCC2 Add Enable Minimum Response Time TCC2 MRTA Enable High Current Trip TCC2 HCT Enable Reset Coefficient TCC2 Disk Reset Kyle 112 Kyle 112 0,70 1,50 0,13 Seconds 0,17 Seconds Kyle 116 1,00 0,00 Seconds 0,01 Seconds 0,01 Seconds 0,01 Seconds 3,0 x Min Trip 12,5 x Min Trip 32,0 x Min Trip 1,00E-06 Seconds 1,00E-06 Seconds 1,00E-06 Seconds 1,00E-06 Seconds 1,00E-06 Seconds 1,00E-06 Seconds 3,0 x Min Trip 12,5 x Min Trip 32,0 x Min Trip 0,01 Seconds 0,01 Seconds 0,01 Seconds 0,13 Seconds 0,17 Seconds 0,00 Seconds 0,70 1,50 1,00 Phase Ground Negative Sequence Kyle 112 Kyle 112 Kyle 116 TCC2 (X:1) System Configuration 0,69 AJUSTE System Rotation Wye-Connected PT's 1-2 3-4 5-6 A-B-C Phase Sequence Phase Fault Locator 72 A TEMPORIZADAS FASE TIERRA Ajuste MVA = Ajuste I (pri) = 300 A Ground Negative Sequence Ground Phase Negative Sequence 1000 Amps 3600 Seconds TCC1 270 Amps 3600 Seconds 60 #¡VALOR! PARAMETRO 2,95 AJUSTE 24 DE JULIO Positive Sequence Line Impedance <R> Zero Sequence Line Impedance <R> Zero Sequence Line Impedance <jX> Line Length (Km) 300 Amps 72 Amps SYSTEM CONFIGURATION 0 1000 13,80 DATOS DEL ALIMENTADOR X = MVA FASE x % A CUBRIR = Positive Sequence Line Impedance <jX> 3200 Amps MULTIPLICADOR = 3,0 NIVELES DE CC EN 13,8 KV MULTIPLICADOR = 12,5 = 571,2 A = 438,0 A Ipri = 65 Amps 3600 Seconds Pick-up (tierra) = Pick-up (fase) = CT Type CT Primary Rating (X:1) PT Ratio (X:1) Adjust (Deg) OPERATION PARAMETERS Overcurrent Protection INSTANTANEAS 10,47 MVA X = MVA TIERRA x % A CUBRIR = Ipri = FASE TIERRA V expected (kV pri) Zero Seq. Source Impedance <R> Zero Seq. Source Impedance <jX> FORMATO DE AJUSTES - RECONECTADOR COOPER FORM 6 System Frecuency (Hz) PARAMETRO PARAMETRO Feeder Description NOTA: La unidad de la función instantánea se ajusta a tres (3) veces el TAP de la temporizada de fase; lo cual representa un 52% del recorrido del troncal ó 41,1% del Ncc de la barra en 13,8 KV. R X X X X X X X X X X X GERENCIA DE INGENIERÍA DE TRANSMISIÓN UNIDAD DE INGENIERÍA DE PROTECCIONES USO INTERNO ENEL-S-21 Realizado por: EEM

Upload: carlose123

Post on 16-Sep-2015

7 views

Category:

Documents


2 download

DESCRIPTION

cooper form 6

TRANSCRIPT

  • 13,8 kV ? S/E BACHAQUERO?

    No se tiene potencial FALLA 3F 2190 AMP 52,35 MVAFALLA 1F 2856 AMP 68,26 MVA

    D-205 Tipo de Conductor: 1/0 AWG24 DE JULIO Longitud del Troncal:15,00 Km

    Corriente Nominal: 302 AmpCorriente Emergencia: 380 Amp

    13,65 MVA

    X X3 x kV 3 x kV

    Ipri (seleccionado) = 900 A Ipri (seleccionado) = 900 A

    Ajuste I (pri) = 300 7,17 72 Ajuste MVA = 1,72

    AJUSTE8,25

    6,90

    10,85

    28,44

    15,00

    Indicate PT Connection: Wye or Delta

    System Zero Seq. Source Impedance in ohms (pri) Bushings Configuration (Wye/Delta)

    ParametroMinimum TripBlock Trips

    Overcurrent AlarmAlarm Time Delay

    ParametroCurve Type Nota: Curva utilizada unicamente para la primera operacin

    Time Multiplier (inicio de la falla) con la sobrecorriente instantanea habilitadaTCC1 Mult Enable

    Time AdderTCC1 Add Enable

    Minimum Response TimeTCC1 MRTA EnableHigh Current TripTCC1 HCT EnableReset CoefficientTCC1 Disk Reset

    ParametroCurve Type Nota: Se utiliza unicamente para el ciclo de recierre, pues se

    Time Multiplier desea que durante la actuacion del mismo la instantaneaTCC2 Mult Enable permanezca deshabilitada

    Time AdderTCC2 Add Enable

    Minimum Response TimeTCC2 MRTA EnableHigh Current TripTCC2 HCT EnableReset CoefficientTCC2 Disk Reset

    Kyle 112 Kyle 112

    0,70 1,50

    0,13 Seconds 0,17 Seconds

    Kyle 116

    1,00

    0,00 Seconds

    0,01 Seconds 0,01 Seconds 0,01 Seconds

    3,0 x Min Trip 12,5 x Min Trip 32,0 x Min Trip

    1,00E-06 Seconds 1,00E-06 Seconds 1,00E-06 Seconds

    1,00E-06 Seconds 1,00E-06 Seconds 1,00E-06 Seconds

    3,0 x Min Trip 12,5 x Min Trip 32,0 x Min Trip

    0,01 Seconds 0,01 Seconds 0,01 Seconds

    0,13 Seconds 0,17 Seconds 0,00 Seconds

    0,70 1,50 1,00

    Phase Ground Negative SequenceKyle 112 Kyle 112 Kyle 116

    TCC2

    (X:1)

    System Configuration

    0,69

    AJUSTESystem Rotation

    Wye-Connected PT's

    1-2 3-4 5-6

    A-B-C Phase Sequence

    Phase

    Fault Locator

    72 A

    TEMPORIZADASFASE TIERRA

    Ajuste MVA = Ajuste I (pri) =

    300 A

    Ground Negative Sequence

    GroundPhase Negative Sequence1000 Amps

    3600 Seconds

    TCC1

    270 Amps

    3600 Seconds

    60

    #VALOR!

    PARAMETRO

    2,95

    AJUSTE24 DE JULIO Positive Sequence Line Impedance

    Zero Sequence Line Impedance Zero Sequence Line Impedance Line Length (Km)

    300 Amps 72 Amps

    SYSTEM CONFIGURATION

    0

    1000

    13,80

    DATOS DEL ALIMENTADOR

    X = MVA FASE x % A CUBRIR =

    Positive Sequence Line Impedance

    3200 Amps

    MULTIPLICADOR = 3,0

    NIVELES DE CC EN 13,8 KV

    MULTIPLICADOR = 12,5

    = 571,2 A= 438,0 A Ipri =

    65 Amps

    3600 Seconds

    Pick-up (tierra) =Pick-up (fase) =

    CT TypeCT Primary Rating (X:1)PT Ratio (X:1)Adjust (Deg)

    OPERATION PARAMETERS

    Overcurrent Protection

    INSTANTANEAS

    10,47 MVA X = MVA TIERRA x % A CUBRIR =

    Ipri =

    FASE TIERRA

    V expected (kV pri)

    Zero Seq. Source Impedance Zero Seq. Source Impedance

    FORMATO DE AJUSTES - RECONECTADOR COOPER FORM 6

    System Frecuency (Hz)

    PARAMETRO

    PARAMETRO

    Feeder Description

    NOTA: La unidad de la funcin instantnea se ajusta a tres (3) veces el TAP de la temporizada de fase; lo cual representa un 52% del recorrido del troncal 41,1% del Ncc de la barra en 13,8 KV.

    R

    X

    X X

    X X

    X X

    X X

    X X

    GERENCIA DE INGENIERA DE TRANSMISINUNIDAD DE INGENIERA DE PROTECCIONES

    USO INTERNO ENEL-S-21 Realizado por: EEM

  • FORMATO DE AJUSTES - RECONECTADOR COOPER FORM 6

    GERENCIA DE INGENIERA DE TRANSMISINUNIDAD DE INGENIERA DE PROTECCIONES

    Reclosing

    ParametroOpen Interval #1Open Interval #2Open Interval #3

    Seconds

    Seconds

    Operations

    Reclose RetrySeconds

    Operation

    ParametroOperation #1Operation #2Operation #3Operation #4

    ParametroPhase Pickup

    Phase Time DelayThree-Phase Pickup

    Three-Phase Time DelayAlarm Pickup

    Alarm Time Delay

    Enable 1P UV Trips Enable OV Trips

    Enable 3P UV Trips

    ParametroStage 1 Pickup

    Stage 1 Time DelayStage 2 Pickup

    Stage 2 Time DelayEnable UFreq Trips Enable OFreq Trips

    ParametroAlarm Pickup

    Alarm Time Delay

    OBSERVACIONES:- Se recomienda habilitar el esquema de minima tensin (27) para facilitar las maniobras de recuperacin en caso de apagones, igualmente evitar someter a depresiones de tensin sostenidas a los clientes servidos por este alimentador.- Se mantiene el mismo arranque de la temporizada de fase y para el ajuste del arranque de la temporizada de tierra se aplic el criterio del 24% de desbalance del ajuste en fase.- Se recomienda habilitar dos ciclos de recierre, un 1er ciclo de 300 mseg y un 2do ciclo de 45 seg, con un tiempo de reposicin de 60 seg.

    60Reset time

    Reset Target 36001Allow Sequence Coordination up to

    1000,0 Seconds 1000,0 Seconds

    45,0 Seconds 45,0 Seconds

    GroundPhase/Neg Seq0,3 Seconds 0,3 Seconds

    Recloser Timing

    RECLOSER

    OPERATION SEQUENCE

    Phase/Neg Seq Ground

    Reclose Retry Interval 3600

    Allow Reclose Retry for up to 1

    TCC1 TCC1

    TCC2 TCC2

    TCC2 TCC2

    Number of Trip Operation to Lockout 3

    VOLTAGE

    Undervoltage Overvoltage

    TCC2 TCC2

    11,04 kV (pri) 15,87 kV (pri)

    10 Seconds 1 Seconds

    11,04 kV (pri) 15,87 kV (pri)

    10 Seconds 1 Seconds

    11,73 kV (pri) 15,18 kV (pri)

    3 Seconds 1 Seconds

    with 3P Inhibit

    FREQUENCY

    Underfrequency Tripping Overfrequency Tripping

    59,5 Hz 62,0 Hz

    58,7 Hz 63,0 Hz

    0 Seconds 100 Seconds

    1 Seconds 10 Seconds

    58,7 Hz 63,0 Hz

    0 Seconds 100 Seconds

    Underfrequency Alarm Overfrequency Alarm

    X

    USO INTERNO ENEL-S-21 Realizado por: EEM