  • MEMORIA DE DISEO Y CLCULO ESTRUCTURAL DE TIJERALES METALICOS EN AUDITORIO

    MEMORIA DE CLCULO

    PROYECTO:

    CONSTRUCCIN DE LA NUEVA SEDE DEL INSTITUTO NACIONAL DE REHABILITACIN "DRA. ADRIANA REBAZA FLORES"

    CALCULO Y DISEO ESTRUCTURAL DE TIJERALES METLICOS DEL AUDITORIO

  • MEMORIA DE DISEO Y CLCULO ESTRUCTURAL DE TIJERALES METALICOS EN AUDITORIO

    NDICE

    1. GENERALIDADES ......................................................................................................................... 3

    1.1. OBJETIVO:................................................................................................................................... 3 1.2. DESCRIPCIN DE LA ESTRUCTURA: .................................................................................... 3 1.3. NORMATIVIDAD .......................................................................................................................... 3

    2. PROCEDIMIENTO DE DISEO .............................................................................................. 3

    2.1. CONTROL DE DEFLEXIONES: ................................................................................................. 3 2.2. CONTROL DE RATIOS DE INTERACCIN (P-MX-MY): .................................................... 3

    3. CONSIDERACIONES SSMICAS.......................................................................................... 4

    3.1. ZONIFICACIN (Z) ................................................................................................................... 4 3.2. PARMETROS DEL SUELO (S) .............................................................................................. 5 3.3. FACTOR DE AMPLIFICACIN SSMICA (C) ......................................................................... 5 3.4. CATEGORA DE LAS EDIFICACIONES (U)............................................................................. 5 3.5. COEFICIENTE DE REDUCCIN DE FUERZA SSMICA (R) ............................................... 5 3.6. ANLISIS SSMICO ESTTICO ............................................................................................... 5

    4. ESTADOS DE CARGA................................................................................................................. 6

    4.1. CARGAS POR PESO PROPIO (D): ......................................................................................... 6 4.2. SOBRECARGAS (LR): .............................................................................................................. 6 4.3. CARGAS PRODUCIDAS POR SISMO (E): ............................................................................. 6 4.4. CARGAS PRODUCIDAS POR VIENTO (W): ........................................................................... 6

    5. COMBINACIONES DE CARGAS ........................................................................................... 6

    6. ANLISIS ESTRUCTURAL ........................................................................................................ 7

    6.1. MODELO ESTRUCTURAL ADOPTADO ................................................................................... 8 6.2. INTRODUCCIN GRFICA DE CARGAS AL SAP 2000 V.14: ........................................ 9

    7. DISEO Y MEMORIA DE CLCULO ................................................................................. 11

    7.1. DISEO DE ESTRUCTURA ..................................................................................................... 11

    8. CONCLUSIONES Y RECOMENDACIONES .................................................................. 18

  • MEMORIA DE DISEO Y CLCULO ESTRUCTURAL DE TIJERALES METALICOS EN AUDITORIO

    Propietario : INR Proyecto : COBERTURA TECHO METLICO Direccin : CHORRILLOS-LIMA-PER

    1. GENERALIDADES

    1.1. Objetivo:

    La finalidad de la presente memoria de clculo es sustentar el DISEO Y CALCULO ESTRUCTURAL DE TIJERALES METALICOS del Auditorio del Instituto Nacional de Rehabilitacin.

    1.2. Descripcin de la Estructura: La estructura a disear se construir sobre un rea de aproximadamente de 315 m2 que la cubrir en su totalidad. Dicha estructura est compuesta por armaduras (tijerales) en la direccin asignada como X-X y vigas de amarre en la direccin Y-Y, as como correas metlicas para sujecin de cobertura. La estructura metlica se apoyara en vigas de concreto armado. Los techos de la estructura estn ntegramente conformados por coberturas Tipo CALAMINON TI o similar de 0.6mm de espesor.

    1.3. Normatividad El diseo estructural cumplir la normatividad siguiente:

    o RNE 2009, Captulo E020 Cargas. o RNE 2009, Captulo E030 Diseo Sismo Resistente. o RNE 2009, Captulo E090 Estructuras Metlicas o AISC LFRD 2010 o ANSI American National Standards Institute o AISI American Iron and Steel Institute o ASME American Society of Mechanical Engineers o ASTM American Society for Testing of Materials o AWS American Welding Society o SAE Society of Automotive Engineers o SSPC Steel Structures Painting Council

    2. PROCEDIMIENTO DE DISEO

    2.1. Control de Deflexiones:

    Se verificar los desplazamientos verticales obtenidos en el programa SAP 2000 V 15 con los permisibles de la Norma correspondiente.

    2.2. Control de Ratios de Interaccin (P-Mx-My):

  • MEMORIA DE DISEO Y CLCULO ESTRUCTURAL DE TIJERALES METALICOS EN AUDITORIO

    Entre los parmetros que intervienen en el diseo estructural se encuentran las fuerzas de traccin y compresin en los diferentes elementos de la estructura metlica, como son brida superior, brida inferior, montantes, diagonales y viguetas metlicas que se han colocado, as como soportes del techo. De acuerdo al RNE 2009, Captulo E090 Estructuras Metlicas, basada en la norma AISC - LRFD 2010, se efectu una revisin de las fuerzas de demanda (reacciones internas) con las fuerzas de capacidad del elemento (reacciones nominales), dando por aceptable el diseo cuando las capacidades del elemento son mayores a los esfuerzos demandados. (Ru

  • MEMORIA DE DISEO Y CLCULO ESTRUCTURAL DE TIJERALES METALICOS EN AUDITORIO

    3.2. Parmetros del Suelo (S) Para los fines de este estudio, los perfiles de suelo se clasifican tomando en cuenta sus propiedades mecnicas, el espesor del estrato, el periodo fundamental de vibracin y la velocidad de propagacin de las ondas de corte. Para la aplicacin de la norma E-030 de diseo sismo resistente se considera que el perfil de suelo del lugar de la edificacin es de tipo rgido (S3), el parmetro Tp asociado con este tipo de suelo es de 0.90 s, y el factor de amplificacin del suelo se considera S= 1.4.

    3.3. Factor de amplificacin Ssmica (C) De acuerdo a las caractersticas de sitio, se define al factor de amplificacin ssmica (C) por la siguiente expresin:

    C = 2.5 x (Tp/T); C 2.5 Donde Tp est relacionado al parmetro de suelo, y T es el periodo fundamental de la estructura

    3.4. Categora de las edificaciones (U) Cada estructura debe ser clasificada de acuerdo a la categora de uso de la misma, debido a que la actual estructura sirve como almacn y alberga cantidad considerable de trabajadores la norma establece un factor de importancia U=1.3, que es el que se tomar para este anlisis.

    3.5. Coeficiente de Reduccin de Fuerza Ssmica (R) El coeficiente de reduccin de fuerza ssmica est en funcin de los materiales usados y el sistema de estructuracin sismo resistente predominante en cada direccin. Para nuestro caso la Norma Tcnica considera R=6 (prtico dctil por ser un sistema de acero).

    3.6. Anlisis Ssmico Esttico Para poder calcular la fuerza de sismo que actuara en la estructura procedemos a definir el valor de la fuerza cortante basal, definida por la formula siguiente:

    =

    Donde: Z = 0.4 (Zona 3 Lima) U = 1.0 S = 1.40 (Tp = 0.90 Suelo intermedio segn NTE E-030) R = 6 (Estructuras dctiles)

  • MEMORIA DE DISEO Y CLCULO ESTRUCTURAL DE TIJERALES METALICOS EN AUDITORIO

    C= 2.5 x (Tp / T); C 2.5

    4. ESTADOS DE CARGA

    4.1. Cargas por peso propio (D): Son cargas provenientes del peso de los materiales, coberturas, luminarias y otros elementos que forman parte de la estructura y/o se consideran permanentes.

    4.2. Sobrecargas (Lr): Cargas que provienen de los pesos no permanentes en la estructura, tales como montaje, mantenimiento, etc.

    4.3. Cargas producidas por sismo (E): Anlisis de cargas que representan un evento ssmico y estn reglamentadas por la norma E.030 de diseo sismo resistente.

    4.4. Cargas producidas por viento (W): Anlisis de cargas generadas por la accin del viento sobre la estructura debido a las grandes reas de exposicin directa y que estn reglamentadas por la norma E.020 Cargas siendo la velocidad adoptada segn la norma V=75 kph para alturas menores a 10 m, teniendo dos casos de incidencia de viento W1 y W2.

    5. COMBINACIONES DE CARGAS Las combinaciones de cargas usadas para realizar el diseo de la estructura aporticada se rigen por la norma E-090 Estructuras Metlicas del Reglamento Nacional de Edificaciones, como a continuacin se detalla: COMB1 : 1.4 D COMB2 : 1.2 D + 1.6 Lr COMB3 : 1.2 D + 1.6 Lr + 0.8 W1 COMB4 : 1.2 D + 1.6 Lr + 0.8 W2 COMB5 : 1.2 D + 0.5 Lr + 1.3 W1 COMB6 : 1.2 D + 0.5 Lr + 1.3 W2 COMB7 : 1.2 D 1.3 W1 COMB8 : 1.2 D 1.3 W2 COMB9a, COMB9b : 1.2 D Ex COMB10a, COMB10b : 1.2 D Ey ENVOLVENTE : COMB1+COMB2+COMB3+COMB3+COMB4+COMB5+

  • MEMORIA DE DISEO Y CLCULO ESTRUCTURAL DE TIJERALES METALICOS EN AUDITORIO

    COMB6+COMB7+COMB8+COMB9+COMB10

    METRADO DE CARGAS:

    Signo (-) : Succin Signo (+): Presin

    6. ANLISIS ESTRUCTURAL

    De acuerdo a los procedimientos sealados y tomando en cuenta las caractersticas de los materiales y cargas que actan sobre la estructura e influyen en el comportamiento de la misma, se muestra a continuacin el anlisis realizado para la obtencin de los resultados.

  • MEMORIA DE DISEO Y CLCULO ESTRUCTURAL DE TIJERALES 8

    6.1. Modelo Estructural Adoptado

    La estructura ha sido analizada mediante el modelamiento de cada elemento que conforma la Nave Industrial, de la siguiente manera: 1. Modelamiento y anlisis de la cubierta o aplicando las cargas antes

    descritas. 2. Luego de obtener el diseo de la cubierta se proceder a obtener las

    reacciones de cada carga en la base de la cubierta.

    3. Los tijerales que componen la estructura estn compuestas por perfiles angulares as tambin las vigas secundarias que conectan los prticos conformados por los tijerales y las columnas metlicas, a continuacin se presenta una breve descripcin de la perfilera principal de la estructura.

    Perfilera Usada en Tijerales T1:

    Perfil : L2x2x1/8 (Brida Superior e Inferior) o Acero Estructural ASTM A-36 o Fluencia: 2530 Kg/cm2 o Rotura : 4100 Kg/cm2

    Perfil : L1x1x1/8 (Montantes Y Diagonales) o Acero Estructural ASTM A-36 o Fluencia: 2530 Kg/cm2 o Rotura : 4100 Kg/cm2

    Perfilera Usada en Vigas V1:

    Perfil : L2x2x1/8 (Brida Superior) o Acero Estructural ASTM A-36 o Fluencia: 2530 Kg/cm2 o Rotura : 4100 Kg/cm2

    Perfil : L2x2x1/4 (Brida Inferior) o Acero Estructural ASTM A-36 o Fluencia: 2530 Kg/cm2 o Rotura : 4100 Kg/cm2

    Perfil : L1x1x1/4 (Diagonales y Montantes) o Acero Estructural ASTM A-36 o Fluencia: 2530 Kg/cm2 o Rotura : 4100 Kg/cm2

    Perfilera Usada en Vigas V2:

    Perfil : L2x2x1/8 (Brida Superior e Inferior) o Acero Estructural ASTM A-36 o Fluencia: 2530 Kg/cm2 o Rotura : 4100 Kg/cm2

  • MEMORIA DE DISEO Y CLCULO ESTRUCTURAL DE TIJERALES 9

    Perfil : L2x2x1/8 (Montantes) o Acero Estructural ASTM A-36 o Fluencia: 2530 Kg/cm2 o Rotura : 4100 Kg/cm2

    Perfil : 2L1x1x1/8 (Diagonales y Montantes) o Acero Estructural ASTM A-36 o Fluencia: 2530 Kg/cm2 o Rotura : 4100 Kg/cm2

    Modelo Tridimensional Super-Estructura

    6.2. Introduccin Grfica de Cargas al SAP 2000 v.14:

    Con el programa SAP definimos cada uno de los elementos de la estructura con sus respectivas caractersticas, en el caso considerando el Acero Estructural ASTM A-36 (fy=2,530 kg/cm2). El mtodo de diseo tomado en cuenta ser AISC LRFD2010.

  • MEMORIA DE DISEO Y CLCULO ESTRUCTURAL DE TIJERALES 10

    Carga muerta (D) Carga en las correas: 17kg/m Carga en los nudos: 57.38kg

    Carga Viva (Lr): 114.75 Kg/nudo

  • MEMORIA DE DISEO Y CLCULO ESTRUCTURAL DE TIJERALES 11

    Carga de Viento (W1): Agua Derecha: 75.94 Kg/m (Succin) Agua Izquierda: 37.97 Kg/m (Succion)

    Carga de Viento (W): Agua Derecha: 75.94 Kg/m (Succin) Agua Izquierda: 88.59 Kg/m (Presin)

    7. DISEO Y MEMORIA DE CLCULO

    De acuerdo al anlisis realizado con SAP 2000 se tienen: 7.1. Diseo de Estructura

  • MEMORIA DE DISEO Y CLCULO ESTRUCTURAL DE TIJERALES 12

    De los resultados que nos proporciona el anlisis estructural, obtenemos los reportes de diseo:

    DFA-COMB1

    Grafica de Ratios de Interaccin Axial-Momento Flector (P-M-M)

    A. TIJERALES BRIDA SUPERIOR L 2X2X1/8:

  • MEMORIA DE DISEO Y CLCULO ESTRUCTURAL DE TIJERALES 13

    Reporte de Diseo de Brida Superior

    BRIDA INFERIOR L 2X2X1/8:

    Reporte de Diseo de Brida Inferior

  • MEMORIA DE DISEO Y CLCULO ESTRUCTURAL DE TIJERALES 14

    MONTANTE L 1X1X1/4:

    Reporte de Diseo de Montantes

    DIAGONAL L 1x1x1/8:

    Reporte de Diseo de Diagonales

  • MEMORIA DE DISEO Y CLCULO ESTRUCTURAL DE TIJERALES 15

    B. VIGA V1: BRIDA SUPERIOR L 2X2X1/4:

    Reporte de Diseo de Brida Superior BRIDA INFERIOR L2X2x1/4

    Reporte de Diseo de Brida Inferior

  • MEMORIA DE DISEO Y CLCULO ESTRUCTURAL DE TIJERALES 16

    MONTANTE L 1x1x1/4

    Reporte de Diseo de Montantes DIAGONAL L 1x1x1/4

    Reporte de Diseo de Diagonales

    C. VIGA V2:

    BRIDA SUPERIOR L 2X2X1/8:

  • MEMORIA DE DISEO Y CLCULO ESTRUCTURAL DE TIJERALES 17

    Reporte de Diseo de Brida Superior

    BRIDA INFERIOR L 2x2x1/8

    Reporte de Diseo de Brida Inferior

  • MEMORIA DE DISEO Y CLCULO ESTRUCTURAL DE TIJERALES 18

    MONTANTE L 1x1x1/8:

    Reporte de Diseo de Montante

    DIAGONAL L1x1x1/8

    Reporte de Diseo de Diagonal

    8. CONCLUSIONES Y RECOMENDACIONES

    o La estructuracin de los tijerales principales y secundarios del presente

    proyecto reemplaza a la que estaba proyectada, la cual de acuerdo al

  • MEMORIA DE DISEO Y CLCULO ESTRUCTURAL DE TIJERALES 19

    anlisis estructural de comprobacin efectuado con el software SAP 2000 no cumple con las solicitaciones de carga.

    o El diseo y calculo estructural utilizados determina que los elementos

    metlicos constitutivos de la estructura se encuentran cumpliendo los requisitos establecidos por las Normas del Reglamento Nacional de Edificaciones E.090 y del AISC (American Institute of Steel Construction) segn los factores de carga y resistencia -LRFD, por tal razn los elementos de los tijerales y las vigas secundarias y columnas se encuentran seguras ante las cargas de peso propio, sobrecargas, viento y/o sismo.

    o Los perfiles utilizados en la composicin de la estructura se encuentran

    trabajando dentro de un rango aceptable.

    o Las vigas secundarias (correas de techo) no presentan mayores exigencias o demandas de carga por lo que se observan valores de ratio bajos.

    o Los perfiles para los tijerales y vigas son los siguientes:

    Perfilera Usada en Tijerales T1: Perfil : L2x2x1/8 (Brida Superior e Inferior) Perfil : L1x1x1/8 (Montantes Y Diagonales)

    Perfilera Usada en Vigas V1: Perfil : L2x2x1/8 (Brida Superior) Perfil : L2x2x1/4 (Brida Inferior) Perfil : L1x1x1/4 (Diagonales y Montantes)

    Perfilera Usada en Vigas V2: Perfil : L2x2x1/8 (Brida Superior e Inferior) Perfil : L2x2x1/8 (Montantes) Perfil : 2L1x1x1/8 (Diagonales y Montantes)

    o Se indica que cualquier variacin en la aplicacion de las normas actuales

    o anomalas respecto a la calidad de los materiales a emplearse y descritos en el presente informe y los planos de dise dejan sin validez las conclusiones aqu presentadas.

  • MEMORIA DE DISEO Y CLCULO ESTRUCTURAL DE TIJERALES 20

    ANEXOS

    PESO DE LA ESTRUCTURA

    TABLE: Frame Section Properties 01 - General

    SectionName Material TotalWt

    Text Text Kgf

    2L1X1/8 A36 688.86

    2L2X1/4 A36 437.71

    2L2x1/8 A36 2204.2

    barra de 5/8 A36 281.41

    L1X1/4 A36 423.35

    Z10X3X3 A653SQGr50 1345.79

    TOTAL 5381.32 REACCIONES GLOBALES

    REACCIONES EN LOS APOYOS NUDO 143

  • MEMORIA DE DISEO Y CLCULO ESTRUCTURAL DE TIJERALES 21

    NUDO 145

    NUDO 147

    NUDO 149

    NUDO 165

    TABLE: Joint ReactionsJoint OutputCase CaseType F1 F2 F3 M1 M2 M3Text Text Text Kgf Kgf Kgf Kgf-m Kgf-m Kgf-m

    143 D LinStatic 0.65 92.34 1216.09 0 0 0143 Sx LinStatic -64.33 0.69 3.82 0 0 0143 W LinStatic -68.06 -5.51 -232.9 0 0 0143 Lr LinStatic -8.07 32.68 1336.71 0 0 0143 W1 LinStatic -15.31 -16.77 -465.34 0 0 0143 Sy LinStatic 1.91 -12.91 -5.99 0 0 0

    TABLE: Joint ReactionsJoint OutputCase CaseType F1 F2 F3 M1 M2 M3Text Text Text Kgf Kgf Kgf Kgf-m Kgf-m Kgf-m

    145 D LinStatic 43.78 44.55 1278.89 0 0 0145 Sx LinStatic -108.37 -1.71 7.48 0 0 0145 W LinStatic -65.41 -9.96 -232.93 0 0 0145 Lr LinStatic 115.95 22.39 889.33 0 0 0145 W1 LinStatic -35 -16.74 -439.28 0 0 0145 Sy LinStatic -40.29 -39.23 3.7 0 0 0

    TABLE: Joint ReactionsJoint OutputCase CaseType F1 F2 F3 M1 M2 M3Text Text Text Kgf Kgf Kgf Kgf-m Kgf-m Kgf-m

    147 D LinStatic -303.65 13.64 1219.44 0 0 0147 Sx LinStatic -107.31 1.85 7.83 0 0 0147 W LinStatic -74.36 -3.67 -238.23 0 0 0147 Lr LinStatic -224.26 1.75 842.27 0 0 0147 W1 LinStatic 82.55 1.59 -421.8 0 0 0147 Sy LinStatic 21.69 -34.89 -1.29 0 0 0

    TABLE: Joint ReactionsJoint OutputCase CaseType F1 F2 F3 M1 M2 M3Text Text Text Kgf Kgf Kgf Kgf-m Kgf-m Kgf-m

    149 D LinStatic 299.87 -109.04 856.44 0 0 0149 Sx LinStatic -113.48 -1.52 9.98 0 0 0149 W LinStatic -59.95 8.83 -232.39 0 0 0149 Lr LinStatic 227.44 -77.9 562.06 0 0 0149 W1 LinStatic -114.35 37.51 -298.14 0 0 0149 Sy LinStatic -23.33 -23.37 0.72 0 0 0

  • MEMORIA DE DISEO Y CLCULO ESTRUCTURAL DE TIJERALES 22

    NUDO 223

    NUDO 224

    NUDO 225

    TABLE: Joint ReactionsJoint OutputCase CaseType F1 F2 F3 M1 M2 M3Text Text Text Kgf Kgf Kgf Kgf-m Kgf-m Kgf-m

    165 D LinStatic -50.58 54.19 1339.3 0 0 0165 Sx LinStatic -108.9 1.34 7.57 0 0 0165 W LinStatic -69.16 -3.99 -231.09 0 0 0165 Lr LinStatic -114.33 45.33 1038.63 0 0 0165 W1 LinStatic 5.74 -27.89 -460.79 0 0 0165 Sy LinStatic 39.86 -39.13 -5.57 0 0 0

    TABLE: Joint ReactionsJoint OutputCase CaseType F1 F2 F3 M1 M2 M3Text Text Text Kgf Kgf Kgf Kgf-m Kgf-m Kgf-m

    223 D LinStatic -2.81 -105.37 127.04 0 0 0223 Sx LinStatic -0.06936 -0.9 0.03242 0 0 0223 W LinStatic 0.43 19.71 -0.7 0 0 0223 Lr LinStatic -2.16 -32.98 0.99 0 0 0223 W1 LinStatic 1.1 19.36 -0.62 0 0 0223 Sy LinStatic -0.03886 -5.66 0.29 0 0 0

    TABLE: Joint ReactionsJoint OutputCase CaseType F1 F2 F3 M1 M2 M3Text Text Text Kgf Kgf Kgf Kgf-m Kgf-m Kgf-m

    224 D LinStatic 2.92 171.33 75.25 0 0 0224 Sx LinStatic -2.69 0.93 0.26 0 0 0224 W LinStatic -0.31 -21.11 -5.73 0 0 0224 Lr LinStatic 2.02 64.51 66.95 0 0 0224 W1 LinStatic -0.97 -32.48 -5.62 0 0 0224 Sy LinStatic -0.06884 -9.49 1.63 0 0 0

    TABLE: Joint ReactionsJoint OutputCase CaseType F1 F2 F3 M1 M2 M3Text Text Text Kgf Kgf Kgf Kgf-m Kgf-m Kgf-m

    225 D LinStatic 0 0 1217.73 0 0 0225 Sx LinStatic 0 0 -5.02 0 0 0225 W LinStatic 0 0 319.58 0 0 0225 Lr LinStatic 0 0 1335.15 0 0 0225 W1 LinStatic 0 0 -334.43 0 0 0225 Sy LinStatic 0 0 -5.04 0 0 0

  • MEMORIA DE DISEO Y CLCULO ESTRUCTURAL DE TIJERALES 23

    NUDO 227

    NUDO 229

    NUDO 231

    NUDO 247

    TABLE: Joint ReactionsJoint OutputCase CaseType F1 F2 F3 M1 M2 M3Text Text Text Kgf Kgf Kgf Kgf-m Kgf-m Kgf-m

    227 D LinStatic 0 0 1288.17 0 0 0227 Sx LinStatic 0 0 -7.17 0 0 0227 W LinStatic 0 0 317.23 0 0 0227 Lr LinStatic 0 0 903.03 0 0 0227 W1 LinStatic 0 0 -315.99 0 0 0227 Sy LinStatic 0 0 0.31 0 0 0

    TABLE: Joint ReactionsJoint OutputCase CaseType F1 F2 F3 M1 M2 M3Text Text Text Kgf Kgf Kgf Kgf-m Kgf-m Kgf-m

    229 D LinStatic 0 0 1205.89 0 0 0229 Sx LinStatic 0 0 -6.78 0 0 0229 W LinStatic 0 0 316.52 0 0 0229 Lr LinStatic 0 0 830.21 0 0 0229 W1 LinStatic 0 0 -288.46 0 0 0229 Sy LinStatic 0 0 -1.31 0 0 0

    TABLE: Joint ReactionsJoint OutputCase CaseType F1 F2 F3 M1 M2 M3Text Text Text Kgf Kgf Kgf Kgf-m Kgf-m Kgf-m

    231 D LinStatic 0 0 870.61 0 0 0231 Sx LinStatic 0 0 -5.12 0 0 0231 W LinStatic 0 0 295.84 0 0 0231 Lr LinStatic 0 0 586.06 0 0 0231 W1 LinStatic 0 0 -186.86 0 0 0231 Sy LinStatic 0 0 3 0 0 0

    TABLE: Joint ReactionsJoint OutputCase CaseType F1 F2 F3 M1 M2 M3Text Text Text Kgf Kgf Kgf Kgf-m Kgf-m Kgf-m

    247 D LinStatic 0 0 1323.64 0 0 0247 Sx LinStatic 0 0 -6.88 0 0 0247 W LinStatic 0 0 318.58 0 0 0247 Lr LinStatic 0 0 1024.06 0 0 0247 W1 LinStatic 0 0 -332.46 0 0 0247 Sy LinStatic 0 0 -2.69 0 0 0

  • MEMORIA DE DISEO Y CLCULO ESTRUCTURAL DE TIJERALES 24

    NUDO 305

    NUDO 306

    TABLE: Joint Reactions Joint OutputCase CaseType F1 F2 F3 M1 M2 M3 Text Text Text Kgf Kgf Kgf Kgf-m Kgf-m Kgf-m 306 D LinStatic -2.19 69.92 71.41 0 0 0 306 Sx LinStatic -2.64 -0.57 -0.05569 0 0 0 306 W LinStatic -0.49 22.59 6.51 0 0 0 306 Lr LinStatic -1.61 -27.35 64.01 0 0 0 306 W1 LinStatic 0.61 8.42 -1.62 0 0 0 306 Sy LinStatic 0.26 -112.23 1.23 0 0 0

    NUDO 379

    TABLE: Joint Reactions Joint OutputCase CaseType F1 F2 F3 M1 M2 M3 Text Text Text Kgf Kgf Kgf Kgf-m Kgf-m Kgf-m 379 D LinStatic 1.14 -4090.44 268.1 0 0 0 379 Sx LinStatic -0.23 21.7 -0.16 0 0 0 379 W LinStatic -0.55 -135.98 1.02 0 0 0 379 Lr LinStatic 0.94 -2873.01 20.71 0 0 0 379 W1 LinStatic -0.54 1236.65 -8.99 0 0 0 379 Sy LinStatic -0.18 -119.52 0.45 0 0 0

    NUDO 380

    TABLE: Joint ReactionsJoint OutputCase CaseType F1 F2 F3 M1 M2 M3Text Text Text Kgf Kgf Kgf Kgf-m Kgf-m Kgf-m

    305 D LinStatic 3.1 -208.56 127.54 0 0 0305 Sx LinStatic -0.15 0.36 -0.005246 0 0 0305 W LinStatic 0.55 -29.34 0.83 0 0 0305 Lr LinStatic 2.3 -128.39 1.52 0 0 0305 W1 LinStatic -0.93 40.53 -0.42 0 0 0305 Sy LinStatic 0.16 -108.47 1.24 0 0 0

    TABLE: Joint ReactionsJoint OutputCase CaseType F1 F2 F3 M1 M2 M3Text Text Text Kgf Kgf Kgf Kgf-m Kgf-m Kgf-m

    380 D LinStatic 0.75 4166.24 1123.51 0 0 0380 Sx LinStatic -7.19 -23.01 -5.41 0 0 0380 W LinStatic 0.35 127.43 33.82 0 0 0380 Lr LinStatic 0.65 2878.83 812.38 0 0 0380 W1 LinStatic -0.17 -1246.28 -303.35 0 0 0380 Sy LinStatic -0.33 -142.51 2.47 0 0 0

  • MEMORIA DE DISEO Y CLCULO ESTRUCTURAL DE TIJERALES 25

    NUDO 387

    NUDO 388

    NUDO 389

    NUDO 390

    TABLE: Joint ReactionsJoint OutputCase CaseType F1 F2 F3 M1 M2 M3Text Text Text Kgf Kgf Kgf Kgf-m Kgf-m Kgf-m

    387 D LinStatic 2.46 -83.87 62.93 0 0 0387 Sx LinStatic -3.85 0.25 -0.18 0 0 0387 W LinStatic -0.15 23.45 -2.77 0 0 0387 Lr LinStatic 0.4 15.32 120.87 0 0 0387 W1 LinStatic -0.24 10.65 -3.81 0 0 0387 Sy LinStatic 0.11 -73.75 2.1 0 0 0

    TABLE: Joint ReactionsJoint OutputCase CaseType F1 F2 F3 M1 M2 M3Text Text Text Kgf Kgf Kgf Kgf-m Kgf-m Kgf-m

    388 D LinStatic -4.441E-16 -2.487E-14 64.57 0 0 0388 Sx LinStatic -3.83 4.649E-16 0 0 0 0388 W LinStatic 0 5.1E-16 0 0 0 0388 Lr LinStatic 0 1.492E-13 114.75 0 0 0388 W1 LinStatic 0 1.932E-14 0 0 0 0388 Sy LinStatic 0 -6.4 0 0 0 0

    TABLE: Joint ReactionsJoint OutputCase CaseType F1 F2 F3 M1 M2 M3Text Text Text Kgf Kgf Kgf Kgf-m Kgf-m Kgf-m

    389 D LinStatic 2.3 -11.92 55.1 0 0 0389 Sx LinStatic -3.17 -1.07 -0.08587 0 0 0389 W LinStatic -0.12 3.76 -1.9 0 0 0389 Lr LinStatic 0.43 13.48 119.73 0 0 0389 W1 LinStatic -0.23 -1.43 -2.79 0 0 0389 Sy LinStatic 0.1 -67.31 2.08 0 0 0

    TABLE: Joint ReactionsJoint OutputCase CaseType F1 F2 F3 M1 M2 M3Text Text Text Kgf Kgf Kgf Kgf-m Kgf-m Kgf-m

    390 D LinStatic 2.27 -3.01 58.9 0 0 0390 Sx LinStatic -4.38 1.65 -0.12 0 0 0390 W LinStatic -0.05803 3.78 -1.19 0 0 0390 Lr LinStatic 0.28 65.33 117.08 0 0 0390 W1 LinStatic -0.17 -13.12 -1.83 0 0 0390 Sy LinStatic 0.15 -91.25 2.68 0 0 0

  • MEMORIA DE DISEO Y CLCULO ESTRUCTURAL DE TIJERALES 26

    NUDO 91

    NUDO 392

    RATIOS DE INTERACCION

    TABLE: Steel Design 1 - Summary Data - AISC-LRFD93 Frame DesignSect DesignType Status Ratio RatioType Combo Text Text Text Text Unitless Text Text

    15 2L1X1/8 Column No Messages 0.803103 PMM COMB2 16 2L1X1/8 Column No Messages 0.735207 PMM COMB2 17 2L1X1/8 Column No Messages 0.574884 PMM COMB2 18 2L1X1/8 Column No Messages 0.557161 PMM COMB3 19 2L1X1/8 Column No Messages 0.348836 PMM COMB3 20 2L1X1/8 Column No Messages 0.260907 PMM COMB3 21 2L1X1/8 Column No Messages 0.059403 PMM COMB5 22 L1X1/4 Column No Messages 0.02665 PMM COMB3 23 2L1X1/8 Column No Messages 0.121459 PMM COMB2 24 2L1X1/8 Column No Messages 0.058969 PMM COMB10 25 2L1X1/8 Column No Messages 0.31581 PMM COMB2 26 2L1X1/8 Column No Messages 0.460374 PMM COMB3 27 2L1X1/8 Column No Messages 0.594718 PMM COMB3 28 2L1X1/8 Column No Messages 0.767383 PMM COMB3 29 2L1X1/8 Column No Messages 0.867087 PMM COMB3 30 2L1X1/8 Column No Messages 0.737081 PMM COMB2 31 2L1X1/8 Column No Messages 0.672727 PMM COMB2

    TABLE: Joint ReactionsJoint OutputCase CaseType F1 F2 F3 M1 M2 M3Text Text Text Kgf Kgf Kgf Kgf-m Kgf-m Kgf-m

    391 D LinStatic -1.332E-15 1.137E-13 66.17 0 0 0391 Sx LinStatic -4.37 0 0 0 0 0391 W LinStatic 0 3.553E-15 0 0 0 0391 Lr LinStatic 0 0 114.75 0 0 0391 W1 LinStatic 0 0 0 0 0 0391 Sy LinStatic 0 -7.3 0 0 0 0

    TABLE: Joint ReactionsJoint OutputCase CaseType F1 F2 F3 M1 M2 M3Text Text Text Kgf Kgf Kgf Kgf-m Kgf-m Kgf-m

    392 D LinStatic -8.882E-16 -5.684E-14 60.02 0 0 0392 Sx LinStatic -3.16 -3.553E-15 0 0 0 0392 W LinStatic 0 -7.105E-15 0 0 0 0392 Lr LinStatic 0 -5.684E-14 114.75 0 0 0392 W1 LinStatic 0 2.842E-14 0 0 0 0392 Sy LinStatic 0 -5.28 0 0 0 0

  • MEMORIA DE DISEO Y CLCULO ESTRUCTURAL DE TIJERALES 27

    32 2L1X1/8 Column No Messages 0.518233 PMM COMB2 33 2L1X1/8 Column No Messages 0.480864 PMM COMB3 34 2L1X1/8 Column No Messages 0.305685 PMM COMB3 35 2L1X1/8 Column No Messages 0.125415 PMM COMB3 36 2L1X1/8 Column No Messages 0.055338 PMM COMB9 37 2L1X1/8 Column No Messages 0.095336 PMM COMB2 38 2L1X1/8 Column No Messages 0.056099 PMM COMB10 39 2L1X1/8 Column No Messages 0.272558 PMM COMB2 40 2L1X1/8 Column No Messages 0.419457 PMM COMB3 41 2L1X1/8 Column No Messages 0.539641 PMM COMB3 42 2L1X1/8 Column No Messages 0.708795 PMM COMB3 43 2L1X1/8 Column No Messages 0.807043 PMM COMB3 44 2L1X1/8 Column No Messages 0.668936 PMM COMB2 45 2L1X1/8 Column No Messages 0.592358 PMM COMB2 46 2L1X1/8 Column No Messages 0.444191 PMM COMB2 47 2L1X1/8 Column No Messages 0.379677 PMM COMB3 48 2L1X1/8 Column No Messages 0.130948 PMM COMB3 49 2L1X1/8 Column No Messages 0.071365 PMM COMB5 50 2L1X1/8 Column No Messages 0.047124 PMM COMB10 51 2L1X1/8 Column No Messages 0.05892 PMM COMB10 52 2L1X1/8 Column No Messages 0.067825 PMM COMB3 53 2L1X1/8 Column No Messages 0.113831 PMM COMB2 54 2L1X1/8 Column No Messages 0.326259 PMM COMB3 55 2L1X1/8 Column No Messages 0.467617 PMM COMB3 56 2L1X1/8 Column No Messages 0.639862 PMM COMB3 57 2L1X1/8 Column No Messages 0.741491 PMM COMB3 58 2L1X1/8 Column No Messages 0.479702 PMM COMB2 59 2L1X1/8 Column No Messages 0.435087 PMM COMB2 60 2L1X1/8 Column No Messages 0.248388 PMM COMB2 61 2L1X1/8 Column No Messages 0.236418 PMM COMB2 62 2L1X1/8 Column No Messages 0.044721 PMM COMB2 63 2L1X1/8 Column No Messages 0.117103 PMM COMB2 64 2L1X1/8 Column No Messages 0.118576 PMM COMB2 65 2L1X1/8 Column No Messages 0.092417 PMM COMB3 66 2L1X1/8 Column No Messages 0.14971 PMM COMB3 67 2L1X1/8 Column No Messages 0.04546 PMM COMB3 68 2L1X1/8 Column No Messages 0.094469 PMM COMB3 69 2L1X1/8 Column No Messages 0.271632 PMM COMB3 70 2L1X1/8 Column No Messages 0.440972 PMM COMB3 71 2L1X1/8 Column No Messages 0.545176 PMM COMB3 72 2L1X1/8 Column Overstressed 2.672067 PMM COMB2 73 2L1X1/8 Column Overstressed 1.988782 PMM COMB2 74 2L1X1/8 Column Overstressed 1.791651 PMM COMB2 75 2L1X1/8 Column Overstressed 1.300229 PMM COMB2 76 2L1X1/8 Column No Messages 0.14548 PMM COMB2 77 2L1X1/8 Column No Messages 0.015494 PMM COMB1

  • MEMORIA DE DISEO Y CLCULO ESTRUCTURAL DE TIJERALES 28

    78 2L1X1/8 Column No Messages 0.009308 PMM COMB8 79 2L1X1/8 Column No Messages 0.004604 PMM COMB8 80 2L1X1/8 Column No Messages 0.028272 PMM COMB2 81 2L1X1/8 Column No Messages 0.028055 PMM COMB2 82 2L1X1/8 Column No Messages 0.13495 PMM COMB2 83 2L1X1/8 Column Overstressed 2.131751 PMM COMB2 84 2L1X1/8 Column No Messages 0.130078 PMM COMB2 85 2L1X1/8 Column No Messages 0.013532 PMM COMB1 86 2L1X1/8 Column No Messages 0.009903 PMM COMB2 87 2L1X1/8 Column No Messages 0.002147 PMM COMB2 88 2L1X1/8 Column No Messages 0.013047 PMM COMB2 89 2L1X1/8 Column No Messages 0.014556 PMM COMB1 90 2L1X1/8 Column No Messages 0.120299 PMM COMB2 91 2L1X1/8 Column No Messages 0.122305 PMM COMB2 92 2L1X1/8 Column No Messages 0.014272 PMM COMB3 93 2L1X1/8 Column No Messages 0.01042 PMM COMB3 94 2L1X1/8 Column No Messages 0.002388 PMM COMB8 95 2L1X1/8 Column No Messages 0.014858 PMM COMB2 96 2L1X1/8 Column No Messages 0.01609 PMM COMB2 97 2L1X1/8 Column No Messages 0.11003 PMM COMB2 98 2L1X1/8 Column No Messages 0.110924 PMM COMB2 99 2L1X1/8 Column No Messages 0.019589 PMM COMB3 100 2L1X1/8 Column No Messages 0.016825 PMM COMB3 101 2L1X1/8 Column No Messages 0.002854 PMM COMB8 102 2L1X1/8 Column No Messages 0.018967 PMM COMB2 103 2L1X1/8 Column No Messages 0.01958 PMM COMB2 104 2L1X1/8 Column No Messages 0.084238 PMM COMB2 105 2L1X1/8 Column No Messages 0.077214 PMM COMB2 106 2L1X1/8 Column No Messages 0.010792 PMM COMB6 107 2L1X1/8 Column No Messages 0.011303 PMM COMB2 108 2L1X1/8 Column No Messages 0.007513 PMM COMB2 109 2L1X1/8 Column No Messages 0.035609 PMM COMB2 110 2L1X1/8 Column No Messages 0.044041 PMM COMB2 111 2L1X1/8 Column No Messages 0.048029 PMM COMB2 112 2L1X1/8 Column No Messages 0.053013 PMM COMB2 113 2L1X1/8 Column Overstressed 2.878829 PMM COMB3 114 2L1X1/8 Column Overstressed 2.162824 PMM COMB3 115 2L1X1/8 Column Overstressed 1.96068 PMM COMB3 116 2L1X1/8 Column Overstressed 1.465237 PMM COMB3 117 2L1X1/8 Column No Messages 0.155322 PMM COMB3 118 2L1X1/8 Column No Messages 0.01564 PMM COMB3 119 2L1X1/8 Column No Messages 0.007507 PMM COMB7 120 2L1X1/8 Column No Messages 0.004799 PMM COMB3 121 2L1X1/8 Column No Messages 0.031964 PMM COMB3 122 2L1X1/8 Column No Messages 0.030742 PMM COMB3 123 2L1X1/8 Column No Messages 0.145724 PMM COMB3

  • MEMORIA DE DISEO Y CLCULO ESTRUCTURAL DE TIJERALES 29

    124 2L1X1/8 Column Overstressed 2.28963 PMM COMB3 125 2L1X1/8 Column No Messages 0.139647 PMM COMB3 126 2L1X1/8 Column No Messages 0.013932 PMM COMB1 127 2L1X1/8 Column No Messages 0.010731 PMM COMB3 128 2L1X1/8 Column No Messages 0.003164 PMM COMB3 129 2L1X1/8 Column No Messages 0.013392 PMM COMB3 130 2L1X1/8 Column No Messages 0.014199 PMM COMB3 131 2L1X1/8 Column No Messages 0.129838 PMM COMB3 132 2L1X1/8 Column No Messages 0.132098 PMM COMB3 133 2L1X1/8 Column No Messages 0.014367 PMM COMB2 134 2L1X1/8 Column No Messages 0.010951 PMM COMB2 135 2L1X1/8 Column No Messages 0.003059 PMM COMB18 136 2L1X1/8 Column No Messages 0.016473 PMM COMB3 137 2L1X1/8 Column No Messages 0.017302 PMM COMB3 138 2L1X1/8 Column No Messages 0.120915 PMM COMB3 139 2L1X1/8 Column No Messages 0.120579 PMM COMB3 140 2L1X1/8 Column No Messages 0.020773 PMM COMB3 141 2L1X1/8 Column No Messages 0.017841 PMM COMB3 142 2L1X1/8 Column No Messages 0.004358 PMM COMB3 143 2L1X1/8 Column No Messages 0.019683 PMM COMB3 144 2L1X1/8 Column No Messages 0.019457 PMM COMB2 145 2L1X1/8 Column No Messages 0.092697 PMM COMB3 146 2L1X1/8 Column No Messages 0.086996 PMM COMB3 147 2L1X1/8 Column No Messages 0.011934 PMM COMB3 148 2L1X1/8 Column No Messages 0.012913 PMM COMB3 149 2L1X1/8 Column No Messages 0.007952 PMM COMB3 150 2L1X1/8 Column No Messages 0.037547 PMM COMB3 151 2L1X1/8 Column No Messages 0.046028 PMM COMB3 152 2L1X1/8 Column No Messages 0.049933 PMM COMB3 153 2L1X1/8 Column No Messages 0.054011 PMM COMB3 154 L1X1/4 Column No Messages 0.039538 PMM COMB1 155 L1X1/4 Column No Messages 0.034837 PMM COMB1 156 L1X1/4 Column No Messages 0.027645 PMM COMB1 157 L1X1/4 Column No Messages 0.007907 PMM COMB1 158 L1X1/4 Column No Messages 0.012634 PMM COMB11 159 L1X1/4 Column No Messages 0.018622 PMM COMB11 160 L1X1/4 Column No Messages 0.022659 PMM COMB11 161 L1X1/4 Column No Messages 0.03619 PMM COMB3 162 L1X1/4 Column No Messages 0.05882 PMM COMB3 163 L1X1/4 Column No Messages 0.055609 PMM COMB3 164 L1X1/4 Column No Messages 0.048632 PMM COMB3 165 L1X1/4 Column No Messages 0.012578 PMM COMB3 166 L1X1/4 Column No Messages 0.016041 PMM COMB3 167 L1X1/4 Column No Messages 0.014071 PMM COMB3 168 L1X1/4 Column No Messages 0.016263 PMM COMB3 169 L1X1/4 Column No Messages 0.047317 PMM COMB3

  • MEMORIA DE DISEO Y CLCULO ESTRUCTURAL DE TIJERALES 30

    170 L1X1/4 Column No Messages 0.057519 PMM COMB3 171 L1X1/4 Column No Messages 0.053759 PMM COMB3 172 L1X1/4 Column No Messages 0.046919 PMM COMB3 173 L1X1/4 Column No Messages 0.01237 PMM COMB3 174 L1X1/4 Column No Messages 0.015384 PMM COMB3 175 L1X1/4 Column No Messages 0.01339 PMM COMB3 176 L1X1/4 Column No Messages 0.017657 PMM COMB3 177 L1X1/4 Column No Messages 0.113342 PMM COMB3 178 L1X1/4 Column No Messages 0.025194 PMM COMB3 179 L1X1/4 Column No Messages 0.020718 PMM COMB3 180 L1X1/4 Column No Messages 0.022705 PMM COMB3 181 L1X1/4 Column No Messages 0.015662 PMM COMB3 182 L1X1/4 Column No Messages 0.061443 PMM COMB3 183 L1X1/4 Column No Messages 0.069868 PMM COMB3 184 L1X1/4 Column No Messages 0.069715 PMM COMB2 185 L1X1/4 Column No Messages 0.042601 PMM COMB3 186 L1X1/4 Column No Messages 0.157432 PMM COMB3 187 L1X1/4 Column No Messages 0.159335 PMM COMB3 188 L1X1/4 Column No Messages 0.158607 PMM COMB3 189 L1X1/4 Column No Messages 0.080133 PMM COMB3 190 L1X1/4 Column No Messages 0.05472 PMM COMB2 191 L1X1/4 Column No Messages 0.671917 PMM COMB3 192 L1X1/4 Column No Messages 0.666676 PMM COMB3 193 L1X1/4 Column No Messages 0.651117 PMM COMB3 196 2L2x1/8 Brace No Messages 0.667426 PMM COMB2 197 2L2x1/8 Brace No Messages 0.658212 PMM COMB2 198 2L2x1/8 Brace No Messages 0.609683 PMM COMB2 199 2L2x1/8 Brace No Messages 0.601478 PMM COMB2 200 2L2x1/8 Brace No Messages 0.503292 PMM COMB2 201 2L2x1/8 Brace No Messages 0.514491 PMM COMB2 202 2L2x1/8 Brace No Messages 0.33047 PMM COMB2 203 2L2x1/8 Brace No Messages 0.336366 PMM COMB3 225 2L1X1/8 Brace No Messages 0.370779 PMM COMB5 226 2L1X1/8 Brace No Messages 0.119161 PMM COMB6 227 2L1X1/8 Brace No Messages 0.086525 PMM COMB2 228 2L1X1/8 Brace No Messages 0.129301 PMM COMB2 229 2L1X1/8 Brace No Messages 0.334751 PMM COMB3 230 2L1X1/8 Brace No Messages 0.456285 PMM COMB3 231 2L1X1/8 Brace No Messages 0.64517 PMM COMB3 232 2L1X1/8 Brace No Messages 0.711657 PMM COMB3 233 2L1X1/8 Brace No Messages 0.331659 PMM COMB10 234 2L1X1/8 Brace No Messages 0.209151 PMM COMB10 235 2L1X1/8 Brace No Messages 0.095099 PMM COMB3 236 2L1X1/8 Brace No Messages 0.166058 PMM COMB3 237 2L1X1/8 Brace No Messages 0.339025 PMM COMB3 238 2L1X1/8 Brace No Messages 0.459357 PMM COMB2

  • MEMORIA DE DISEO Y CLCULO ESTRUCTURAL DE TIJERALES 31

    239 2L1X1/8 Brace No Messages 0.598932 PMM COMB2 240 2L1X1/8 Brace No Messages 0.655012 PMM COMB2 241 2L1X1/8 Brace No Messages 0.396104 PMM COMB5 242 2L1X1/8 Brace No Messages 0.122757 PMM COMB5 243 2L1X1/8 Brace No Messages 0.076525 PMM COMB2 244 2L1X1/8 Brace No Messages 0.120142 PMM COMB2 245 2L1X1/8 Brace No Messages 0.292267 PMM COMB3 246 2L1X1/8 Brace No Messages 0.407373 PMM COMB3 247 2L1X1/8 Brace No Messages 0.58797 PMM COMB3 248 2L1X1/8 Brace No Messages 0.653365 PMM COMB3 249 2L1X1/8 Brace No Messages 0.32395 PMM COMB10 250 2L1X1/8 Brace No Messages 0.111911 PMM COMB10 251 2L1X1/8 Brace No Messages 0.085916 PMM COMB3 252 2L1X1/8 Brace No Messages 0.139184 PMM COMB3 253 2L1X1/8 Brace No Messages 0.294608 PMM COMB3 254 2L1X1/8 Brace No Messages 0.405352 PMM COMB2 255 2L1X1/8 Brace No Messages 0.537866 PMM COMB2 256 2L1X1/8 Brace No Messages 0.594074 PMM COMB2 257 2L1X1/8 Brace No Messages 0.521325 PMM COMB3 258 2L1X1/8 Brace No Messages 0.329804 PMM COMB5 259 2L1X1/8 Brace No Messages 0.054064 PMM COMB2 260 2L1X1/8 Brace No Messages 0.091986 PMM COMB2 261 2L1X1/8 Brace No Messages 0.252016 PMM COMB3 262 2L1X1/8 Brace No Messages 0.367964 PMM COMB3 263 2L1X1/8 Brace No Messages 0.544679 PMM COMB3 264 2L1X1/8 Brace No Messages 0.613545 PMM COMB3 265 2L1X1/8 Brace No Messages 0.366415 PMM COMB10 266 2L1X1/8 Brace No Messages 0.260163 PMM COMB10 267 2L1X1/8 Brace No Messages 0.056954 PMM COMB5 268 2L1X1/8 Brace No Messages 0.103333 PMM COMB3 269 2L1X1/8 Brace No Messages 0.252821 PMM COMB3 270 2L1X1/8 Brace No Messages 0.355851 PMM COMB2 271 2L1X1/8 Brace No Messages 0.48936 PMM COMB2 272 2L1X1/8 Brace No Messages 0.548084 PMM COMB2 273 2L1X1/8 Brace No Messages 0.860582 PMM COMB3 274 2L1X1/8 Brace No Messages 0.73083 PMM COMB3 275 2L1X1/8 Brace No Messages 0.316456 PMM COMB3 276 2L1X1/8 Brace No Messages 0.051535 PMM COMB5 277 2L1X1/8 Brace No Messages 0.086088 PMM COMB3 278 2L1X1/8 Brace No Messages 0.129748 PMM COMB3 279 2L1X1/8 Brace No Messages 0.375661 PMM COMB3 280 2L1X1/8 Brace No Messages 0.447348 PMM COMB3 281 2L1X1/8 Brace No Messages 0.69323 PMM COMB2 282 2L1X1/8 Brace No Messages 0.610135 PMM COMB2 283 2L1X1/8 Brace No Messages 0.128333 PMM COMB2 284 2L1X1/8 Brace No Messages 0.070417 PMM COMB3

  • MEMORIA DE DISEO Y CLCULO ESTRUCTURAL DE TIJERALES 32

    285 2L1X1/8 Brace No Messages 0.069279 PMM COMB3 286 2L1X1/8 Brace No Messages 0.152108 PMM COMB2 287 2L1X1/8 Brace No Messages 0.333072 PMM COMB2 288 2L1X1/8 Brace No Messages 0.393689 PMM COMB2 289 2L1X1/8 Brace No Messages 0.171434 PMM COMB2 290 2L1X1/8 Brace No Messages 0.015712 PMM COMB2 291 2L1X1/8 Brace No Messages 0.008325 PMM COMB1 292 2L1X1/8 Brace No Messages 0.021359 PMM COMB2 293 2L1X1/8 Brace No Messages 0.022092 PMM COMB2 294 2L1X1/8 Brace No Messages 0.011273 PMM COMB1 295 2L1X1/8 Brace No Messages 0.017566 PMM COMB2 296 2L1X1/8 Brace No Messages 0.150536 PMM COMB2 297 2L1X1/8 Brace No Messages 0.154641 PMM COMB2 298 2L1X1/8 Brace No Messages 0.017472 PMM COMB2 299 2L1X1/8 Brace No Messages 0.009813 PMM COMB1 300 2L1X1/8 Brace No Messages 0.010887 PMM COMB3 301 2L1X1/8 Brace No Messages 0.009822 PMM COMB3 302 2L1X1/8 Brace No Messages 0.009979 PMM COMB1 303 2L1X1/8 Brace No Messages 0.015988 PMM COMB2 304 2L1X1/8 Brace No Messages 0.141437 PMM COMB2 305 2L1X1/8 Brace No Messages 0.146819 PMM COMB2 306 2L1X1/8 Brace No Messages 0.017121 PMM COMB2 307 2L1X1/8 Brace No Messages 0.010091 PMM COMB1 308 2L1X1/8 Brace No Messages 0.015087 PMM COMB3 309 2L1X1/8 Brace No Messages 0.013843 PMM COMB3 310 2L1X1/8 Brace No Messages 0.009735 PMM COMB1 311 2L1X1/8 Brace No Messages 0.015029 PMM COMB2 312 2L1X1/8 Brace No Messages 0.128751 PMM COMB2 313 2L1X1/8 Brace No Messages 0.127665 PMM COMB2 314 2L1X1/8 Brace No Messages 0.016621 PMM COMB2 315 2L1X1/8 Brace No Messages 0.010628 PMM COMB1 316 2L1X1/8 Brace No Messages 0.023061 PMM COMB2 317 2L1X1/8 Brace No Messages 0.02173 PMM COMB2 318 2L1X1/8 Brace No Messages 0.009482 PMM COMB1 319 2L1X1/8 Brace No Messages 0.013076 PMM COMB2 320 2L1X1/8 Brace No Messages 0.080707 PMM COMB2 321 2L1X1/8 Brace No Messages 0.031897 PMM COMB2 322 2L1X1/8 Brace No Messages 0.032528 PMM COMB2 323 2L1X1/8 Brace No Messages 0.011852 PMM COMB2 324 2L1X1/8 Brace No Messages 0.013949 PMM COMB2 325 2L1X1/8 Brace No Messages 0.015554 PMM COMB2 326 2L1X1/8 Brace No Messages 0.007434 PMM COMB1 327 2L1X1/8 Brace No Messages 0.011854 PMM COMB2 328 2L1X1/8 Brace No Messages 0.108455 PMM COMB2 329 2L1X1/8 Brace No Messages 0.192342 PMM COMB3 330 2L1X1/8 Brace No Messages 0.016381 PMM COMB3

  • MEMORIA DE DISEO Y CLCULO ESTRUCTURAL DE TIJERALES 33

    331 2L1X1/8 Brace No Messages 0.008169 PMM COMB1 332 2L1X1/8 Brace No Messages 0.024503 PMM COMB3 333 2L1X1/8 Brace No Messages 0.025331 PMM COMB3 334 2L1X1/8 Brace No Messages 0.011578 PMM COMB1 335 2L1X1/8 Brace No Messages 0.018392 PMM COMB3 336 2L1X1/8 Brace No Messages 0.162918 PMM COMB3 337 2L1X1/8 Brace No Messages 0.170323 PMM COMB3 338 2L1X1/8 Brace No Messages 0.018252 PMM COMB3 339 2L1X1/8 Brace No Messages 0.010002 PMM COMB1 340 2L1X1/8 Brace No Messages 0.011029 PMM COMB3 341 2L1X1/8 Brace No Messages 0.009483 PMM COMB2 342 2L1X1/8 Brace No Messages 0.009804 PMM COMB1 343 2L1X1/8 Brace No Messages 0.016588 PMM COMB3 344 2L1X1/8 Brace No Messages 0.152016 PMM COMB3 345 2L1X1/8 Brace No Messages 0.17238 PMM COMB3 346 2L1X1/8 Brace No Messages 0.01801 PMM COMB3 347 2L1X1/8 Brace No Messages 0.010137 PMM COMB1 348 2L1X1/8 Brace No Messages 0.015585 PMM COMB3 349 2L1X1/8 Brace No Messages 0.0144 PMM COMB3 350 2L1X1/8 Brace No Messages 0.009771 PMM COMB1 351 2L1X1/8 Brace No Messages 0.015799 PMM COMB3 352 2L1X1/8 Brace No Messages 0.145525 PMM COMB3 353 2L1X1/8 Brace No Messages 0.142651 PMM COMB3 354 2L1X1/8 Brace No Messages 0.017483 PMM COMB3 355 2L1X1/8 Brace No Messages 0.01066 PMM COMB1 356 2L1X1/8 Brace No Messages 0.023711 PMM COMB3 357 2L1X1/8 Brace No Messages 0.022535 PMM COMB3 358 2L1X1/8 Brace No Messages 0.00948 PMM COMB1 359 2L1X1/8 Brace No Messages 0.013704 PMM COMB3 360 2L1X1/8 Brace No Messages 0.08054 PMM COMB3 361 2L1X1/8 Brace No Messages 0.033146 PMM COMB3 362 2L1X1/8 Brace No Messages 0.032938 PMM COMB3 363 2L1X1/8 Brace No Messages 0.012159 PMM COMB3 364 2L1X1/8 Brace No Messages 0.014254 PMM COMB3 365 2L1X1/8 Brace No Messages 0.015793 PMM COMB3 366 2L1X1/8 Brace No Messages 0.007195 PMM COMB1 367 2L1X1/8 Brace No Messages 0.012659 PMM COMB3 368 2L1X1/8 Brace No Messages 0.1446 PMM COMB3 369 L1X1/4 Brace No Messages 0.016528 PMM COMB1 370 L1X1/4 Brace No Messages 0.027749 PMM COMB1 371 L1X1/4 Brace No Messages 0.016617 PMM COMB1 372 L1X1/4 Brace No Messages 0.018686 PMM COMB1 373 L1X1/4 Brace No Messages 0.029336 PMM COMB6 374 L1X1/4 Brace No Messages 0.018251 PMM COMB1 375 L1X1/4 Brace No Messages 0.013121 PMM COMB11 376 L1X1/4 Brace No Messages 0.025605 PMM COMB5

  • MEMORIA DE DISEO Y CLCULO ESTRUCTURAL DE TIJERALES 34

    377 L1X1/4 Brace No Messages 0.019779 PMM COMB3 378 L1X1/4 Brace No Messages 0.050051 PMM COMB3 379 L1X1/4 Brace No Messages 0.021174 PMM COMB3 380 L1X1/4 Brace No Messages 0.023177 PMM COMB3 381 L1X1/4 Brace No Messages 0.030267 PMM COMB5 382 L1X1/4 Brace No Messages 0.042777 PMM COMB3 383 L1X1/4 Brace No Messages 0.036015 PMM COMB3 384 L1X1/4 Brace No Messages 0.036446 PMM COMB3 385 L1X1/4 Brace No Messages 0.019165 PMM COMB3 386 L1X1/4 Brace No Messages 0.047499 PMM COMB3 387 L1X1/4 Brace No Messages 0.020254 PMM COMB3 388 L1X1/4 Brace No Messages 0.022278 PMM COMB3 389 L1X1/4 Brace No Messages 0.031924 PMM COMB5 390 L1X1/4 Brace No Messages 0.040294 PMM COMB3 391 L1X1/4 Brace No Messages 0.034096 PMM COMB3 392 L1X1/4 Brace No Messages 0.034169 PMM COMB3 393 L1X1/4 Brace No Messages 0.064111 PMM COMB3 394 L1X1/4 Brace No Messages 0.02397 PMM COMB3 395 L1X1/4 Brace No Messages 0.05662 PMM COMB3 396 L1X1/4 Brace No Messages 0.049784 PMM COMB3 397 L1X1/4 Brace No Messages 0.043829 PMM COMB3 398 L1X1/4 Brace No Messages 0.024357 PMM COMB3 399 L1X1/4 Brace No Messages 0.026593 PMM COMB3 400 L1X1/4 Brace No Messages 0.030948 PMM COMB2 401 L1X1/4 Brace No Messages 0.893481 PMM COMB2 402 L1X1/4 Brace No Messages 0.861938 PMM COMB2 403 L1X1/4 Brace No Messages 0.845371 PMM COMB2 404 L1X1/4 Brace No Messages 0.830901 PMM COMB3 405 L1X1/4 Brace No Messages 0.120728 PMM COMB3 406 L1X1/4 Brace No Messages 0.121208 PMM COMB3 407 L1X1/4 Brace No Messages 0.123784 PMM COMB3 408 L1X1/4 Brace No Messages 0.221632 PMM COMB3 421 barra de 5/8 Brace See WarnMsg 0.644022 PMM COMB1 422 barra de 5/8 Brace See WarnMsg 0.644008 PMM COMB1 423 barra de 5/8 Brace See WarnMsg 0.644022 PMM COMB1 424 barra de 5/8 Brace See WarnMsg 0.644029 PMM COMB1 425 barra de 5/8 Brace See WarnMsg 0.644027 PMM COMB1 426 barra de 5/8 Brace See WarnMsg 0.644027 PMM COMB1 427 barra de 5/8 Brace See WarnMsg 0.644015 PMM COMB1 428 barra de 5/8 Brace See WarnMsg 0.644018 PMM COMB1 429 barra de 5/8 Brace See WarnMsg 0.644026 PMM COMB1 430 barra de 5/8 Brace See WarnMsg 0.65042 PMM COMB1 431 barra de 5/8 Brace See WarnMsg 0.644036 PMM COMB1 432 barra de 5/8 Brace See WarnMsg 0.644001 PMM COMB1 433 barra de 5/8 Brace See WarnMsg 0.644016 PMM COMB1 434 barra de 5/8 Brace See WarnMsg 0.644027 PMM COMB1

  • MEMORIA DE DISEO Y CLCULO ESTRUCTURAL DE TIJERALES 35

    435 barra de 5/8 Brace See WarnMsg 0.64402 PMM COMB1 436 barra de 5/8 Brace See WarnMsg 0.644009 PMM COMB1 195 2L2X1/4 Beam No Messages 0.030864 PMM COMB17 204 2L2X1/4 Beam No Messages 0.044977 PMM COMB3 209 2L2X1/4 Beam No Messages 0.069466 PMM COMB3 210 2L2X1/4 Beam No Messages 0.073312 PMM COMB3 211 2L2X1/4 Beam No Messages 0.502861 PMM COMB3 222 2L2x1/8 Beam See WarnMsg 0.059669 PMM COMB2 223 2L2x1/8 Beam See WarnMsg 0.047553 PMM COMB2 224 2L2x1/8 Beam See WarnMsg 0.050489 PMM COMB2 409 2L2x1/8 Beam See WarnMsg 0.049231 PMM COMB2 410 2L2x1/8 Beam No Messages 0.032335 PMM COMB2 411 2L2x1/8 Beam See WarnMsg 0.352564 PMM COMB2 413 2L2x1/8 Beam See WarnMsg 0.338577 PMM COMB2 414 2L2x1/8 Beam See WarnMsg 0.319382 PMM COMB2 415 2L2x1/8 Beam See WarnMsg 0.286672 PMM COMB2 416 2L2x1/8 Beam See WarnMsg 0.215141 PMM COMB2 417 2L2X1/4 Beam No Messages 0.03442 PMM COMB1 437 2L2X1/4 Beam No Messages 0.051246 PMM COMB3 438 2L2X1/4 Beam No Messages 0.086408 PMM COMB3 439 2L2X1/4 Beam No Messages 0.107 PMM COMB3 440 2L2X1/4 Beam No Messages 0.660719 PMM COMB3 441 2L2x1/8 Beam See WarnMsg 0.055338 PMM COMB3 442 2L2x1/8 Beam See WarnMsg 0.049763 PMM COMB3 443 2L2x1/8 Beam See WarnMsg 0.051514 PMM COMB3 444 2L2x1/8 Beam See WarnMsg 0.051508 PMM COMB3 445 2L2x1/8 Beam See WarnMsg 0.035322 PMM COMB3 446 2L2x1/8 Beam See WarnMsg 0.295227 PMM COMB3 447 2L2x1/8 Beam See WarnMsg 0.311168 PMM COMB3 448 2L2x1/8 Beam See WarnMsg 0.288113 PMM COMB3 449 2L2x1/8 Beam See WarnMsg 0.279092 PMM COMB3 450 2L2x1/8 Beam See WarnMsg 0.204166 PMM COMB3 412 2L2x1/8 Beam No Messages 0.434729 PMM COMB2 418 2L2x1/8 Beam No Messages 0.456688 PMM COMB3 419 2L2x1/8 Beam No Messages 0.407859 PMM COMB2 455 2L2x1/8 Beam No Messages 0.42951 PMM COMB3 456 2L2x1/8 Beam No Messages 0.335831 PMM COMB2 457 2L2x1/8 Beam No Messages 0.358719 PMM COMB3 458 2L2x1/8 Beam No Messages 0.214383 PMM COMB2 459 2L2x1/8 Beam No Messages 0.189508 PMM COMB3 460 barra de 5/8 Beam See WarnMsg 0.658558 PMM COMB1 461 barra de 5/8 Beam See WarnMsg 0.652391 PMM COMB1 462 barra de 5/8 Beam See WarnMsg 0.643584 PMM COMB1 463 barra de 5/8 Beam See WarnMsg 0.646622 PMM COMB1 464 barra de 5/8 Beam See WarnMsg 0.647189 PMM COMB1 465 barra de 5/8 Beam See WarnMsg 0.643591 PMM COMB1

  • MEMORIA DE DISEO Y CLCULO ESTRUCTURAL DE TIJERALES 36

    466 barra de 5/8 Beam See WarnMsg 0.643585 PMM COMB1 467 barra de 5/8 Beam See WarnMsg 0.643626 PMM COMB1 468 barra de 5/8 Beam See WarnMsg 0.647941 PMM COMB1 469 barra de 5/8 Beam See WarnMsg 0.643605 PMM COMB1 470 barra de 5/8 Beam See WarnMsg 0.648596 PMM COMB1 471 barra de 5/8 Beam See WarnMsg 0.652445 PMM COMB1 472 barra de 5/8 Beam See WarnMsg 0.650261 PMM COMB1 473 barra de 5/8 Beam See WarnMsg 0.650844 PMM COMB1 474 barra de 5/8 Beam See WarnMsg 0.643592 PMM COMB1 475 barra de 5/8 Beam See WarnMsg 0.643581 PMM COMB1 205 2L1X1/8 Column No Messages 0.879206 PMM COMB2 206 2L1X1/8 Column No Messages 0.796624 PMM COMB2 207 2L1X1/8 Column No Messages 0.607625 PMM COMB2 208 2L1X1/8 Column No Messages 0.511416 PMM COMB3 476 2L1X1/8 Column No Messages 0.351506 PMM COMB3 477 2L1X1/8 Column No Messages 0.259757 PMM COMB3 478 2L1X1/8 Column No Messages 0.081269 PMM COMB6 479 2L1X1/8 Column No Messages 0.114584 PMM COMB2 480 2L1X1/8 Column No Messages 0.076641 PMM COMB10 481 2L1X1/8 Column No Messages 0.323034 PMM COMB2 482 2L1X1/8 Column No Messages 0.508193 PMM COMB3 483 2L1X1/8 Column No Messages 0.632704 PMM COMB3 484 2L1X1/8 Column No Messages 0.827732 PMM COMB3 485 2L1X1/8 Column No Messages 0.941179 PMM COMB3 486 2L2x1/8 Brace No Messages 0.736807 PMM COMB2 487 2L2x1/8 Brace No Messages 0.720871 PMM COMB2 488 2L1X1/8 Brace No Messages 0.343256 PMM COMB3 489 2L1X1/8 Brace No Messages 0.076869 PMM COMB5 490 2L1X1/8 Brace No Messages 0.080094 PMM COMB2 491 2L1X1/8 Brace No Messages 0.132811 PMM COMB2 492 2L1X1/8 Brace No Messages 0.353981 PMM COMB3 493 2L1X1/8 Brace No Messages 0.475776 PMM COMB3 494 2L1X1/8 Brace No Messages 0.676902 PMM COMB3 495 2L1X1/8 Brace No Messages 0.788738 PMM COMB3 496 2L1X1/8 Brace No Messages 0.259688 PMM COMB10 497 2L1X1/8 Brace No Messages 0.086758 PMM COMB10 498 2L1X1/8 Brace No Messages 0.098474 PMM COMB3 499 2L1X1/8 Brace No Messages 0.144756 PMM COMB3 500 2L1X1/8 Brace No Messages 0.351185 PMM COMB3 501 2L1X1/8 Brace No Messages 0.454978 PMM COMB2 502 2L1X1/8 Brace No Messages 0.640045 PMM COMB2 503 2L1X1/8 Brace No Messages 0.727956 PMM COMB2 504 2L2x1/8 Beam See WarnMsg 0.493057 PMM COMB2 505 2L2x1/8 Beam See WarnMsg 0.514464 PMM COMB3

    1. GENERALIDADES1.1. Objetivo:1.2. Descripcin de la Estructura:1.3. Normatividad

    2. PROCEDIMIENTO DE DISEO2.1. Control de Deflexiones:2.2. Control de Ratios de Interaccin (P-Mx-My):

    3. CONSIDERACIONES SSMICAS3.1. Zonificacin (Z)3.2. Parmetros del Suelo (S)3.3. Factor de amplificacin Ssmica (C)3.4. Categora de las edificaciones (U)3.5. Coeficiente de Reduccin de Fuerza Ssmica (R)3.6. Anlisis Ssmico Esttico

    4. ESTADOS DE CARGA4.1. Cargas por peso propio (D):4.2. Sobrecargas (Lr):4.3. Cargas producidas por sismo (E):4.4. Cargas producidas por viento (W):

    5. COMBINACIONES DE CARGAS6. ANLISIS ESTRUCTURAL6.1. Modelo Estructural Adoptado6.2. Introduccin Grfica de Cargas al SAP 2000 v.14:

    7. DISEO Y MEMORIA DE CLCULO7.1. Diseo de Estructura

    8. CONCLUSIONES Y RECOMENDACIONES